CONSOLIDATED WATER SUPPLY AND SANITATION DESIGN STANDARDS AND SPECIFICATIONS FOR LGUS Department of the Interior and Local Government Office of Project Development Services Water Supply and Sanitation Sector 11th Floor, DILG-NAPOLCOM Center EDSA corner Quezon Avenue West Triangle, Quezon City 1104 www.dilg.gov.ph ® 2021 DILG. All rights reserved The Department of the Interior and Local Government (DILG) is the primary catalyst for excellence in local governance that nurtures self-reliant, progressive, orderly, safe, and globally-competitive communities sustained by an empowered citizenry. The Office of Project Development Services (OPDS) formulates innovative approaches and strategies designed to promote technical capabilities of local government units and assist in the development of program components for the implementation of tested and appropriate systems at the local level. CONTACT OPDS Project Monitoring and Evaluation Division | [email protected] OPDS Water Supply and Sanitation Sector | [email protected] COVER AND PAGE BREAKER PHOTOS Cover Photo – Elevated Reinforced Concrete Water Tank – Tulunan, Cotabato Elevated Steel Water Tank – Mahayag (?) ZDS Public Toilet and Rainwater Collector – Pumps and Appurtenances – Overgaard, T. (2018). Retrieved November 2021 from overgaard.dk Steel Ground Reservoir – Lambunao, Iloilo Transmission and Distribution Lines – Anao, Tarlac (?) Water Source –

TABLE OF CONTENTS CONTENT

SHEET NO.

Elevated Reinforced Concrete Reservoir Elevation Plan

--------------------------------------- RCR21-01

Typical Foundation Plan

--------------------------------------- RCR21-02

Typical Footing Details

--------------------------------------- RCR21-03

Sectional View

--------------------------------------- RCR21-04

Tank Dimension & Details of Joints

--------------------------------------- RCR21-05

Top Slab Reinforcement Details

--------------------------------------- RCR21-06

Wall Reinforcement Details

--------------------------------------- RCR21-07

Bottom Slab Reinforcement Details

--------------------------------------- RCR21-08

Typical Supporting Beam Details

--------------------------------------- RCR21-09

Brace Beam Reinforcement Details

--------------------------------------- RCR21-10

Water Level Indicator Details

--------------------------------------- RCR21-11

Construction Joint Details

--------------------------------------- RCR21-12

Manhole Cover Details

--------------------------------------- RCR21-12

Well Design Well Head Design Details

---------------------------------------- DW21-01

Standard Well Design Details

---------------------------------------- DW21-02

Spring Collection Box Plan and Elevation Details

--------------------------------------- SCB21-01

Spring Collection Box Type “A”

--------------------------------------- SCB21-02

Spring Collection Box Type “B”

--------------------------------------- SCB21-03

Spring Collection Box Type “C”

--------------------------------------- SCB21-04

Spring Collection Box Type “D”

--------------------------------------- SCB21-05

Miscellaneous Details

--------------------------------------- SCB21-06

Pipe layout and Perimeter Fence

--------------------------------------- SCB21-07

Fire Hydrant Fire Hydrant Installation Details

----------------------------------------- FH21-01

Fire Hydrant Barricade Installation

----------------------------------------- FH21-02

CONTENT

SHEET NO.

Ram Pump DIY Ram Pump Head Set-up

--------------------------------------- HRP21-01

DIY Ram Pump Head Details

--------------------------------------- HRP21-02

Ram Pump Schematic Diagram

--------------------------------------- HRP21-03

Elevated Steel Reservoir Elevation and Foundation Plan

--------------------------------------- ESR21-01

Foundation Plan and Section Details

--------------------------------------- ESR21-02

Column Bracing and Manhole Details

--------------------------------------- ESR21-03

Appurtenances Details

--------------------------------------- ESR21-04

Transmission and Distribution Lines Trenching, Excavation and Backfilling

---------------------------------------- WD21-01

Valve Box and Gate Valve Details

---------------------------------------- WD21-02

Buried Gate Valve Details

---------------------------------------- WD21-03

End of Line Blow Off Assembly

---------------------------------------- WD21-05

In Line Blow Off Assembly

---------------------------------------- WD21-06

Pipe Crossing Canal/Creek

---------------------------------------- WD21-09

Pipe Crossing Culvert

---------------------------------------- WD21-11

Thrust Blocks

-------------------------------------- WD21-12A

Pipe in Road Crossings

---------------------------------------- WD21-14

Service Connection

---------------------------------------- WD21-15

Public Toilet Facility

---------------------------------------- PTF21-01

Ladder & Safety Cage DESIGN CRITERIA

CENTERLINE OF SUPPORTING BEAM

S

S

S

1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12.

fc' = 3,000psi / 210kg/cm² fc = 1,350psi / 94.5kg/cm² fs = 18,000psi / 1260kg/cm² n =9 j = 0.856 p = 0.15 (min) R = 235psi / 16.45kg.cm² LL = 150kg/cm² / DL = 2400kg/cm² / k = 0.403 W = 62.4pcf / 996.8kg/m³ SOIL BEARING CAPACITY = 9750kg/m²

NOMECLATURE d - TOTAL DEPTH OF SUPPORTING BEAM d' - TOTAL DEPTH OF BRACE BEAM

S

D - DEPTH BELOW FINISHED GRADELINE TO CENTERLINE OF LOWEST BRACE BEAM

F.G.L.

S - CENTER TO CENTER OF BRACE BEAM H - HEIGHT OF TANK

ELEVATION NOTES: 1. 2. 3.

