POLE BARNS ACCESSORY BUILDINGS LIVING AREAS IN POLE BARNS/ACCESSORY BUILDINGS

BASIC

CODE

INFORMATION

1

GREENE COUNTY RESOURCE MANAGEMENT DEPARTMENT Building Regulations Section 940 Boonville, Room 305 Springfield, Missouri Telephone 417 - 868-4015 Fax 417 - 868-4175

2

INTRODUCTION

THIS INFORMATION IS BASED ON THE 2006 INTERNATIONAL 0NE-AND

TWO-FAMILY

DWELLING

CODE

AND

OTHER

ADOPTED GREENE COUNTY AMENDMENTS.

THIS HANDOUT IS ONLY PROVIDED AS A CONVENIENT SOURCE

FOR

BASIC

INFORMATION

AND

DOES

NOT

ADDRESS ALL THE CODES NOR DOES THIS INFORMATION TAKE

THE

PLACE

OF

ANY

ADOPTED

CODE

OR

AMENDMENTS.

THIS INFORMATION SIMPLY ACTS AS AN INSTRUMENT TO BETTER PRESENT AND CLARIFY SOME OF THE CODE INTERPRETATIONS AND ENFORCEMENT AND DOES NOT REPRESENT THE REQUIREMENTS FOR ANY BUILDING THAT FALLS

UNDER

EDUCATION,

THESE

FACTORY

&

OCCUPANCIES; INDUSTRIAL,

ASSEMBLY,

HIGH

HAZARD,

INSTITUTIONAL, MERCANTILE, RESIDENTIAL (other than one and two family), AND THESE USE GROUPS; STORAGE, 3

UTILITY AND MISCELLANEOUS OCCUPANCIES, WHERE THE BUILDINGS ARE NOT AN ACCESSORY TO ONE-AND TWOFAMILY DWELLINGS AND WOULD NOT BE CLASSIFIED AS AN AGRICULTURE STRUCTURE.

REQUIRED INSPECTONS ON-SITE

FOOTINGS

FRAMING

FINAL

ADDITIONAL INSPECTIONS REQUIRED WHEN ANYOF THE FOLLOWING ARE INSTALLED IN-GROUND PLUMBING ELECTRICAL PLUMBING MECHANICAL

ON-SITE EVALUATION:

METERS (Gas and/or Electric) SEWER or SEPTIC

The location of the structure and septic system is to 4

be staked out on the property. excavation.

The on-site inspection is required before any

FOOTING INSPECTION/POLE HOLES: Commonly made after the excavation is

completed. All property pins must be visible. Pole holes must be excavated with the required gravel in the bottom. Formed footings require the forms erected and required reinforcing steel in place prior to the placement of concrete.

IN-GROUND OR UNDERSLAB PLUMBING INSPECTION:

All joints and

piping in place and visible prior to concrete

.ELECTRICAL, MECHANICAL, & PLUMBING ROUGH-IN INSPECTIONS: These inspections are required before a framing inspection and prior to insulation or sheet rock installation.

FRAMING INSPECTION: All electrical, mechanical, plumbing rough-ins, and all framing, fire-stopping, draft-stopping, and bracing in place. and prior to insulation or sheet rock installation.

Inspection conducted

SEPTIC and LATERAL, OR SEWER INSPECTION: All drain pipe, clean outs and/or septic tank in place prior to covering.

ELECTRIC METER INSPECTION: Electrical service equipment, service wiring, bonding, main disconnect, grounding in place, before meter will be approved.

GAS METER INSPECTION: Gas service to building must be installed by the gas company. Gas line installed from meter to gas fired equipment or appliance inside

of structure, with twenty (20) pounds of air pressure on the line. Furnace must be ready for operation before a gas meter will be released.

FINAL INSPECTION: Building, yard grading and all phases of construction

complete. Inspection must be performed before occupancy or items are moved into the structure.

5

INSPECTIONS It is the responsibility of the person and/or agent listed as the owner on the permit to obtain the proper inspections.

The

failure to obtain the proper inspections will result in the uncovering of work.

EXAMPLE: Placing poles or concrete in footing holes or forms

before being approved by the building inspector.

THE PERMIT NUMBER OR ADDRESS IS REQUIRED TO BE POSTED and VISIBLE FROM THE STREET AT ALL TIMES DURING THE CONSTRUCTION.

INSPECTIONS

WILL NOT BE CONDUCTED IF THIS INFORMATION IS NOT POSTED. A PERMANENT ADDRESS MUST BE POSTED BEFORE A FINAL INSPECTION IS CONDUCTED.

REQUEST FOR INSPECTIONS: All inspections (EXCEPT FINAL INSPECTIONS) must be called in to the Greene County Building Regulation

Department by 8:15 A.M., inspections called after 8:15 A.M. will be scheduled for the next day.

6

Inspections are conducted according to the inspectors’ route.

Footings,

sewers, and septic inspections may be requested for a certain time.

If

you have a special situation you will need to contact the inspector by 8:15 A.M. on the day you are requesting the inspection.

