Data Loading...

MODBUS over Serial Line Specification and Implementation ... Flipbook PDF

MODBUS over serial line specification and implementation guide V1.02 Modbus-IDA.ORG Modbus.org http://www ...


105 Views
65 Downloads
FLIP PDF 318.76KB

DOWNLOAD FLIP

REPORT DMCA

MODBUS over serial line specification and implementation guide V1.02

Modbus-IDA.ORG

MODBUS over Serial Line Specification and Implementation Guide V1.02

Modbus.org Dec 20, 2006

http://www.modbus.org/

1/44

MODBUS over serial line specification and implementation guide V1.02

Contents

1

Introduction ..............................................................................4 1.1 1.2 1.3 1.4 1.5

2

6

Installation................................................................................ 33 User Guide............................................................................... 33

Implementation Classes ........................................................34 Appendix ................................................................................35 6.1 6.2 6.3

Modbus.org Dec 20, 2006

Preamble.................................................................................. 20 , and 0x42 ="B" in ASCII ). The format ( 10 bits ) for each byte in ASCII mode is : Coding System: Bits per Byte:

Hexadecimal, ASCII characters 0–9, A–F One hexadecimal character contains 4-bits of data within each ASCII character of the message 1 start bit 7 data bits, least significant bit sent first 1 bit for parity completion; 1 stop bit

Even parity is required, other modes ( odd parity, no parity ) may also be used. In order to ensure a maximum compatibility with other products, it is recommended to support also No parity mode. The default parity mode must be Even parity. Remark : the use of no parity requires 2 stop bits.

How Characters are Transmitted Serially : Each character or byte is sent in this order (left to right): Least Significant Bit (LSB) . . . Most Significant Bit (MSB) With Parity Checking Start

1

2

3

Figure 15:

4

5

6

7

Par Stop

Bit Sequence in ASCII mode

Devices may accept by configuration either Even, Odd, or No Parity checking. If No Parity is implemented, an additional stop bit is transmitted to fill out the character frame :

Without Parity Checking Start

Figure 16: Frame Checking Field:

Modbus.org Dec 20, 2006

1

2

3

4

5

6

7

Stop Stop

Bit Sequence in ASCII mode (specific case of No Parity)

Longitudinal Redundancy Checking (LRC)

http://www.modbus.org/

16/44

Modbus-IDA.ORG

MODBUS over serial line specification and implementation guide V1.02

2.5.2.1

MODBUS Message ASCII Framing

A MODBUS message is placed by the transmitting device into a frame that has a known beginning and ending point. This allows devices that receive a new frame to begin at the start of the message, and to know when the message is completed. Partial messages must be detected and errors must be set as a result. The address field of a message frame contains two characters. In ASCII mode, a message is delimited by specific characters as Start-of-frames and End-of-frames. A message must start with a ‘colon’ ( : ) character (ASCII 3A hex), and end with a ‘carriage return – line feed’ (CRLF) pair (ASCII 0D and 0A hex). Remark : The LF character can be changed using a specific MODBUS application command ( see MODBUS application protocol specification). The allowable characters transmitted for all other fields are hexadecimal 0–9, A–F (ASCII coded). The devices monitor the bus continuously for the ‘colon’ character. When this character is received, each device decodes the next character until it detects the End-Of-Frame. Intervals of up to one second may elapse between characters within the message. Unless the user has configured a longer timeout, an interval greater than 1 second means an error has occurred. Some Wide-Area-Network application may require a timeout in the 4 to 5 second range. A typical message frame is shown below.

Start 1 char :

Address 2 chars

Function 2 chars

Data

LRC 2 chars

0 up to 2x252 char(s)

Figure 17:

End 2 chars CR,LF

ASCII Message Frame

Remark : Each data byte needs two characters for encoding. Thus, to ensure compatibility at MODBUS application level between ASCII mode and RTU mode, the maximum data size for ASCII data field (2x252) is the double the maximum data size for RTU data field (252). Consequently, the maximum size of a MODBUS ASCII frame is 513 characters. The ASCII framing requirements are synthesized in the following state diagram. Both "master" and "slave" points of view are expressed in the same drawing : Reception of ":" character / Empty reception buffer

Reception of ":" character

Idle

Sending of “LF”

Reception

(ready to receive or to emit)

Reception of character / Concatenation of character into reception buffer

Emission Demand

Emission start

Reception of "LF" character / control frame (LRC, Parity, Slave addr.)

Comment If frame OK  processing frame If frame NOK  delete entire frame

Sending of “:”

Emission

Reception of "CR" character

Waiting "End of Frame"

Reception of ":" character / Empty reception buffer

Sending of all characters Sending of “CR”

Emission End

Figure 18:

Modbus.org Dec 20, 2006

ASCII Transmission mode State diagram

http://www.modbus.org/

17/44

MODBUS over serial line specification and implementation guide V1.02

Modbus-IDA.ORG

Some explanations about the above state diagram : 

"Idle" state is the normal state when neither emission nor reception is active.



Each reception of a ":" character means a beginning of a new message. If a message was in process of reception while receiving such a character, the current message is declared incomplete and it is discarded. A new reception buffer is then allocated.



After detection of the end of frame, the LRC calculation and checking is completed. Afterwards the address field is analyzed to determine if the frame is for the device. If not the frame is discarded. In order to reduce the reception processing time the address field can be analyzed as soon as it is reserved without waiting the end of frame.

2.5.2.2

LRC Checking

In ASCII mode, messages include an error–checking field that is based on a Longitudinal Redundancy Checking (LRC) calculation that is performed on the message contents, exclusive of the beginning ‘colon’ and terminating CRLF pair characters. It is applied regardless of any parity checking method used for the individual characters of the message. The LRC field is one byte, containing an 8–bit binary value. The LRC value is calculated by the device that emits, which appends the LRC to the message. The device that receives calculates an LRC during receipt of the message, and compares the calculated value to the actual value it received in the LRC field. If the two values are not equal, an error results. The LRC is calculated by adding together successive 8–bit bytes of the message, discarding any carries, and then two’s complementing the result. It is performed on the bytes of the message, before the encoding of each byte in the two ASCII characters corresponding to the hexadecimal representation of each nibble. The computation does not include the 'colon' character that begins the message, and does not include the CRLF pair at the end of the message. The resulting LRC is ASCII encoded into two bytes and placed at the end of the ASCII mode frame before the CRLF. A detailed example of LRC generation is contained in Appendix B.