THE DESIGN OF THE CONCRETE MIX SHALL BE SUCH THAT THE RESULTANT CONCRETE IS SUFFICIENTLY IMPERVIOUS. ALL JOINTS SHALL BE MADE WATERTIGHT AS THESE ARE POTENTIAL SOURCES OF LEAKAGE. PROVIDE SLOPES TO ENSURE DRAINAGE FOR THE TOP AND BOTTOM SLABS nxS S n

4.80 M n x S 2.40 M 2.10 M 2 3

Title

nxS 2.60 M 3

nxS nxS 2.35 M 2.72 M 4 4

Department of the Interior and Local Government

Office of Project Development Services

ELEVATED R. C. WATER RESERVOIR

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. RCR21-01 REINFORCED CONCRETE RESERVOIR

F

FOOTING

G

F

BRACE BEAM

F

BRACE BEAM

PLAN G

D

COLUMNS

80cm (min)

BRACE BEAM

E

SEE DETAIL COLUMN & FOOTING

F

FOOTING SECTION

TYPICAL FOUNDATION PLAN / SECTION Title

Department of the Interior and Local Government

Office of Project Development Services

ELEVATED R. C. WATER RESERVOIR

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. RCR21-02 REINFORCED CONCRETE RESERVOIR

DESIGN DATA 1. 2. 3. 4. 5. 6. 7. 8.

VERT. BARS

SOIL PRESSURE = 9750kg/m² fs = 1260kg.cm² fc = 210kg/cm² v = 4.20kg/cm² n = 9 R = 16.45kg/cm² j = 0.866 W (concrete) = 2400kg/m³

E

100mm

LATERAL TIES (See Dwg _____ )

F

CAPACITY COLUMN SIZE SQUARE FOOTING G (M) (LITERS) (cm) E (M) F (M) 22,600 31,700

0.30 0.30

30 x 30 30 x 30

1.75 2.00

BAR EACHWAY

D (cm)

3.80 3.90

12 - 12mm Ø

15

13 - 12mm Ø

15 15

38,200 45,600

30 x 30 30 x 30

0.30 0.35

2.50 2.50

4.10 4.40

14 - 12mm Ø 15 - 12mm Ø

15

52,600 60,300

35 x 35 35 x 35

0.30 0.30

2.59 2.60

4.70 5.00

15 - 12mm Ø

10

16 - 12mm Ø

10

68,400 74,100

40 x 40 40 x 40

0.30 0.30

2.70 2.70

5.30 5.50

17 - 12mm Ø

10

17 - 12mm Ø

10

TYPICAL FOOTING DETAILS Title

Department of the Interior and Local Government

Office of Project Development Services

ELEVATED R. C. WATER RESERVOIR

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. RCR21-03 REINFORCED CONCRETE RESERVOIR

tw

tw

B

C

tw

B

tw

STEEL RUNGS @ 0.30m o.c.

C M.H.

B

B

tw

tw

tw

TOP SLAB

tw

tw

BOTTOM SLAB

B

tw

B

tw

tw

B

B B

A

tf

tw

HOR. SECTION @ MID-HEIGHT (Section B - B)

tb

BOTTOM SLAB

D

D

tw

VERT. SECTION (C - C)

Title

BOTTOM SLAB (D - D)

Department of the Interior and Local Government

Office of Project Development Services

ELEVATED R. C. WATER RESERVOIR

Drawn by:

Reviewed by:

Sheet No. RCR21-04 REINFORCED CONCRETE RESERVOIR

B

SEE DETAIL "A"

tf

tw

A

Max. Depth of Water

tw

SEE DETAIL "B"

tb

BOTTOM SLAB

VERTICAL SECTION tf

WATER STOP BOTTOM SLAB

150mm

50

50

DETAIL "B" CAPACITY (LITERS) 22, 600 31, 700

A (M.)

DETAIL "A"

2.00

1.85

B (M.) 3.50

2.60

2.45 2.65

3.60 3.80

15 15

15 15

20 20

3.00

2.85 2.85

4.00 4.30

15 15

20 20

20 20

MAX. DEPTH OF WATER (M.)

tf (cm) 15

tw (cm) 15

tb (cm) 20

38, 200

2.80

45, 600 52, 600 60, 300

3.00

3.00

2.85

4.60

20

20

25

68, 400

3.00

74, 100

3.00

2.85 2.85

4.90 5.10

20 20

20 20

25 25

TANK DIMENSIONS & DETAILS OF CONSTRUCTION JOINTS

Title

Department of the Interior and Local Government

Office of Project Development Services

ELEVATED R. C. WATER RESERVOIR

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. RCR21-05 REINFORCED CONCRETE RESERVOIR

tw

B B/4

tw



TOP BARS

BOT. BARS

A

B

B

B/4

B

B/4

A

PLAN TOP REINF. BARS (B.W.)

BOT. REINF. BARS (B.W.)

SECTION A - A B/4

B/4

TOP REINF. BARS (B.W.)

BOT. REINF. BARS (B.W.)

SECTION B - B

B (M)

tf (cm)

tw (cm)

TOP REINFORCING BARS BOTHWAYS

3.50

15

15

12mm Ø @ 30cm o.c.

12mm Ø @ 30cm o.c.

3.60 3.80

15 15

15 15

12mm Ø @ 30cm o.c. 12mm Ø @ 30cm o.c.

12mm Ø @ 30cm o.c. 12mm Ø @ 30cm o.c.

45, 600 52, 600 60, 300

4.00

15

20

4.30 4.60

15 20

20 20

12mm Ø @ 30cm o.c. 12mm Ø @ 30cm o.c.

12mm Ø @ 30cm o.c. 12mm Ø @ 30cm o.c.

68, 400

4.90 5.10

20 20

20 20

16mm Ø @ 30cm o.c. 16mm Ø @ 30cm o.c.

16mm Ø @ 30cm o.c. 16mm Ø @ 30cm o.c.

16mm Ø @ 30cm o.c.

16mm Ø @ 30cm o.c.

