Vibration Eliminators

Refrigeration Connectors Bulletin No. 302

Table 1 Anaconda Bronze Vibration Eliminators with Female Copper Tube Ends Nominal Copper Tube Size 1/8 1/4 3/8 1/2 5/8 5/8 3/4 1 1-1/4 1

Actual Tube O.D. in.(mm) 1/4 (6.4) 3/8 (9.5) 1/2 (12.7) 5/8 (15.9) 3/4 (19.0) 3/4 (19.0) 7/8 (22.2) 1-1/8 (28.6) 1-3/8 (34.9) 2

Model Number 1418FZ 5614FZ 3838FZ 1212FY 1258FY 3458FY 3434FY 1010FY 5454FY 3

Maximum Operating Pressure psig(barg) 700 (47) 700 (47) 500 (33) 450 (30) 450 (30) 450 (30) 450 (30) 450 (30) 500 (33)

Flexible Hose I.D. in.(mm) 1/4 (6.4) 5/16 (7.9) 3/8 (9.5) 1/2 (12.7) 1/2 (12.7) 3/4 (19.0) 3/4 (19.0) 1 (25.4) 1-1/4 (31.8)

Overall Length (+/-1/4) in.(mm) 7-1/2 (191) 8-1/4 (210) 9 (229) 9-3/4 (248) 10 (254) 11-1/4 (286) 11-1/2 (292) 13 (330) 14-3/4 (375)

4

5

6

Maximum Outside Diameter in.(mm) 0.63 (15.9) 0.75 (19.0) 0.88 (22.2) 1.13 (28.60 1.13 (28.6) 1.50 (38.1) 1.50 (38.1) 1.88 (47.6) 2.25 (57.2) 7

Tube End Length (+/-1/8) in.(mm) 0.50 (12.7) 0.63 (15.9) 0.75 (19.0) 0.88 (22.2) 1.00 (25.4) 1.13 (28.6) 1.25 (31.8) 1.50 (38.1) 1.63 (41.3) 8

Part Identification Number (PIN) Bagged/Boxed 210073 211073 210093 211093 210113 211113 210132 211132 210142 211142 210152 211152 210162 211162 210172 211172 210192 211192 9

Weight lbs(kgs) .10(.05) .12(.05) .15(.07) .16(.07) .25(.11) .28(.13) .45(.20) .47(.21) .50(.23) .54(.24) .85(.39) .95(.43) .90(.41) 1.00(.45) 1.25(.57) 1.35(.61) 2.30(1.04) 2.40(1.09) 10

Refer to the Notes on Page 3

SUITABLE FOR USE WITH THE FOLLOWING REFRIGERANTS R12 R125 R401B R404A R407C R410A R502 R22 R134A R402A R407A R408A R410B R507 R23 R401A R402B R407B R409A R412A R508 R509 NOT FOR USE WITH AMMONIA Refrigerant saturation pressure at 125ºF(52ºC) maximum and 80ºF(27ºC) minimum must be equal to or less than the design pressure.

ORDERING INSTRUCTIONS Vibration Eliminators can be ordered by indicating the Model Number (column 3), if they are bagged or boxed, or by the Part Identification Number (PIN) in Column 9.

Vibration Eliminators

Table 2 Anaconda Stainless Steel Vibration Eliminators with Female Copper Tube Ends Nominal Copper Tube Size 1-1/2 2 2-1/2 3 3-1/2 4 1

Actual Tube O. D. in. (mm) 1-5/8 (41.3) 2-1/8 (54.0) 2-5/8 (66.7) 3-1/8 (79.4) 3-5/8 (92.0) 4-1/8 (104.8) 2

Model Number 6464FS 2020FS 5252FS 3030FS 7272FS 4040FS 3

Maximum Operating Pressure psig(barg) 400 (27) 360 (24) 300 (20) 300 (20) 150 (10) 150 (10) 4

Flexible Hose I. D. in. (mm) 1-1/2 (38) 2 (50) 2-1/2 (64) 3 (76) 3-1/2 (89) 4 (102) 5

Overall Length (+/-1/4) in. (mm) 17.0 (432) 20.0 (508) 24.0 (610) 27.0 (686) 23.0 (584) 25.0 (635) 6

Maximum Outside Diameter in. (mm) 2.38 (60) 3.25 (83) 3.88 (99) 4.50 (114) 4.94 (125) 5.75 (146) 7

Tube End Length (+/-1/8) in. (mm) 2.00 (50) 2.50 (64) 3.00 (76) 3.50 (89) 3.19 (82) 4.38 (111) 8