Modbus.org Dec 20, 2006

http://www.modbus.org/

18/44

MODBUS over serial line specification and implementation guide V1.02

2.6

Modbus-IDA.ORG

Error Checking Methods

The security of standard MODBUS Serial Line is based on two kinds of error checking : 

Parity checking (even or odd) should be applied to each character.



Frame checking (LRC or CRC) must be applied to the entire message.

Both the character checking and message frame checking are generated in the device (master or slave) that emits and applied to the message contents before transmission. The device (slave or master) checks each character and the entire message frame during receipt. The master is configured by the user to wait for a predetermined timeout interval ( Response time-out) before aborting the transaction. This interval is set to be long enough for any slave to respond normally ( unicast request). If the slave detects a transmission error, the message will not be acted upon. The slave will not construct a response to the master. Thus the timeout will expire and allow the master’s program to handle the error. Note that a message addressed to a nonexistent slave device will also cause a timeout.

2.6.1

Parity Checking

Users may configure devices for Even ( required) or Odd Parity checking, or for No Parity checking ( recommended). This will determine how the parity bit will be set in each character. If either Even or Odd Parity is specified, the quantity of 1 bits will be counted in the data portion of each character (seven data bits for ASCII mode, or eight for RTU). The parity bit will then be set to a 0 or 1 to result in an Even or Odd total of 1 bits. For example, these eight data bits are contained in an RTU character frame: 1100 0101 The total quantity of 1 bits in the frame is four. If Even Parity is used, the frame’s parity bit will be a 0, making the total quantity of 1 bits still an even number (four). If Odd Parity is used, the parity bit will be a 1, making an odd quantity (five). When the message is transmitted, the parity bit is calculated and applied to the frame of each character. The device that receives counts the quantity of 1 bits and sets an error if they are not the same as configured for that device (all devices on the MODBUS Serial Line must be configured to use the same parity checking method). Note that parity checking can only detect an error if an odd number of bits are picked up or dropped in a character frame during transmission. For example, if Odd Parity checking is employed, and two 1 bits are dropped from a character containing three 1 bits, the result is still an odd count of 1 bits. If No Parity checking is specified, no parity bit is transmitted and no parity checking can be made. An additional stop bit is transmitted to fill out the character frame.

2.6.2

Frame Checking

Two kinds of frame checking is used depending on the transmission mode, RTU or ASCII. 

In RTU mode, messages include an error–checking field that is based on a Cyclical Redundancy Checking (CRC) method. The CRC field checks the contents of the entire message. It is applied regardless of any parity checking method used for the individual characters of the message.



In ASCII mode, messages include an error–checking field that is based on a Longitudinal Redundancy Checking (LRC) method. The LRC field checks the contents of the message, exclusive of the beginning ‘colon’ and ending CRLF pair. It is applied regardless of any parity checking method used for the individual characters of the message.

The detailed information about error checking methods is contained in the previous sections.

Modbus.org Dec 20, 2006

http://www.modbus.org/

19/44

MODBUS over serial line specification and implementation guide V1.02

3 3.1

Modbus-IDA.ORG

Physical Layer Preamble

A new MODBUS solution over serial line should implement an electrical interface in accordance with EIA/TIA-485 standard ( also known as RS485 standard). This standard allows point to point and multipoint systems, in a “two-wire configuration”. In addition, some devices may implement a “Four-Wire” RS485-Interface. A device may also implement an RS232-Interface.

In such a MODBUS system, a Master Device and one or several Slave Devices communicate on a passive serial line. On standard MODBUS system, all the devices are connected (in parallel) on a trunk cable constituted by 3 conductors. Two of those conductors ( the “Two-Wire” configuration ) form a balanced twisted pair, on which bi-directional data are transmitted, typically at the bit rate of 9600 bits per second. Each device may be connected ( see figure 19): -

either directly on the trunk cable, forming a daisy-chain,

-

either on a passive Tap with a derivation cable,

-

either on an active Tap with a specific cable.

Screw Terminals, RJ45, or D-shell 9 connectors may be used on devices to connect cables (see the chapter “Mechanical Interfaces”).

3.2

Data Signaling Rates

9600 bps and 19.2 Kbps are required and 19.2 is the required default Other baud rates may optionally be implemented : 1200, 2400, 4800, … 38400 bps, 56 Kbps, 115 Kbps, … Every implemented baud rate must be respected better than 1% in transmission situation, and must accept an error of 2% in reception situation.

Modbus.org Dec 20, 2006

http://www.modbus.org/

20/44

Modbus-IDA.ORG

MODBUS over serial line specification and implementation guide V1.02

3.3 3.3.1

Electrical Interfaces Multipoint Serial Bus Infrastructure

Figure 19 gives a general overview of the serial bus infrastructure in a MODBUS multipoint Serial Line system.

Master

D R

IDv Passive TAP

ActiveTap

ITr ITr

ITr

LT

D

Passive TAP

R

LT

IDv AUI

R D

R D

Slave n Slave 1

Slave 2

Figure 19 : Serial bus infrastructure

A multipoint MODBUS Serial Line bus is made of a principal cable (the Trunk), and possibly some derivation cables. Line terminations are necessary at each extremity of the trunk cable for impedance adaptation (see § "Two-Wire MODBUS Definition" & "Optional Four-Wire MODBUS Definition" for details). As shown in figure 19, different implementations may operate in the same MODBUS Serial Line system : 

the device integrates the communication transceiver and is connected to the trunk using a Passive Tap and a derivation cable ( case of Slave 1 and Master ) ;



the device doesn't integrate the communication transceiver and is connected to the trunk using an Active Tap and a derivation cable (the active TAP integrates the transceiver) ( case of Slave 2 ) ;



the device is connected directly to the trunk cable, in a Daisy-Chain ( case of Slave n )

The following conventions are adopted : 

The interface with the trunk is named ITr (Trunk Interface)



The interface between the device and the Passive Tap is named IDv (Derivation Interface)



The interface between the device and the Active Tap is named AUI (Attachment Unit Interface)

Remarks : 1. In some cases, the Tap may be connected directly to the IDv-socket or the AUI-socket of the device, without using a derivation cable. 2. A Tap may have several IDv sockets to connect several devices. Such a Tap is named Distributor when it is a passive one. 3. When using an active Tap, power supply of the Tap may be provided either via its AUI or ITr interface. ITr and IDv interfaces are described in the following chapters (see § "Two-Wire MODBUS DEFINITION" & "Four-Wire MODBUS DEFINITION").