CAPACITY (LITERS) 22, 600 31, 700 38, 200

74, 100

BOTTOM REINFORCING BARS BOTHWAYS

TOP SLAB REINFORCEMENT Title

Department of the Interior and Local Government

Office of Project Development Services

ELEVATED R. C. WATER RESERVOIR

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. RCR21-06 REINFORCED CONCRETE RESERVOIR

tw

B

tf

SEE DETAIL "A"

A

Max. Depth of Water

tw

SEE DETAIL "B"

tb

BOTTOM SLAB

VERTICAL SECTION tf

WATER STOP BOTTOM SLAB

150mm

50

50

DETAIL "B" CAPACITY (LITERS) 22, 600 31, 700

A (M.)

DETAIL "A"

2.00

1.85

B (M.) 3.50

2.60

2.45

3.60

15

15

20

38, 200

2.80

45, 600 52, 600 60, 300

3.00

2.65 2.85

3.80 4.00

15 15

15 20

20 20

2.85 2.85

4.30 4.60

15 20

20 20

20 25

68, 400

3.00

74, 100

3.00

2.85 2.85

4.90 5.10

20 20

20 20

25 25

3.00 3.00

MAX. DEPTH OF WATER (M.)

tf (cm) 15

tw (cm) 15

tb (cm) 20

TANK DIMENSIONS & DETAILS OF CONSTRUCTION JOINTS

Title

Department of the Interior and Local Government

Office of Project Development Services

ELEVATED R. C. WATER RESERVOIR

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. RCR21-07 REINFORCED CONCRETE RESERVOIR

tw

tw

B

tw

B

Sp

tf

ROOF

HOR. REINF. BAR

A

VERT. REINF. BARS

B

HOR. REINF. BAR

WATER STOP HOR. REINF. BARS

Sp

tb

BOTTOM SLAB

Sp

PLAN @ MID-HEIGHT OF TANK

CAPACITY (LITERS)

A (m)

tb (cm)

TYP. WALL DETAIL

B VERTICAL REINFORCING (m) STEEL BARS

HORIZONTAL REINFORCING BARS

Sp (cm)

22,600

2.00

20

3.50

12 mm Ø @ 30 cm O.C.

12 mm Ø @ 30 cm O.C.

35

31,700

2.50

20

3.60

16 mm Ø @ 20 cm O.C.

16 mm Ø @ 25 cm O.C.

50

38,200

2.80

20

3.80

16 mm Ø @ 18 cm O.C.

16 mm Ø @ 25 cm O.C.

50

45,600

3.00

20

4.00

16 mm Ø @ 18 cm O.C.

16 mm Ø @ 25 cm O.C.

50

52,600

3.00

20

4.30

16 mm Ø @ 15 cm O.C.

16 mm Ø @ 25 cm O.C.

50

60,300

3.00

25

4.60

16 mm Ø @ 15 cm O.C.

16 mm Ø @ 25 cm O.C.

50

68,400

3.00

25

4.90

16 mm Ø @ 15 cm O.C.

16 mm Ø @ 25 cm O.C.

50

74,100

3.00

25

5.10

16 mm Ø @ 15 cm O.C.

16 mm Ø @ 25 cm O.C.

50

WALL REINFORCEMENT Title

Department of the Interior and Local Government

Office of Project Development Services

ELEVATED R. C. WATER RESERVOIR (Drawing #7)

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. RCR21-08 REINFORCED CONCRETE RESERVOIR

tw B/4 TOP BARS



BOT. BARS

E

E

F

F

B/4

B

B/4

tw

B

PLAN tw

tw

B

BOT. REINF. BARS (B.W.)

tb

TOP REINF. BARS (B.W.)

SECTION E - E

C

C BOT. REINF. BARS (B.W.)

tb

TOP REINF. BARS (B.W.)

SECTION F - F

C

C

B (M)

tb (cm)

tw (cm)

C (cm)

TOP REINFORCING BARS BOTHWAYS

BOTTOM REINFORCING BARS BOTHWAYS

22, 600 31, 700

3.50 3.60

15 15

15 15

30 30

16mm Ø @ 18cm o.c.

16mm Ø @ 30cm o.c.

38, 200

3.80 4.00

15 15

15 20

30 30

16mm Ø @ 12cm o.c. 16mm Ø @ 10cm o.c.

16mm Ø @ 30cm o.c. 16mm Ø @ 30cm o.c.

4.30 4.60

15 20

20 20

35 35

20mm Ø @ 15cm o.c. 20mm Ø @ 12cm o.c.

20mm Ø @ 30cm o.c. 20mm Ø @ 30cm o.c.

20mm Ø @ 15cm o.c.

20mm Ø @ 30cm o.c.

4.90 5.10

20 20

20 20

40 40

20mm Ø @ 12cm o.c. 20mm Ø @ 10cm o.c.

20mm Ø @ 30cm o.c. 20mm Ø @ 30cm o.c.

CAPACITY (LITERS)

45, 600 52, 600 60, 300 68, 400 74, 100

BOTTOM SLAB REINFORCEMENT Title

Department of the Interior and Local Government

Office of Project Development Services

ELEVATED R. C. WATER RESERVOIR (Drawing #8)

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. RCR21-09 REINFORCED CONCRETE RESERVOIR

b

b T - B2

B - B1

B - B1

tw

d

T - B1

d

T - B1

SECTION @FACE OF SUPPORT

SECTION @MID-SPAN

B - B1

B - B1

T - B2



T - B1

L/4

10mm Ties

3@8cm

3@16cm

Rest @30cm o.c.