FINAL INSPECTIONS REQUESTS received before 8:15 A.M. will be scheduled for the next business day.

Requests made after

8:15 A.M. will be scheduled for the second business day TO SCHEDULE AN INSPECTION:

Call 417 - 868-4015.

We

will require the following information: Permit number, address, individuals name requesting the inspection and a contact telephone number.

BUILDING PLANNING DESIGN LOADS:

Roof Live load – 20 PSF Ground Snow load – 20 PSF Wind Speed – 90 MPH Seismic Design Category – B Soil Minimum Bearing Capacity – 2,500 PSF

ENGINEERING REQUIREMENTS:

A

Missouri

licensed

design

professional is required to design for the following; 

Other loads such as loft areas, hoist or other attached loads require a design for the footings/piers and structure.



Any building pad that has fill material placed on it shall have a compaction test. The fill material is required to be engineered from the bottom of the fill to the top of the fill. The compaction tests are required to be submitted to Greene Building Regulations before the footing or foundation holes are inspected.



Any wood pole barn structure that has a width exceeding forty (40) feet or exceeds 5,000 square feet in area requires a designed set of plans. Plans are to indicate the footings or piers, column attachments, structure and design loads. Plans are to be submitted to Greene County Building Regulations with the application for the building permit.



All wood trusses. Submit shop drawings and certification.

7



All metal or steel structures. Complete set of plans and shop drawings indicating footings or piers, column attachments, structure and design loads. Plans are to be submitted to Greene County Building Regulations with the application for the building permit.



Pole foundation depths that are shallower than the required depth indicated in the charts in this document for minimum hole depth.

POSTS:

Wood posts are required to be a minimum six inch by six inch (6” X 6”) ACQ or CCA treated.

EXITS:

The distance from the egress door to the most remote area can not exceed seventy-five (75) feet. Over seventy five (75) feet will require two (2) or more egress doors located remotely from each other.

ELECTRICAL REQUIREMENTS FOR BARN/ACCESSORY STRUCTURES: Installed according to the adopted National Electric Code. HEATING-AIR CONDITIONING, PLUMBING and GAS SERVICE: Installed according to the adopted International Codes.

POLE BARN STRUCTURES FOOTING REQUIREMENTS

When the posts are placed in concrete the diameter of the hole is required to be 10 inches. The depth of the footing holes are according to the tables located on Page 7. The bottom of the footing hole is required to have 4 inches of crushed stone placed under the post. DO NOT PLACE CONCRETE UNDER THE POST. 8

When posts are placed in soil the diameter of the hole is required to be 12 inches. The depth of the hole is according to the tables located on Page 7. The bottom of the footing hole is required to have 4 inches of crushed stone under the post. The soil placed around the pole is to be compacted.

POLES ARE REQUIRED TO BE A MINIMUM 6”X6” TREATED POST

POLES SPACED 8 FEET ON CENTER DEPTH OF FOUNDATION HOLES

Maximum Clear Truss Span 20 ft. 30 ft. 40 ft.

Soil Backfill

Concrete Backfill

Eave Height From Finish Grade 8 ft. 10 ft. 14 ft.

Eave Height From Finish Grade 8 ft. 10 ft. 14 ft.

29” 32” 34”

28” 28” 28”

37” 40” 42’

52” 54” 55”

29” 31” 32”

40” 41” 42”

POLES SPACED 10 FEET ON CENTER DEPTH OF FOUNDATION HOLES

Maximum

Soil Backfill

Concrete Backfill

Eave Height

Eave Height

9

Clear Truss Span 20 ft. 30 ft. 40 ft.

From Finish Grade 8 ft. 10 ft. 14 ft.

From Finish Grade 8 ft. 10 ft. 14 ft.

34” 37” 40”

28” 29” 31”

43” 46” 49”

60” 62” 64”

33” 35” 37”

46” 48” 49”

Shallower pole depths must be engineered

TRUSS ATTACHMENT When the truss design requires the placement of a truss between the posts, a ledger or rim is required. The ledger is to a minimum of two (2) #2 grade, 2 X 10’s. One placed on each side of the post as indicated in the examples. The ledgers are to be attached to the posts and the center support with two (2) one-half inch carriage bolts with washers and nuts. The trusses are required to be attached to the supports with one (1) one-half inch carriage bolt.

10

TRUSS ATTACHED TO EVERY POST Truss Notched Into Post: Notch is to be no deeper than 1 ½” into side of post. The truss is to be attached to the post with one (1) one-half inch carriage bolt with nut and washer. A number 2 grade 2 X 10 ledger or rim is required to be attached from post to post with two (2) one-half inch carriage bolts and washers. LEDGER BOARD IS NOT ILLUSTRATED IN THE FOLLOWING EXAMPLE.

Truss Attached to Post: When the truss is attached on the side of every post the truss is to be attached with one (1) one-half inch carriage bolt with washers and nuts. A number 2 grade 2 X 10 ledger or rim is required to be attached from post to 11

post with two (2) one-half inch carriage bolts and washers. A minimum four (4) foot long 2 X 4 is to be attached under the truss to the post with three (3) ½” by 5” lag screws spaced a maximum of six (6) inches from each end and one (1) in the middle.