Modbus.org Dec 20, 2006

http://www.modbus.org/

21/44

Modbus-IDA.ORG

MODBUS over serial line specification and implementation guide V1.02

3.3.2

Two-Wire MODBUS Definition

A MODBUS solution over serial line should implement a “Two-Wire” electrical interface in accordance with EIA/TIA-485 standard. On such a 2W-bus, at any time one driver only has the right for transmitting. In fact a third conductor must also interconnect all the devices of the bus : the common.

Master 5V D

R

Pull Up

D1 Balanced Pair

LT

LT

D0 Pull Down

Common

R

R D

D

Slave n

Slave 1

Figure 20:

General 2-Wire Topology

2W-MODBUS Circuits Definition Required Circuits on ITr

on IDv

For device

Required on device

EIA/TIA-485 name

D1

D1

I/O

X

B/B’

D0

D0

I/O

X

A/A’

Common

Common

--

X

C/C’

Description Transceiver terminal 1, V1 Voltage ( V1 > V0 for binary 1 [OFF] state ) Transceiver terminal 0, V0 Voltage ( V0 > V1 for binary 0 [ON] state ) Signal and optional Power Supply Common

Notes : •

For Line Termination (LT), Pull Up and Pull Down resistors, please refer to section “Multipoint System requirements".



D0, D1, and Common circuit names must be used in the documentation related to the device and the Tap ( User Guide, Cabling Guide, … ) to facilitate interoperability.



Optional electrical interfaces may be added, for example : 

Power Supply :



Port mode control : PMC circuit ( TTL compatible ). When needed, port mode may be controlled either by this external circuit and/or by another way (a switch on the device for example). In the first case while an open circuit PMC will ask for the 2W-MODBUS mode, a Low level on PMC will switch the port into 4W-MODBUS or RS232-MODBUS Mode, depending on the implementation.

Modbus.org Dec 20, 2006

5..24 V D.C.

http://www.modbus.org/

22/44

Modbus-IDA.ORG

MODBUS over serial line specification and implementation guide V1.02

3.3.3

Optional Four-Wire MODBUS Definition

Optionally, such MODBUS devices also permit to implement a 2-pair bus (4 wires) of mono directional data. The data on the master pair ( RXD1-RXD0 ) are only received by the slaves ; the data on the slave pair ( TXD1-TXD0 ) are only received by the only master. In fact a fifth conductor must also interconnect all the devices of the 4W-bus : the common. In the same way as on a 2W-MODBUS, at any time one driver only has the right for emitting. Such a device must implement, for each balanced pair, a driver and a transceiver in accordance with EIA/ TIA-485. ( Sometimes this solution has been named “RS422”, which is not correct : the RS422 standard does not support several drivers on one balanced pair.) M a s te r D

5 V

R

P u ll U p

TXD1 LT

LT

S la v e P a ir TXD0

5 V P u ll D o w n P u ll U p

R XD1 LT

LT

M a s te r P a ir R XD0 P u ll D o w n

Com m on

R

R

D

D

S la v e 1

S la v e n

Figure 21:

General 4-wire topology

Optional 4W-MODBUS Circuits Definition Required Circuits on ITr

on IDv

For device

TXD1

TXD1

Out

Out

Required on device

EIA/TIA-485 name

X

B

X

A

(1)

B’

Generator terminal 1, Vb Voltage ( Vb > Va for binary 1 [OFF] state )

TXD0

TXD0

RXD1

RXD1

RXD0

RXD0

In

(1)

A’

Common

Common

--

X

C/C’

In

Description for IDv

Generator terminal 0, Va Voltage ( Va > Vb for binary 0 [ON] state ) Receiver terminal 1, Vb’ Voltage ( Vb’ > Va’ for binary 1 [OFF] state ) Receiver terminal 0, Va’ Voltage ( Va’ > Vb’ for binary 0 [ON] state ) Signal and optional Power Supply Common

Notes : •

For Line Termination (LT), Pull Up and Pull Down resistors, please refer to section “Multipoint System requirements".



Those circuits (1) are required only if an 4W-MODBUS option is implemented.



The name of the 5 required circuits must be used in the documentation related to the device and the Tap ( User Guide, Cabling Guide, … ) to facilitate interoperability.



Optional electrical interfaces may be added, for example : 

Power Supply :



PMC circuit : See above ( In 2W-MODBUS Circuits Definition ) the note about this optional circuit.

Modbus.org Dec 20, 2006

5..24 V D.C.

http://www.modbus.org/

23/44

Modbus-IDA.ORG

MODBUS over serial line specification and implementation guide V1.02

3.3.3.1

4W-Cabling System Important Topic

In such a 4W-MODBUS, Master Device and Slave Devices have IDv interfaces with the same 5 required circuits. As the master has to : -

receive from the slave the data on the slave pair ( TXD1-TXD0 ),

-

and transmit on the master pair ( RXD1-RXD0 , received by the slaves) ,

the 4W-cabling system must cross the two pairs of the bus between ITr and the IDv of the master :

Signal on Master IDv

EIA/TIA-485

Circuit on ITr

Name

Type

Name

RXD1

In

B’

TXD1

RXD0

In

A’

TXD0

TXD1

Out

B

RXD1

TXD0

Out

A

RXD0

Common

--

C/C’

Common

Slave Pair

Master Pair

This crossing may be implemented by crossed cables, but the connection of such crossed cables in a 2-wire system may cause damages. To connect a 4W master device ( which have a MODBUS connector) a better solution is to use a Tap which includes the crossing function.

3.3.3.2

Compatibility between 4-Wire and 2-Wire cabling

In order to connect devices implementing a 2-Wire physical interface to an already existing 4-Wire system, the 4-Wire cabling system can be modified as described below : 

TxD0 signal shall be wired with the RxD0 signal, turning them to the D0 signal



TxD1 signal shall be wired with the RxD1 signal, turning them to the D1 signal.