C

L/2

HALF SECTION OF BEAM BEAM SIZE b x d (cm)

T - B2

B - B1

T - B1

tw (cm)

22, 600 31, 700

30 x 40 30 x 40

2 - 20mmØ

3 - 20mmØ

3 - 20mmØ

2 - 20mmØ

3 - 20mmØ

3 - 20mmØ

15 15

3.20 3.30

30 30

38, 200

30 x 40 30 x 40

2 - 20mmØ 2 - 20mmØ

3 - 20mmØ 3 - 20mmØ

3 - 20mmØ 3 - 20mmØ

15 20

3.50 3.80

30 30

30 x 45

2 - 25mmØ 2 - 25mmØ

3 - 25mmØ 3 - 25mmØ

3 - 25mmØ 3 - 25mmØ

20

4.00

35

2 - 25mmØ 2 - 25mmØ

3 - 25mmØ 3 - 25mmØ

3 - 25mmØ 3 - 25mmØ

20 20

4.30 4.50

35 40

20

4.70

40

CAPACITY (LITERS)

45, 600 52, 600 60, 300 68, 400

30 x 45 40 x 50

74, 100

40 x 50

L (M)

C (cm)

NOTES: 1. 2. 3. 4.

MAXIMUM AGGREGATES = 25mm STIRRUPS ARE10mm dia. FOR BARS OF 25mm dia OR SMALLER CLEAR DISTANCE FROM FACE OF BEAM TO STIRRUPS = 4cm MINIMUM CLEAR DISTANCE BETWEEN PARALLEL BARS NOT LESS THAN NORMAL DIAMETER OF BAR, 1 31 TIMES MAXIMUM SIZE OF COARSE AGGREGATES (25mm)

TYPICAL DETAIL - SUPPORTING BEAMS Title

Department of the Interior and Local Government

Office of Project Development Services

ELEVATED R. C. WATER RESERVOIR (Drawing #9)

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. RCR21-10 REINFORCED CONCRETE RESERVOIR

C

C

BRACE BEAM

10

10

25

25

25

25

25

25

25

25

25

25

25

25

25

25

25

25

10

10

10

10

COLUMN

COLUMN

SECTION b

TIES

d

TOP BARS

BOTTOM BARS

CAPACITY (LITERS)

BRACE BEAM b x d (cm)

TOP BARS

BOTTOM BARS

C (cm)

22, 600 31, 700

30 x 30 30 x 35

3 - 20mmØ

3 - 20mmØ

30 x 35 30 x 35

3 - 20mmØ 4 - 20mmØ

30 30

38, 200

3 - 20mmØ 4 - 20mmØ 4 - 20mmØ 4 - 20mmØ

4 - 20mmØ 4 - 20mmØ

4 - 20mmØ

4 - 20mmØ

35 35

4 - 20mmØ 4 - 20mmØ

4 - 20mmØ 4 - 20mmØ

40 40

45, 600 52, 600 60, 300 68, 400 74, 100

30 x 40 30 x 40 40 x 45 40 x 45

30 30

BRACE BEAM REINFORCEMENT DETAILS

Title

Department of the Interior and Local Government

Office of Project Development Services

ELEVATED R. C. WATER RESERVOIR (Drawing #10)

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. RCR21-11 REINFORCED CONCRETE RESERVOIR

75mm STD PULLEY

300

200

WEIR

7kg COPPER FLOAT

OVERFLOW PIPE

150

WEIR

5mm BRONZE CABLE

200

INDICATOR PLATE (4.5kg).

OVERFLOW PIPE

OVERFLOW PIPE CONN. DET. 75mm STD PULLEY

REMOVABLE PIPE

BOTTOM SLAB

INDICATOR GUIDE

COUPLING RISER PIPE

LEVEL INDICATOR Title

SUPPLY PIPE CONN. DETAIL Department of the Interior and Local Government

Office of Project Development Services

ELEVATED R. C. WATER RESERVOIR (Drawing #11)

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. RCR21-12 REINFORCED CONCRETE RESERVOIR

50mm FB CAGE STRAP HOR. REINF. BAR

WATER STOP

C

BOTTOM SLAB

0.20

tb

0.3 0m

0.30m

R.C. COLUMN

C

PLAN

CONSTRUCTION JOINT DETAIL 50mm FB CAGE STRAP

1.00m

50mm FB LADDER STRINGER w/ 20mm LADDER RUNGS @ 300mm o.c. COLUMN

0.60

0.60

5mm PLATE COVER

ELEVATION

LADDER CAGE DETAILS PLAN ANGULAR BAR FRAME ( 40 x 40mm)

5mm PLATE COVER TOP SLAB

SECTION ANGULAR BAR FRAME ( 40 x 40mm)

Title

MANHOLE COVER DETAILS Department of the Interior and Local Government

Office of Project Development Services

ELEVATED R. C. WATER RESERVOIR (Drawing #12

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. RCR21-13 REINFORCED CONCRETE RESERVOIR

Pressure Gauge Gate Valve

Non-Return Valve

Flow Meter

45° Elbow

1.0M

Well Head Steel Plate Support (See Details)

GRAVEL TUBE

GROUND LEVEL

Electric Submersible Pump Set

WELL HEAD

Welded G.I. Pipe DN20 w/ End Cap (Sounding Tube)

220mm

50mm

30mm Ø Hole for Pump Wires & Cable

DETAIL WELL HEAD STEEL SUPPORT

Title

Department of the Interior and Local Government

Office of Project Development Services

TYPICAL WELL HEAD

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. DW21-01

Pressure Gauge Gate Valve

Non-Return Valve

Flow Meter

45° Elbow

1.0M

Well Head Steel Plate Support (See Details)

GRAVEL TUBE

GROUND LEVEL

Electric Submersible Pump Set

WELL HEAD

Welded G.I. Pipe DN20 w/ End Cap (Sounding Tube)