Part Identification Number (PIN) Bagged/Boxed 212200 212200BX 212220 212220BX 212240 212240BX 212260 212260BX 210280 211280 210300 211300 9

Weight lbs(kgs) 2.2(1.0) 2.4(1.1) 3.6(1.6) 4.0(1.8) 5.2(2.4) 5.7(2.6) 10.5(4.7) 11.0(5.0) 7.6(3.4) 8.1(3.7) 9.5(4.3) 10.2(4.6) 10

NOTES 1. The designs tabulated are recognized under the component program of Underwriters Laboratories Inc. File No.SA 2585. 2. When purchased as "bagged" each vibration eliminator is cleaned and dehydrated for refrigeration service, and sealed in plastic film. When purchased as "boxed" each vibration eliminator is cleaned and dehydrated for refrigeration service, individually boxed and sealed in plastic film. 3. The maximum test pressure is 1.5 times the maximum operating pressure which is tabulated in Column 4. 4. The minimum burst pressure is 5 times the maximum operating pressure which is tabulated in Column 4. 5. The copper tube ends are designed as sweat connections for refrigeration tubing. The inside surface conforms to ASME/ANSI B16.18 and B16.22. 6. All configurations are available with male copper tube ends.

Synthetic covered Vibration Eliminators are available for use when problems exist from condensation and freezing of moisture on the outside surface of the Vibration Eliminator.

INSTALLATION INSTRUCTIONS 1. Brazing and soldering flux must be removed immediately after installation. Chlorides will cause premature failure of stainless steel vibration eliminators.

4. If condensation will collect and freeze: the entire flexible section, ferrules and braided hose, must be covered with water tight material.

2. Wrap the ferrule and approximately 2" of the braid with a wet cloth to prevent overheating during brazing and soldering.

WATER TIGHT COVER

5. Vibration Eliminators are most effective when installed perpendicular to the major motion. The fixed end should be securely anchored as close as possible to the Vibration Eliminator. When major motion exists in two planes two Vibration Eliminators should be installed. ANCHOR SECURELY AS CLOSE AS POSSIBLE TO VIBRATION ELIMINATOR

3. Direct the torch away from the ferrule and braided section. Avoid contact of the flame with the ferrule and braid.

DIRECTION OF VIBRATION

DIRECTION OF VIBRATION

SOURCE OF VIBRATION

Limited Warranty This warranty is given by Universal Metal Hose (Universal), located at 2133 South Kedzie, Chicago, Illinois 60623-3393, (773) 277-0700, for the benefit of the first purchaser of the product to which the warranty applies. This warranty applies only to those parts which are manufactured and delivered by Universal.

The only entity authorized to do any warranty repair is the manufacturer.

The warranty is that the parts manufactured and delivered by Universal will be free from defects in material or workmanship under normal use and service for the time specified below.

This warranty is expressed in lieu of all other warranties, expressed or implied, including the warranty of merchantability, the implied warranty of fitness for a particular purpose, and of all other obligations or liabilities on the part of Universal and it neither assumes nor authorizes any other persons to assume for Universal any other liabilities in connection with the sale of the products.

In the event of failure of a part due to such a covered defect, Universal will repair or replace, at its option, the defective part at its factory location at 2133 South Kedzie, Chicago, Illinois 60623-3393. The part must be returned to the factory by and at the expense of the person claiming the benefit of the warranty. The warranty shall be for a period of twenty-four (24) months after the date of delivery of the product, twelve (12) months after commencement of use of the product, or the specified service life of the product, whichever period is the shortest. All products for which warranty claims are made must be returned as provided above to the factory within thirty (30) days from the date of claimed malfunction in order for this warranty to be effective.

The repairs or replacement by Universal will be accomplished with in forty-five (45) days from receipt of the defective parts at the factory.

This warranty does not cover parts of products made by others or products or any part thereof which have been repaired or altered, except by Universal, or which shall have been subjected to misuse, negligence or accident. Universal shall not be liable for damage or delay suffered by the purchaser regardless of whether such damages are general, special or consequential in nature, whether caused by defective material or workmanship or otherwise, or whether caused by Universal's negligence regardless of the degree.

®

2133 South Kedzie 17111 South Wallace Street South Holland, IL 60473-2735 Chicago,IL 60623-3393 Voice: 773-277-0700• Fax:(733)277-0727 Voice:(773)277-0700 Fax: 773-277-0727 1-800-MET-HOSE (638-4673) www.universalmetalhose.com www.universalmetalhose.com