Pull-up, Pull-down and line terminations resistors shall be re-arranged to correctly adapt the D0, D1 signals.

Modbus.org Dec 20, 2006

http://www.modbus.org/

24/44

Modbus-IDA.ORG

MODBUS over serial line specification and implementation guide V1.02

The figure hereafter gives an example where slaves 2 and 3 which use a 2-Wire interface can operate with the Master and the slave 1 which use a 4-Wire interface.

M a s te r D

5 V

R

P u ll U p

TXD1 LT

TXD0 P u ll D o w n

R XD1 LT

R XD0 Com m on

R

R

D

R

D

S la v e 1

D

S la v e 2

S la v e 3

Figure 22 : Changing a 4-Wire cabling system into a 2-Wire cabling system

In order to connect devices implementing a 4-Wire physical interface to an already existing 2-Wire system, the 4-Wire interface of the new coming devices can be arranged as describe below : On each 4-Wire device interface : 

TxD0 signal shall be wired with the RxD0 signal and then connected to the D0 signal of the trunk ;



TxD1 signal shall be wired with the RxD1 signal and then connected to the D1 signal of the trunk.

The figure hereafter gives an example where slaves 2 and 3 which use a 4-Wire interface can operate with the Master and the slave 1 which use a 2-Wire interface.

Master 5V D

R

Pull Up

D1 Balanced Pair

LT

LT

D0 Pull Down

Common

R D

Slave 1

R

R D

Slave 2

D

Slave 3

Figure 23 : Connecting devices with 4-Wire interface to a 2-Wire cabling system

Modbus.org Dec 20, 2006

http://www.modbus.org/

25/44

MODBUS over serial line specification and implementation guide V1.02

3.3.4

Modbus-IDA.ORG

RS232-MODBUS Definition

Some devices may implement an RS232-Interface between a DCE and a DTE. Optional RS232-MODBUS Circuits Definition For DCE

Required on DCE (1)

Required on DTE (1)

Common

--

X

X

CTS

In

Clear to Send

DCD

--

Data Carrier Detected ( from DCE to DTE )

DSR

In

Data Set Ready

DTR

Out

Data Terminal Ready

RTS

Out

Request to Send

Signal

Description Signal Common

RXD

In

X

X

Received Data

TXD

Out

X

X

Transmitted Data

Notes : •

“X” marked signals are required only if an RS232-MODBUS option is implemented.



Signals are in accordance with EIA/ TIA-232.



Each TXD must be wired with RXD of the other device ;



RTS may be wired with CTS of the other device,



DTR may be wired with DSR of the other device.



3.3.5

Optional electrical interfaces may be added, for example : 

Power Supply :

5..24 V D.C.



PMC circuit :

See above ( In 2W-MODBUS Circuits Definition ) the note about this optional circuit.

RS232-MODBUS requirements

This optional MODBUS on Serial Line system should only be used for short length ( typically less than 20m ) point to point interconnection. Then, the EIA/TIA-232 standard must be respected : ⇒

circuits definition,



maximum wire capacitance to ground ( 2500 pF, then 25 m for a 100 pF/m cable ).

Please refer to chapter “Cables” for the shield, and for the possibility to use Category 5 Cables. Documentation of the device must indicate : ⇒

if the device must be considered as a DCE either as a DTE,



how optional circuits must work if such is the case.

Modbus.org Dec 20, 2006

http://www.modbus.org/

26/44

MODBUS over serial line specification and implementation guide V1.02

3.4

Modbus-IDA.ORG

Multipoint System requirements

For any EIA/ TIA-485 multipoint system, in either 2-wire or 4-wire configuration, the following requirements all apply.

3.4.1

Maximum number of devices without repeater

A figure of 32 devices is always authorized on any RS485-MODBUS system without repeater. Depending of : - all the possible addresses, - the figure of RS485 Unit Load used by the devices, - and the line polarization in need be, A RS485 system may implement a larger number of devices. Some devices allow the implementation of a RS485-MODBUS serial line with more than 32 devices, without repeater. In this case these MODBUS devices must be documented to say how many of such devices are authorized without repeater. The use of a repeater between two heavy loaded RS485-MODBUS is also possible.

3.4.2

Topology

An RS485-MODBUS configuration without repeater has one trunk cable, along which devices are connected, directly (daisy chaining) or by short derivation cables. The trunk cable, also named “Bus”, can be long (see hereafter). Its two ends must be connected on Line Terminations. The use of repeaters between several RS485-MODBUS is also possible.

3.4.3

Length

The end to end length of the trunk cable must be limited. The maximum length depends on the baud rate, the cable (Gauge, Capacitance or Characteristic Impedance), the number of loads on the daisy chain, and the network configuration (2-wire or 4-wire). For a maximum 9600 Baud Rate and AWG26 (or wider) gauge, the maximum length is 1000m. In the specific case shown in the figure 22 ( 4 Wire cabling used as a 2 Wire cabling system) the maximum length must be divided by two. The derivations must be short, never more than 20m. If a multi-port tap is used with n derivations, each one must respect a maximum length of 40m divided by n.

3.4.4

Grounding Arrangements

The « Common » circuit ( Signal and optional Power Supply Common ) must be connected directly to protective ground, preferably at one point only for the entire bus. Generally this point is to choose on the master device or on its Tap.

3.4.5

Line Termination

A reflection in a transmission line is the result of an impedance discontinuity that a travelling wave sees as it propagates down the line. To minimize the reflections from the end of the RS485-cable it is required to place a Line Termination near each of the 2 Ends of the Bus. It is important that the line be terminated at both ends since the propagation is bi-directional, but it is not allowed to place more than 2 LT on one passive D0-D1 balanced pair . Never place any LT on a derivation cable.

Modbus.org Dec 20, 2006

http://www.modbus.org/

27/44

MODBUS over serial line specification and implementation guide V1.02

Modbus-IDA.ORG

Each line termination must be connected between the two conductors of the balanced line : D0 and D1. Line termination may be a 150 ohms value ( 0.5 W ) resistor. A serial capacitor ( 1 nF, 10 V minimum ) with a 120 Ohms ( 0.25 W ) resistor is a better choice when a polarization of the pair must be implemented (see here after). In a 4W-system, each pair must be terminated at each end of the bus. In an RS232 interconnections, no termination should be wired.