220mm

50mm

30mm Ø Hole for Pump Wires & Cable

DETAIL WELL HEAD STEEL SUPPORT

Title

Department of the Interior and Local Government

Office of Project Development Services

TYPICAL WELL HEAD

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. DW21-01A

GRAVEL PACKED TUBE w/ END CAP DN25 SOUNDING TUBE w/ END CAP, DN25

CONCRETE BASE (600 x 600mm)

1.0M (min) or 1.0M Above Potential Flood Level

SOUNDING TUBE w/ END CAP, DN25

SANITARY SEAL (CEMENT GROUT)

WELL-CASING (uPVC or STEEL) 6"Ø (min)

10.0M (min)

GROUND LEVEL

CENTRALIZER: METAL 4cm x 30cm, 4 pcs. ea LEVEL

WIRE WOUND STAINLESS SCREEN OR SLOTTED CASING ACTUAL SETTING OF SCREEN WILL DEPENDS OF SOIL FORMATION AND RESULT OF DRILLING & ELECTRIC LOG, IF ANY.

SUMP PIPE w/ CLOSE BOTTOM

CEMENT PLUG OR WELDED BOTTOM PLATE

STANDARD WELL DESIGN

Title

Department of the Interior and Local Government

Office of Project Development Services

STANDARD WELL DESIGN

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. DW21-02

0.60

VARIABLE

OVERFLOW PIPE DRAINAGE

AIR VENT VARIABLE

SUPPLY PIPE

RAISED MANHOLE

DRAIN PIPE

0.60

0.60

PLAN

DRAINAGE

AIR VENT

RAISED MANHOLE OVERFLOW PIPE (0.10m, min. Lower than the Spring Eye))

0.15

TO BE GROUTED AND PLASTERED WITH MORTAR EXCEPT AT THE EYE OF THE SPRING. EYE OF THE SPRING TO BE ENLARGE (REMOVE SILT, ROCK, ETC., BUT DO NOT DISTURB UNDERGROUND ROCK FORMATIONS. PLACE STONES AGAINTS EYE TO PREVENT EROSION.

VARIABLE

EYE OF THE SPRING

SUPPLY PIPE DRAIN PIPE

ELEVATION Title

Department of the Interior and Local Government

Office of Project Development Services

SPRING TYPE " A " SPRING COLLECTION BOX (SPRING BOX DOWNHILL OF SPRING)

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. SCB21-02 SPRING COLLECTION BOX

0.60

VARIABLE

OVERFLOW PIPE AIR VENT SUPPLY PIPE VARIABLE

DRAINAGE

RAISED MANHOLE

DRAIN PIPE

0.60

0.60

0.60

AIR VENT

RAISED MANHOLE

OVERFLOW PIPE

DRAINAGE

SUPPLY PIPE EYE OF THE SPRING DRAIN PIPE

TO BE PLASTERED WITH MORTAR EXCEPT AT THE EYE OF THE SPRING. EYE OF THE SPRING TO BE ENLARGE (REMOVE SILT, ROCK, ETC., BUT DO NOT DISTURB UNDERGROUND ROCK FORMATIONS. PLACE STONES AGAINTS EYE TO PREVENT EROSION.

Title

Department of the Interior and Local Government

Office of Project Development Services

SPRING TYPE " B " SPRING COLLECTION BOX (SPRING FLOWS ALMOST @ GROUND LEVEL)

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. SCB21-03 SPRING COLLECTION BOX

B AIR VENT

A

STEEL PLATE MANHOLE COVER 0.60M

OVERFLOW PIPE

SUPPLY PIPE

DRAIN PIPE

B

MANHOLE COVER DET. PLAN

AIR VENT

AIR VENT

MANHOLE

0.60

MANHOLE

EYE OF THE SPRING

OVERFLOW PIPE

OVERFLOW PIPE

SUPPLY PIPE

SUPPLY PIPE

DRAIN PIPE

DRAIN PIPE

SECTION A - A

Title

SECTION B - B

Department of the Interior and Local Government

Office of Project Development Services

SPRING TYPE " C " SPRING COLLECTION BOX (SPRING INSIDE CAVERN / CAVE)

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. SCB21-04 SPRING COLLECTION BOX

0.60

VARIABLE

OVERFLOW PIPE

SPRING DRAINAGE

AIR VENT VARIABLE

SUPPLY PIPE

SPRING RAISED MANHOLE

DRAIN PIPE

0.60

0.60

SPRING

PLAN

DRAINAGE MORTAR COVER PEA SIZE GRAVEL COARSE GRAVEL AIR VENT

RAISED MANHOLE

VARIABLE

OVERFLOW PIPE

SIZE OF OPENING TO BE DETERMINED BY ENGINEER

SUPPLY PIPE DRAIN PIPE

ELEVATION

Title

Department of the Interior and Local Government

Office of Project Development Services

SPRING TYPE " D " SPRING COLLECTION BOX (SCATTERED SPRING)

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. SCB21-05 SPRING COLLECTION BOX

25mm G.I. Pipe Vent 25mm G.I. Pipe Nipple

Side of Box

25mm G.I. Coupling w/ Screen

25 mm G.I. Pipe

25 mm G.I. Pipe 25mm G.I. Pipe Elbow 25mm G.I. Pipe Nipple 25mm G.I. Coupling w/ Screen 0.10

Top of Box

TOP AIR VENT PIPE

SIDE AIR VENT PIPE

Gate Valve G.I. Pipe Elbow

G.I. Pipe

G.I. Coupling w/ Screen

G.I. Coupling w/ Screen

0.15

FLOORING OF BOX

SUPPLY PIPE

OVERFLOW PIPE

Gate Valve G.I. Pipe

FLOORING OF BOX

DRAIN PIPE

Title

Department of the Interior and Local Government

Office of Project Development Services

SPRING COLLECTION BOX MISCELANEOUS DETAILS

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. SCB21-06 SPRING COLLECTION BOX

DRAINAGE CHANNEL

PERIMETER FENCE

AIR VENT

PERIMETER FENCE

ACCESS MANHOLE

0.60

0.60

0.60

PERIMETER FENCE

VARIABLE

APRON

OVERFLOW PIPE

VARIABLE

SUPPLY PIPE

DRAIN PIPE

PERIMETER FENCE

NOTES: 1. 2. 3.