PURLINS

NAILERS 12

All walls shall be braced and sheathed.

CONVENTIONAL CONSTRUCTION The following diagrams and tables represent the requirements for construction using spread footings, rafters and ceiling joist combination. These tables are not used with an engineered truss system and pole construction.

13

GIRDER and HEADER SPANS FOR EXTERIOR BEARING WALLS Building Width in Feet 20 HEADERS SUPPORTING

28

36

SIZE

SPAN

# JACK STUDS

SPAN

# JACK STUDS

SPAN

# JACK STUDS

2-2X4

3-6

1

3-2

1

2-10

1

2-2X6

5-5

1

4-8

1

4-2

1

2 - 2 X8

6-10

1

5-11

2

5-4

2

2 - 2 x 10

8-5

2

7-3

2

6-6

2

2 - 2 x 12

9-9

2

8-5

2

7-6

2

3 - 2 x8

8-4

1

7-5

1

6-8

1

3 - 2 x 10

10-6

1

9-1

2

8-2

2

3 - 2 X 12

12-2

2

10-7

2

9-5

2

4-2X8

9-2

1

8-4

1

7=8

1

4-2X1

11-8

1

10-6

1

9-5

2

4 - 2 X 12

13-1

1

12-2

2

10-11

2

Roof and ceiling

14

15

16

LIVING QUARTERS in BARNS/ ACCESORY BUILDINGS Must comply with the adopted International One and Two Family Dwelling Code and the following;

FOOTING REQUIREMENTS 

Footings are required to extend to the exterior wall side of the supporting post on a pole type structure. (SEE PAGE 16)



Bottom of footing is required to be a minimum of eighteen (18) inches below finish grade.



The top of the footing or foundation shall extend above grade were as the finish backfill or yard grade is a minimum of six (6) inches below the top of the finished floor level.



Footings shall be a minimum of twelve (12) inches wide, eight (8) inches thick with two (2) rows of #4 or ½ inch rebar in place before the concrete is poured. Rebar is to be supported a minimum of four (4) inches from the bottom of the footing, lapped and tied together.

WALLS and CEILINGS 

All interior walls shall be fastened to the concrete with a mechanical fastener spaced a maximum of six (6) feet on centers. (POWER NAILING IS NOT

ACCEPTED) 

All walls on the interior of the exterior walls around the living area and the wall between the barn/accessory structure and living area are to be insulated and covered with approved wall covering from the floor to the ceiling or roof.



The wall between the living area and the barn/accessory structure is required to be covered with a minimum of 1/2” gypsum board applied to the barn or garage side.



The area over the living area is required to be insulated.



The ceiling of the living area is required to have a minimum of 1/2” gypsum board applied to the bottom of the ceiling.

EGRESS 

At least one (1) egress door must exit directly to the exterior of the living area. The required door shall be a side-hinged door not less than thirty-six (36) inches in width and six feet-eight inches (6’ 8”) in height.



All egress doors are required to be opened from the egress side without the use of a key.



All areas used for sleeping rooms must have one (1) direct egress to the exterior of the structure, ether a window or door.

17



Windows in a sleeping room shall be as follows; 1. The unit must be operable from the inside to a full clear opening without the use of a key, tool, or special knowledge. 2. The sill height is not to be more than 44 inches above the floor. 3. The net clear opening requirement is to be obtained by normal operation of the window form the inside. 4. Minimum net clear opening shall be 5.7 square feet or 821 square inches for windows located more than 44 inches above the finished grade adjacent to the window. Windows with the sill height 44 inches or less to the finished grade adjacent to the window shall be a minimum net clear opening of 5 square feet or 720 square inches. 5. Minimum window opening height is 24 inches and the minimum opening width is 20 inches. EXAMPLE: A window with a height of 24 inches would require a width greater than 20 inches to meet the required opening and a window with a width of 20 inches would require a window with a height greater than 24 inches to meet the required opening.

OPENINGS BETWEEN LIVING AREA AND BARN/ACCESSORY STRUCTURE 

No door or window can open into the sleeping area from the barn/accessory structure.



A door from the barn/accessory structure opening into the living area (not allowed in sleeping area) must be a solid wood door a minimum of not less than 1 3/8 inch in thickness, solid or honeycomb steel door no less than 1 3/8 inch thickness or a 20minute fire rated door. Panel doors do not have the required rating or thickness.



Windows are not allowed between the living area and barn/accessory structure.

SMOKE ALARMS 

Required in all sleeping areas and outside of sleeping areas.



Smoke alarms are required to receive their primary power source from the building wiring and have battery back up power.



Smoke alarms are to be interconnected so all alarms will activate when one alarm is activated.

ELECTRIC:

Must comply with adopted National Electric Code.

HEATING/AIR CONDITIONING, PLUMBING and GAS SERVICE: Must comply with the adopted International One and Two Family Building Code and Amendments.

18

FOOTING FOR LIVING SPACE IN POLE STRUCUTURE