3.4.6

Line Polarization

When there is no data activity on an RS-485 balanced pair, the lines are not driven and, thus susceptible to external noise or interference. To insure that its receiver stays in a constant state, when no data signal is present, some devices need to bias the network. Each MODBUS device must be documented to say : -

if the device needs a line polarization,

-

if the device implements, or can implement, such a line polarization.

If one or several devices need polarization, one pair of resistors must be connected on the RS-485 balanced pair : -

a Pull-Up Resistor to a 5V Voltage on D1 circuit,

-

a Pull-Down Resistor to the common circuit on D0 circuit.

The value of those resistors must be between 450 Ohms and 650 Ohms. 650 Ohms resistors value may allow a higher number of devices on the serial line bus. In this case, a polarization of the pair must be implemented at one location for the whole Serial Bus. Generally this point is to choose on the master device or on its Tap. Other devices must not implement any polarization. The maximum number of devices authorized on such a MODBUS Serial Line is reduced by 4 from a MODBUS without polarization.

Modbus.org Dec 20, 2006

http://www.modbus.org/

28/44

Modbus-IDA.ORG

MODBUS over serial line specification and implementation guide V1.02

3.5

Mechanical Interfaces

Screw Terminals may be used for both IDv and ITr connections. All information must be provided to the users about the exact location of each signal, with names in accordance with the previous chapter “Electrical Interface”. If a RJ45 ( or a mini-DIN or a D-Shell) connector is used on an equipment for a MODBUS mechanical interface, a shielded female connector must be chosen. Then the cable-end must have a shielded male connector.

3.5.1

Connectors pin-out for 2W-MODBUS Device side - female connector

Common D0 D1

Figure 24:

2W- MODBUS on RJ45 connector ( required pin-out )

Female (Front view) 5

4 9

3 8

2 7

Male (Front view) 1

1

6

Figure 25:

2 6

3 7

4 8

5 9

D-shell 9-pin connector

Screw type connectors can also be used. If an RJ45 or a 9-pin D-shell connector is used for a standard MODBUS device, the pinouts hereafter must be respected for every implemented circuit. 2W-MODBUS RJ45 and 9-pin D-shell Pinouts Pin on Pin on RJ45 D9-shell

Level of requirement

IDv

ITr

Circuit

Circuit

EIA/TIA485 name

Description for IDv

3

3

optional

PMC

--

--

4

5

required

D1

D1

B/B’

Transceiver terminal 1, V1 Voltage ( V1 > V0 for binary 1 [OFF] state )

5

9

required

D0

D0

A/A’

Transceiver terminal 0, V0 Voltage ( V0 > V1 for binary 0 [ON] state )

7

2

recommended

VP

--

--

Positive 5...24 V D.C. Power Supply

8

1

required

Common

Common

C/C’

Signal and Power Supply Common

Modbus.org Dec 20, 2006

Port Mode Control

http://www.modbus.org/

29/44

Modbus-IDA.ORG

MODBUS over serial line specification and implementation guide V1.02

3.5.2

Connectors pin-out for optional 4W-MODBUS Device side - female connector

Common TXD0 TXD1 RXD1 RXD0

Figure 26:

4W- MODBUS on RJ45 connector ( required pin-out )

Female (Front view) 5

4 9

3 8

2 7

Male (Front view) 1

1

6

Figure 27:

2 6

3 7

4 8

5 9

D-shell 9-pin connector

Screw type connectors can also be used. If an RJ45 or a 9-pin D-shell connector is used for a 4W-MODBUS device, the pinouts hereafter must be respected for every implemented circuit. Optional 4W-MODBUS RJ45 and 9-pin D-shell Pinouts Pin on Pin on RJ45 D9-shell

Note :

Level of requirement

IDv

ITr

Signal

Signal

EIA/TIA485 name

1

8

required

RXD0

RXD0

A’

2

4

required

RXD1

RXD1

B’

3

3

optional

PMC

--

--

4

5

required

TXD1

TXD1

B

5

9

required

TXD0

TXD0

A

7

2

recommended

VP

--

--

8

1

required

Common

Common

C/C’

Description for IDv Receiver terminal 0, Va’ Voltage ( Va’ > Vb’ for binary 0 [ON] state ) Receiver terminal 1, Vb’ Voltage ( Vb’ > Va’ for binary 1 [OFF] state ) Port Mode Control Generator terminal 1, Vb Voltage ( Vb > Va for binary 1 [OFF] state ) Generator terminal 0, Va Voltage ( Va > Vb for binary 0 [ON] state ) Positive 5...24 V DC Power Supply Signal and Power Supply Common

When both 2 and 4-Wire configurations are implemented on the same port, the 4W notations must be used.

Modbus.org Dec 20, 2006

http://www.modbus.org/

30/44

Modbus-IDA.ORG

MODBUS over serial line specification and implementation guide V1.02

3.5.3

RJ45 and 9-pin D-shell Pinouts for optional RS232-MODBUS

If an RJ45 or a 9-pin D-shell connector is used for a RS232-MODBUS device, the pinouts hereafter must be respected for every implemented circuit.

DCE Underlined pins can be output Pin on Pin on RJ45 D9-shell

DTE

Circuit

Level of requirement

Name

Description

Underlined pins can be output RS232 Source DTE

Level of requirement

Pin on RJ45

Pin on D9shell

required

2

3

1

2

required

TXD

Transmitted Data

2

3

required

RXD

Received Data

DCE

required

1

2

3

7

optional

CTS

Clear to Send

DCE

optional

6

8

6

8

optional

RTS

Request to Send

optional

3

7

8

5

required

Common

Signal Common

required

8

5

DTE --

Important Note : Some DCE Pinouts are crossed with DTE Pinouts with the same name : A directly pin to pin wired cable ( without any crossing ) must be used between one DTE ( a PC for example ) and a DCE (a PLC for example).

Modbus.org Dec 20, 2006

http://www.modbus.org/

31/44

Modbus-IDA.ORG

MODBUS over serial line specification and implementation guide V1.02

3.6

Cables

A MODBUS over Serial Line Cable must be shielded. At one end of each cable its shield must be connected to protective ground. If a connector is used at this end, the shell of the connector is connected to the shield of the cable. An RS485-MODBUS must use a balanced pair (for D0-D1) and a third wire (for the Common). In addition to that a second balanced pair must be used in a 4W-MODBUS system (for RXD0-RXD1). If a connectorized 4 pairs Category 5 Cable is used, please remember to the user in the User Guides : “Connection of a crossed cable in a 2-wire MODBUS system may cause damages”.