ALL PIPES & FITTINGS ARE G. I. SCHEDULE 40. SUPPLY PIPE & VALVE IS THE SAME SIZE WITH TRANSMISSION LINE. NO WELDING ON PIPE IS ALLOWED.

Title

Department of the Interior and Local Government

Office of Project Development Services

SPRING COLLECTION BOX PIPE LAYOUT & PERIMETER FENCE

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. SCB21-07 SPRING COLLECTION BOX

0.45 to 0.60

100mm (4") x 63mm ( 2 21") ANGLE FIRE HYDRANT VALVE (SEE SPECIFICATIONS)

0.60 SQ. CONCRETE PAD IN NON-SIDEWALK AREAS

100mm (4") FABRICATED 90° ELBOW 100mm (4") FLANGED GATE VALVE

100mm (4") STEEL PIPE (12GA) W/ CEMENT MORTAR LINING & COATING

TEE WITH FLANGED BRANCH

NOTES : 1.

ALL DIMENSIONS ARE IN METERS EXCEPT WHERE OTHERWISE SHOWN.

2.

WHERE NO CURBS OR GUTTERS EXIST, THE HYDRANTS SHALL BE LOCATED WITHIN 1.50M OF THE ROAD RIGHT-OF-WAY OR AS DIRECTED BY THE ENGINEER & BARRICADES SHALL BE INSTALLED.

3.

HYDRANTS AT INTERSECTIONS SHALL BE AT THE CURB RETURN. OTHER THAN STREET INTERSECTION, HYDRANTS SHALL BE INSTALLED ON LOT LINES.

4.

HYDRANTS SHALL BE PAINTED IN ACCORDANCE WITH THE SPECIFICATIONS. COLOR SHALL BE YELLOW UNLESS OTHERWISE DIRECTED BY THE OWNER

5.

WELD ALL JOINTS EXCEPT WHERE OTHERWISE SHOWN

Title

Department of the Interior and Local Government

Office of Project Development Services

FIRE HYDRANT INSTALLATION (LWUA Standard Drawing)

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. FH21-01 FIRE HYDRANT

EDGE OF ROADWAY BARRICADE 25mm CHAMFER (TYP)

0.15

PE TY U

M M

O

'L

m

0.15

m

(C

ET

O

TL

63 m

30°

) PE

30°

TY

m

'L

O

U

M

M

TL

O

ET

(C

1.00M

)

0 10

p)

Ty 3(

0.6

GROUND LEVEL 4 - 16mmØ BARS w/ 10mm TIES @ 0.20M o.c.

1.20M

PLAN FOR SETTING BARRICADE 0.15 X 0.15 CONCRETE POST BARRICADE

ELEVATION OF CONCRETE BARRICADE

Title

Department of the Interior and Local Government

Office of Project Development Services

FIRE HYRANT BARRICADE INSTALLATION (LWUA Standard Drawing)

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. FH21-02 FIRE HYDRANT

Title

Office of Project Development Services

Department of the Interior and Local Government

RAM PUMP

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No.

HYDRAULIC RAM PUMP

HRP21-01

DIY RAM PUMP

GATE VALVE

OUTFLOW PIPE

PRESSURE GAUGE

220 280

2.0 2.5

70

6.0

255 310

4.0 5.0

180

125

105

215

260

15 33

3.5

3.0

200

96.5 156

135

10

1.5

7.5

282

236

173

150

130

100

79

54

29

20

30

185

155

115

100

87

66

53

36

19.5

40

140

118

86

75

65

40.5

33

19

12.5

112

94

69

60

51

32.5

25

15

50

INFLOW PIPE

CHECK VALVE (SWING TYPE)

Lift - Vertical Height to which Water is Raised Above the Ram (m) 65 1.0

144

5.0

77

Working Fall (m)

CHECK VALVE (SPRING TYPE)

Ram Performance Data for a Supply of 1 liter/minute Liters Delivered over 24 Hours

AIR CHAMBER

AIR CHAMBER

PRESSUDE GAUGE GATE VALVE OUTFLOW PIPE

WASTE WATER CHECK VALVE

INFLOW PIPE

CHECK VALVE

DIY RAM PUMP

Title

Department of the Interior and Local Government

Office of Project Development Services

RAM PUMP

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. HRP21-02 HYDRAULIC RAM PUMP

Title

RAM PUMP

2.0

2.5

310

5.0

Collection Box RAM PUMP (See Details)

255

6.0

215

180

4.0

260

125

105

70

33

15

3.5

3.0

156

220 280

1.5

200

65

10 96.5

7.5

282

236

173

150

130

100

79

54

29

20

185

155

115

100

87

66

53

36

19.5

30

140

118

86

75

65

40.5

33

19

12.5

40

94

69

60

51

32.5

25

15

50

112

Lift - Vertical Height to which Water is Raised Above the Ram (m) 77

144

5.0 135

1.0

Working Fall (m)

Ram Performance Data for a Supply of 1 liter/minute Liters Delivered over 24 Hours

Drawn by: Engr. C. O. De Ocampo September 2021

(Q x F X E) L

D - Amount of water delivered in 24hrs. Q - Quantity of water supplied @ source in LPM F - The fall or height of source above the RAM PUMP L - The lift height of the point of use above the ram in meters. E - Efficiency 0.66 for commercial model 0.33 for home built

where:

D=

GENERAL FORMULA:

Water Tank

Lift

Fall

Office of Project Development Services

Department of the Interior and Local Government

Reviewed by:

Sheet No.