To minimize errors in cabling, a Color Code is recommended for the wires in the RS485-MODBUS Cables : Signal Names

Recommended Color

D1-TXD1

yellow

D0-TXD0

brown

Common

grey

4W ( Optional )

RXD0

white

4W ( Optional )

RXD1

blue

Figure 28: Note :

Color code for RS485-MODBUS wires

Category 5 Cables use other colors.

For RS485-MODBUS, Wire Gauge must be chosen sufficiently wide to permit the maximum length ( 1000 m ). AWG 24 is always sufficient for the MODBUS Data. Category 5 cables may operate for RS485-MODBUS, to a maximum length of 600m. For the balanced pairs used in an RS485-system, a Characteristic Impedance with a value higher than 100 Ohms may be preferred, especially for 19200 and higher baud rates.

3.7

Visual Diagnosis

For a visual diagnosis, communication status and device status must be indicated by LEDs : LED

Level of requirement

State

Recommended colour

Communication

required

Switched ON during frame reception or sending.

Yellow

( 2 LEDs for frame reception and frame sending, or 1 LED for both purposes.) Error

recommended

Switched ON : internal fault

Red

Flashing : Other faults (Communication fault or configuration error) Device status

Modbus.org Dec 20, 2006

optional

Switched ON : device powered

http://www.modbus.org/

Green

32/44

MODBUS over serial line specification and implementation guide V1.02

4

Modbus-IDA.ORG

Installation and Documentation

4.1

Installation

Product vendor should pay attention to give to the user of a MODBUS System or MODBUS Devices all useful information to prevent them from any error in cabling or bad utilization of cabling accessories : -

Some other Fieldbuses, CANopen for example, use the same connector types ( D-shell, RJ45…) .

-

Studies are conducted on Ethernet, with power supply on the same Balanced Pairs Cable.

-

Some Products use for I/O circuits the same connector types ( D-shell, RJ45…).

On these connectors, for the most part, no foolproofing is available (polarizing notch or other implementation) .

4.2

User Guide

The User Guide of any MODBUS Device or Cabling System Component must include in a non exhaustive manner one or two types of information:

4.2.1

For any MODBUS Product :

The following information should be documented : 

All the implemented requests.



The operating modes.



The visual diagnostics.



The reachable registers and supported function codes.



Installation rules.



The required information in the following sections should also be documented :



"Two-Wire MODBUS Definition" (to mention the Required Circuits) ;



"Optional Four-Wire MODBUS Definition" (to mention the Required Circuits) ;



"Line Polarization" (to mention a possible Need or an Implementation) ;



"Cables" (special care of crossed cables).



A specific indication relating to the devices addresses, is to be written in the form of an important warning :

"It is of great importance to ensure at the time of the procedure of devices addressing, that there is not two devices with the same address. In such a case, an abnormal behavior of the whole serial bus can occur, the Master being then in the impossibility to communicate with all present slaves on the bus." 

A "Getting Started" chapter is highly recommended, with the documented description of a typical application example, for an easy start.

4.2.2

For a MODBUS Product with implemented Options :

The different optional parameters must be clearly detailed : ⇒ ⇒ ⇒ ⇒ ⇒ ⇒

Optional serial Transmission mode ; Optional Parity Checking ; Optional Baud Rates ; Optional Circuit(s) : Power Supply, Port Configuration ; Optional Interface(s) ; Maximum number of devices (without repeater) if greater than 32.

Modbus.org Dec 20, 2006

http://www.modbus.org/

33/44

MODBUS over serial line specification and implementation guide V1.02

5

Modbus-IDA.ORG

Implementation Classes

Each device on a MODBUS Serial Line must respect all the mandatory requirements of a same implementation class. The following parameters are used to classify the MODBUS Serial Line devices : •

Addressing



Broadcasting



Transmission mode



Baud rate



Character format



Electrical interface parameter

Two implementation classes are proposed, the Basic and the Regular classes. The regular class must provide configuration capabilities. BASIC Addressing

Slave :

REGULAR Master :

Default value

Same as Basic

-

-

configurable address to be able to address from 1 to 247 a slave from address 1 to 247 Broadcast

Yes

Yes

Baud Rate

9600 ( 19200 is also recommended)

9600, 19200 + additional configurable baud rates

19200 (if implemented, else 9600)

Parity

EVEN

EVEN + possibility to configure NO and ODD parity

EVEN

Mode

RTU

RTU + ASCII

RTU

Electrical Interface RS485 2W-cabling or RS232

RS485 2W-cabling (and 4W-cabling as an RS485 2W-cabling additional option) or RS232

Connector Type

Modbus.org Dec 20, 2006

RJ 45 ( recommended )

-

http://www.modbus.org/

34/44

MODBUS over serial line specification and implementation guide V1.02

6

Modbus-IDA.ORG

Appendix

6.1

Appendix A - Management of Serial Line Diagnostic Counters

6.1.1

General description

MODBUS Serial Line defines a list of diagnostic counters to allow performance and error management. These counters are accessible using the MODBUS application protocol and its Diagnostic function (function code 08). Each counter can be get by a sub-function code bound to the counter number. All counters can be cleared using the sub-function code 0x0A. The format of the Diagnostic function is described in the MODBUS application protocol specification. Herein is the list of diagnostics and associated sub-function codes supported by a serial line device. Subfunction code Hex

Counter

Counters Name

number

Comments (for diagram below)

Dec

0x0B

1

Return Bus Message Count

Quantity of messages that the remote device has detected on the communications system since its last restart, clear counters operation, or power–up. Messages with bad CRC are not taken into account.

0x0C

2

Return Bus Communication Error Count

Quantity of CRC errors encountered by the remote device since its last restart, clear counters operation, or power–up. In case of an error detected on the character level, (overrun, parity error), or in case of a message length < 3 bytes, the receiving device is not able to calculate the CRC. In such cases, this counter is also incremented.