HYDRAULIC RAM PUMP

HRP21-03

FOUNDATION PLAN

Title

ELEVATED STEEL WATER RESERVOIR

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

24,000

90,850

18,000

68,000

22,000

16,000

60,500

83,300

14,000

55,000

20,000

12,000

45,400

4.60

4.40

4.35

4.20

4.20

4.10

3.80

3.60

3.30

2.90

4.60

4.40

4.35

4.20

4.20

4.10

3.80

3.60

3.30

2.90

2.30

2.20

2.20

2.10

2.10

2.05

1.90

1.80

1.65

1.45

0.80

0.80

0.80

0.70

0.70

0.70

0.70

0.60

0.60

0.50

100 x 90 x 8

W6 x 24

100 x 90 x 10

100 x 90 x 8

W6 x 24

W6 x 28

100 x 76 x 8

W6 x 24

100 x 90 x 10

100 x 76 x 8

W6 x 24

W6 x 28

76 x 76 x 8

W6 x 20

100 x 90 x 10

76 x 76 x 6

W6 x 20

W6 x 28

76 x 76 x 6

W6 x 20

35

35

32

32

30

30

25

25

22

22

Rod (mm)

n=3

6.222

6.081

6.000

5.940

5.940

5.798

5.374

4.233

4.950

4.525

A

4.40

4.30

4.30

4.20

4.20

4.10

3.80

3.70

3.50

3.20

B

A

n=3

6.647

6.364

6.364

6.222

6.222

6.080

5.780

5.657

5.374

4.950

2L-Struts (See ESR21-04)

75,700

10,000

37,800

B

8,000

ELEVATION Column 2L STRUTS ASTM A36 (mm)

Std Tower Rod

6,000

h" (m)

Riser Pipe

30,200

h' (m)

Ladder & Safety Cage (See ESR21-03) 4.70

4.50

4.50

4.40

4.40

4.30

4.10

4.00

3.80

3.50

B

n=3

6.930

6.647

6.647

6.505

6.505

6.364

6.080

5.780

5.515

5.090

A

4.90

4.70

4.70

4.60

4.60

4.50

4.30

4.10

3.90

3.60

B

H = 9.00m S = 3.30m

7mm Thk. Bot. Plate

22,700

h (m)

h'

Overflow Pipe

H = 8.10m S = 2.70m

S h

h''

n=4

7.540

7.070

7.070

6.788

6.788

6.647

6.505

6.222

5.940

5.150

A

5.20

5.00

5.00

4.80

4.80

4.70

4.60

4.40

4.20

3.90

B

H =10.80m S = 2.70m

Ladder (Inside & Outside) (see ESR21-03)

H = 6.60m S = 2.20m

S

Manhole (see ESR21-03)

GALS.

D (m)

S

150mmØ Vent

LITERS

CAPACITY

A

B

D

5mm Thk. Shell Plate

Department of the Interior and Local Government

Office of Project Development Services

Sheet No.

ELEV. STEEL RESERVOIR

ESR21-01

STD. NUT 400mm

TOP OF BASE PLATE

A

SECTION Title

35mm Ø

32mm Ø 32

35

400 400 0.75 10 - 20mm Ø 11 - 20mm Ø 10 - 10mm Ø 11 - 10mm Ø 10 - 20mm Ø

0.85 11 - 20mm Ø 12 - 20mm Ø 11 - 10mm Ø 12 - 10mm Ø 12 - 20mm Ø 0.75

0.65

2.00

2.20

2.40

46,000 - 60,000

61,000 - 75,000

76,000 - 90,000

2.20

1.80

2.00

25mm Ø

25mm Ø

30mm Ø 30 400 8- 20mm Ø 9 - 20mm Ø 10 - 20mm Ø 9 - 10mm Ø 10 - 10mm Ø 0.65 0.55

30

25 400

400 6 - 20mm Ø

6 - 20mm Ø 7 - 20mm Ø 6 - 10mm Ø 7 - 10mm Ø

9 - 20mm Ø 8 - 10mm Ø 9 - 10mm Ø 8 - 20mm Ø

6 - 20mm Ø 1.60

BAR " B " Design Data:

20,000 - 30,000

BAR " A "

BAR " D "

31,000 - 45,000

600mm

BAR " C "

1.80

b (M.) a (M.)

BAR " E "

A (M.)

1000mm

0.40

B (M.)

0.40

CAPACITY (LITERS)

BASE PLATE (See Details)

10mm Ties [email protected] rest @ 0.20m o.c.

200

100

PLAN

0.55

BAR B BAR A

A NOTE : 1. Additional excavation below 1.5m depth, made to reach good natural soil shall be filled w/ unreinforced lean cement concrete.

0.50

BAR C

B BAR " A " BAR " B "

0.45

a

0.35

0.50

BAR D

0.40

0.50

a

BAR E (Top & Bot Bars)

COL. BASE PLATE DETAIL

1.60

t (mm)

BOLT DETAIL

1.40

80mm

G (mm)

80mm

BOLT D (mm)

900mm

400mm

BOLT HOLE BOLT Dia + 4mm

Reinf. Bars: fs =1260kg/cm² Concrete: fc'=210kg/cm² Soil Brng: q = 9750kg/m² Wind Load = wl=150kg/m²

Department of the Interior and Local Government

Office of Project Development Services

ELEVATED STEEL WATER RESERVOIR

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. ESR21-02 ELEV. STEEL RESERVOIR

0.65m

50mm FB CAGE STRAP

5mm Thk PLATE

COLUMN 0.3

INSIDE LADDER 0.30m

0m

5mm Thk ROOF PLATE 0.60m

ELEVATION PLAN

0.