0x0D

3

Return Slave Exception Error Count

Quantity of MODBUS exception error detected by the remote device since its last restart, clear counters operation, or power–up. It comprises also the error detected in broadcast messages even if an exception message is not returned in this case. Exception errors are described and listed in "MODBUS Application Protocol Specification" document.

0xOE

4

Return Slave Message Count

Quantity of messages addressed to the remote device, including broadcast messages, that the remote device has processed since its last restart, clear counters operation, or power–up.

0x0F

5

Return Slave No Response Count

Quantity of messages received by the remote device for which it returned no response (neither a normal response nor an exception response), since its last restart, clear counters operation, or power–up. Then, this counter counts the number of broadcast messages it has received.

0x10

6

Return Slave NAK Count

Quantity of messages addressed to the remote device for which it returned a Negative Acknowledge (NAK) exception response, since its last restart, clear counters operation, or power–up. Exception responses are described and listed in "MODBUS Application Protocol Specification" document.

0x11

7

Return Slave Busy Count

Quantity of messages addressed to the remote device for which it returned a Slave Device Busy exception response, since its last restart, clear counters operation, or power–up. Exception responses are described and listed in "MODBUS Application Protocol Specification" document

0x12

8

Return Bus Character Overrun Count

Quantity of messages addressed to the remote device that it could not handle due to a character overrun condition, since its last restart, clear counters operation, or power–up. A character overrun is caused by data characters arriving at the port faster than they can be stored, or by the loss of a character due to a hardware malfunction.

Modbus.org Dec 20, 2006

http://www.modbus.org/

35/44

Modbus-IDA.ORG

MODBUS over serial line specification and implementation guide V1.02

6.1.2

Counters Management Diagram

The following diagrams describe when each previous counters must be incremented. 3

Rest IDLE reception

reception reception max 255number characters max characters

CPT8 = CPT8 + 1

character overrun error

end of frame detected 3 characters silence

YES

NO

error on at least 1 frame character YES

YES

length < 3 bytes

NO

CRC incorrect

NO

CPT2 = CPT2 + 1

CPT1 ==CPT1 + 1+ 1 CPT1 CPT1 YES

YES YES CPT5 = CPT5 + 1

CPT5 = CPT5 + 1

1



slave number 0

NO

CPT4 = CPT4 + 1 slave number =0 YES

NO

slave number = 0 or slave number = my slave number

slave number = workstation slave number

NO

NO

CPT4 = CPT4 + 1

YES

function code not known

exception n° 1

YES

CPT3 = CPT3 + 1

NO

length incorrect

exception n° 3

NO

YES

CPT3 = CPT3 + 1

addressing incorrect

NO

YES

exception n° 2

data incorrect

NO

CPT3 = CPT3 + 1

exception n° 3

2

CPT3 = CPT3 + 1

Modbus.org Dec 20, 2006

http://www.modbus.org/

36/44

Modbus-IDA.ORG

MODBUS over serial line specification and implementation guide V1.02

1 3 YES

function code not known

YES

NO

function code prohibited in broadcasts

YES

NO

length incorrect

YES

NO

addressing incorrect

YES

NO

data incorrect

NO

CPT3 = CPT3 + 1

2

2 3

application processing

NO

YES processing error

CPT3 = CPT3 + 1

NO

YES broadcast

broadcast

exception response

Modbus.org Dec 20, 2006

NO

YES

http://www.modbus.org/

response

37/44

Modbus-IDA.ORG

MODBUS over serial line specification and implementation guide V1.02

6.2

6.2.1

Appendix B - LRC/CRC Generation

LRC Generation

The Longitudinal Redundancy Checking (LRC) field is one byte, containing an 8–bit binary value. The LRC value is calculated by the transmitting device, which appends the LRC to the message. The device that receives recalculates an LRC during receipt of the message, and compares the calculated value to the actual value it received in the LRC field. If the two values are not equal, an error results. The LRC is calculated by adding together successive 8–bit bytes in the message, discarding any carries, and then two’s complementing the result. The LRC is an 8–bit field, therefore each new addition of a character that would result in a value higher than 255 decimal simply ‘rolls over’ the field’s value through zero. Because there is no ninth bit, the carry is discarded automatically. A procedure for generating an LRC is: 1.

Add all bytes in the message, excluding the starting ‘colon’ and ending CRLF. Add them into an 8–bit field, so that carries will be discarded.

2.

Subtract the final field value from FF hex (all 1’s), to produce the ones–complement.

3.

Add 1 to produce the twos–complement.

Placing the LRC into the Message

When the 8–bit LRC (2 ASCII characters) is transmitted in the message, the high–order character will be transmitted first, followed by the low–order character. For example, if the LRC value is 61 hex (0110 0001):

Colon

Addr

Func

Data Count

Data

Data

Data

Data

LRC Hi "6" 0x36

Figure 29:

LRC Lo

CR

LF

"1" 0x31

LRC Character Sequence

Example: an example of a C language function performing LRC generation is shown below. The function takes two arguments: unsigned char *auchMsg;

A pointer to the message buffer containing binary data to be used for generating the LRC,

unsigned short usDataLen; The quantity of bytes in the message buffer. LRC Generation Function

static unsigned char LRC(auchMsg, usDataLen)

/* the function returns the LRC as a type unsigned char */

unsigned char *auchMsg ;

/* message to calculate LRC upon */

unsigned short usDataLen ;

/* quantity of bytes in message */

{ unsigned char uchLRC = 0 ;

/* LRC char initialized */

while (usDataLen––)

/* pass through message buffer */

uchLRC += *auchMsg++ ;

/* add buffer byte without carry */

return ((unsigned char)(–((char)uchLRC))) ;

/* return twos complement */

}

Modbus.org Dec 20, 2006

http://www.modbus.org/

38/44

Modbus-IDA.ORG

MODBUS over serial line specification and implementation guide V1.02

6.2.2

CRC Generation

The Cyclical Redundancy Checking (CRC) field is two bytes, containing a 16–bit binary value. The CRC value is calculated by the transmitting device, which appends the CRC to the message. The device that receives recalculates a CRC during receipt of the message, and compares the calculated value to the actual value it received in the CRC field. If the two values are not equal, an error results. The CRC is started by first preloading a 16–bit register to all 1’s. Then a process begins of applying successive 8–bit bytes of the message to the current contents of the register. Only the eight bits of data in each character are used for generating the CRC. Start and stop bits and the parity bit, do not apply to the CRC. During generation of the CRC, each 8–bit character is exclusive ORed with the register contents. Then the result is shifted in the direction of the least significant bit (LSB), with a zero filled into the most significant bit (MSB) position. The LSB is extracted and examined. If the LSB was a 1, the register is then exclusive ORed with a preset, fixed value. If the LSB was a 0, no exclusive OR takes place. This process is repeated until eight shifts have been performed. After the last (eighth) shift, the next 8–bit character is exclusive ORed with the register’s current value, and the process repeats for eight more shifts as described above. The final content of the register, after all the characters of the message have been applied, is the CRC value. A procedure for generating a CRC is: 1. Load a 16–bit register with FFFF hex (all 1’s). Call this the CRC register. 2. Exclusive OR the first 8–bit byte of the message with the low–order byte of the 16–bit CRC register, putting the result in the CRC register. 3. Shift the CRC register one bit to the right (toward the LSB), zero–filling the MSB. Extract and examine the LSB. 4. (If the LSB was 0): Repeat Step 3 (another shift). (If the LSB was 1): Exclusive OR the CRC register with the polynomial value 0xA001 (1010 0000 0000 0001). 5. Repeat Steps 3 and 4 until 8 shifts have been performed. When this is done, a complete 8–bit byte will have been processed. 6. Repeat Steps 2 through 5 for the next 8–bit byte of the message. Continue doing this until all bytes have been processed. 7. The final content of the CRC register is the CRC value. 8. When the CRC is placed into the message, its upper and lower bytes must be swapped as described below. Placing the CRC into the Message

When the 16–bit CRC (two 8–bit bytes) is transmitted in the message, the low-order byte will be transmitted first, followed by the highorder byte. For example, if the CRC value is 1241 hex (0001 0010 0100 0001):

Addr

Func

Data Count

Data

Figure 30:

Modbus.org Dec 20, 2006

Data

Data

Data

CRC Lo

CRC Hi

0x41

0x12

CRC Byte Sequence

http://www.modbus.org/

39/44

Modbus-IDA.ORG

MODBUS over serial line specification and implementation guide V1.02 Calculation algorithm of the CRC 16 OxFFFF → CRC16

CRC16 XOR BYTE → CRC16

N=0

Move to the right CRC16

No

Yes Carry over

CRC16 XOR POLY → CRC 16

N=N+1

No

Yes N>7

No

Yes End of message

Following BYTE

END

XOR = exclusive or N = number of information bits POLY = calculation polynomial of the CRC 16 = 1010 0000 0000 0001 (Generating polynomial = 1 + x2 + x 15 + x 16) In the CRC 16, the 1st byte transmitted is the least significant one.

Modbus.org Dec 20, 2006

http://www.modbus.org/

40/44

Modbus-IDA.ORG

MODBUS over serial line specification and implementation guide V1.02

Example of CRC calculation (frame 02 07)

CRC register initialization

1111

1111

1111

1111

XOR 1st character

0000

0000

0000

0010

1111

1111

1111

1101

0111

1111

1111

1110|1

1010

0000

0000

0001

1101

1111

1111

1111

0110

1111

1111

1111|1

1010

0000

0000

0001

Move 1 Flag to 1,

XOR polynomial Move 2

Flag to 1, XOR polynomial

1100

1111

1111

1110

Move 3

0110

0111

1111

11110

Move 4

0011

0011

1111

11111

1010

0000

0000

0001

1001

0011

1111

1110

Move 5

0100

1001

1111

11110

Move 6

0010

0100

1111

11111

1010

0000

0000

0001

1000

0100

1111

1110

0100

0010

0111

11110

Move 7 Move 8

XOR 2nd character Move 1

Move 2

0010

0001

0011

11111

1010

0000

0000

0001

1000

0001

0011

1110

0000

0000

0000

0111

1000

0001

0011

1001

0100

0000

1001

11001

1010

0000

0000

0001

1110

0000

1001

1101

0111

0000

0100

11101

1010

0000

0000

0001

1101

0000

0100

1111

0110

1000

0010

01111

1010

0000

0000

0001

1100

1000

0010

0110

Move 4

0110

0100

0001

00110

Move 5

0011

0010

0000

10011

1010

0000

0000

0001

Move 3

1001

0010

0000

1000

Move 6

0100

1001

0000

01000

Move 7

0010

0100

1000

00100

Move 8

0001

0010

0100

00010

Most significant

least significant

The CRC 16 of the frame is then: 4112

Modbus.org Dec 20, 2006

http://www.modbus.org/

41/44

MODBUS over serial line specification and implementation guide V1.02

Modbus-IDA.ORG

Example An example of a C language function performing CRC generation is shown on the following pages. All of the possible CRC values are preloaded into two arrays, which are simply indexed as the function increments through the message buffer. One array contains all of the 256 possible CRC values for the high byte of the 16–bit CRC field, and the other array contains all of the values for the low byte. Indexing the CRC in this way provides faster execution than would be achieved by calculating a new CRC value with each new character from the message buffer. Note: This function performs the swapping of the high/low CRC bytes internally. The bytes are already swapped in the CRC value that is returned from the function. Therefore the CRC value returned from the function can be directly placed into the message for transmission. The function takes two arguments: unsigned char *puchMsg;

A pointer to the message buffer containing binary data to be used for generating the CRC

unsigned short usDataLen;

The quantity of bytes in the message buffer.

CRC Generation Function

unsigned short CRC16 ( puchMsg, usDataLen )

/* The function returns the CRC as a unsigned short type */

unsigned char *puchMsg ;

/* message to calculate CRC upon

*/

unsigned short usDataLen ;

/* quantity of bytes in message

*/

/* high byte of CRC initialized

*/

unsigned char uchCRCLo = 0xFF ;

/* low byte of CRC initialized

*/

unsigned uIndex ;

/* will index into CRC lookup table

*/

while (usDataLen--) {

/* pass through message buffer

*/

/* calculate the CRC

*/

{ unsigned char uchCRCHi = 0xFF ;

uIndex = uchCRCLo ^ *puchMsg++ ; uchCRCLo = uchCRCHi ^ auchCRCHi[uIndex] ; uchCRCHi = auchCRCLo[uIndex] ; } return (uchCRCHi