30 m

5mm Thk PLATE (COVER)

50mm FB CAGE STRAP

PLAN

1.00m

50mm FB LADDER STRINGER w/ 20mm LADDER RUNGS @ 300mm o.c. COLUMN

MANHOLE DETAILS 63 X 63mm HAND RAILING 5mm Thk. Shell Plate 36x36x5mm W Rail @0.40m

12mm @.10mm o.c. CATWALK

ELEVATION 2L GIRDER (Same size as struts)

LADDER CAGE DETAILS

2C 5 X 9 (4 Places) 2L STRUTS 10mm SPACER PLATE 50

150 50

COLUMN ( See Table) 50

10mm Thk PAD PLATE

TOWER ROD (See Table) 50

STD CLEVIS w/ STD PIN

7mm BOT PLATE

10mm STRUT STIFFINER

BALCONY, COLUMN - SHELL CONN. DETAILS COLUMN-BRACING DETAILS Title

Department of the Interior and Local Government

Office of Project Development Services

ELEVATED STEEL WATER RESERVOIR

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. ESR21-03 ELEV. STEEL RESERVOIR

5mm Thk ROOF PLATE

150mm AIR VENT 5mm Thk ROOF PLATE 75mm STD PULLEY

FLOAT GUIDE (0.5mm Bronze Cable)

L50 x 50 x 3mm ROOF RING

4.5kg INDICATOR PLATE

COPPER FLOAT w/ GUIDE EARS (Wt. = 7.0kg)

5mm Thk Reinf Plate

OVERFLOW PIPE (Same size as inlet)

INDICATOR GUIDE

0.5mm BRONZE CABLE SCALE BOTTOM PLATE

75mm STD PULLEY

INSIDE

OUTSIDE COLUMN

WATER LEVEL INDICATOR DETAILS CANAL

RISER CLAMP BRACING RISER PIPE (Inlet / Outlet)

E

A

OVERFLOW PIPE DETAILS

E

N AI R

D

A

R

2L STRUT

To

:S

E

R

V

IC

0.15

GUSSET PLATE COLUMN

P UM P : Fr

CE UR O /S

COLUMN BRACINGS DETAILS

RISER PIPE ASSEMBLY

Title

Department of the Interior and Local Government

Office of Project Development Services

ELEVATED STEEL WATER RESERVOIR

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. ESR21-04 ELEV. STEEL RESERVOIR

5mm SHELL REMOVABLE PIPE

2L RING GIRDER SAME SIZE AS STRUTS SPRING LINE

BOTTOM PLATE 7mm BOT.PLATE

G.I. COUPLING

10mm BACKING PLATE RISER PIPE (Inlet / Outlet)

SHELL & BOTTOM PLATE TO RING GIRDER CONN. DETAIL RISER PIPE - BOT. PLATE CONN. 150mmØ AIR VENT 5mm Thk ROOF PLATE

150mmØ NIPPLE

0.15

300mm

150mmØ COUPLING w/ WELDED SS SCREEN INSIDE

DETAIL OF AIR VENT

OVERFLOW PIPE

G.I. TANK SHELL

OVERFLOW PIPE - SHELL CONN.

Title

Department of the Interior and Local Government

Office of Project Development Services

ELEVATED STEEL WATER RESERVOIR

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. ESR21-05 ELEV. STEEL RESERVOIR

1

COMPACTED SELECTED NATIVE MATERIAL BACKFILL

2

COMPACTED SELECTED NATIVE MATERIAL BACKFILL

VARIABLE

Trench Width "W"

1

COMPACTED SELECTED NATIVE MATERIAL BACKFILL

3

APPROVED SAND BEDDING AND BACKFILL HANDPLACED AND COMPACTED

0.15

0.75

Trench Width "W"

NORMAL INSTALLATION WHERE SAND BEDDING/ BACKFILL NOT REQUIRED

IN ROCK OR WHEN ORDERED BY ENGINEER

NOTES: 1.

ALL DIMENSIONS ARE IN METERS UNLESS OTHERWISE SHOWN.

2.

SPACE SHALL BE PROVIDED FOR PIPE JOINTS TO PREVENT BRIDGING

TABLE OF TRENCH DIMENSION (IN METERS) inch

3" & under

4"

6"

8"

10"

12"

100

150

200

250

300

PIPE DIAMETER mm

75mm & under

MINIMUM " W "

0.20

0.40

0.45

0.50

0.55

0.60

MAXIMUM " W "

0.30

0.70

0.75

0.80

0.85

0.90

Title

Department of the Interior and Local Government

Office of Project Development Services

TRENCHING, EXCAVATION & BACKFILLING

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. WD21-01 WATER DISTRIBUTION

0.60

HINGED CAST IRON FRAME & COVER MARKED " W ".

W

VALVE BOX COVER 0.80 0.10 BRONZE GATE VALVE MALE ADAPTOR

0.10

0.60

PE PIPE

PLAN 50mm THK (min) CONCRETE COVER

HINGED & CAST IRON FRAME & COVER MARKED " W ".

0.75

GROUND LEVEL

4" LOAD BEARING CHB BRONZE GATE VALVE MALE ADAPTOR PE PIPE

NOTES:

SECTION

1.

ALL DIMENSIONS ARE IN METERS UNLESS OTHERWISE SHOWN.

2.

VALVES BOX SHALL HAVE A MINIMUM COVER OF 50MM w/ 10mm REINFORCEMENT @ 150mm O.C. BOTHWAYS.

3.

APPROVED COMPRESSION MALE ADAPTOR IS TO USED TO CONNECT GATE VALVE AND PE PIPES.

Title

VALVE BOX & BRONZE GATE VALVES INSTALLATION 2 1/2" Dia. and SMALLER

Department of the Interior and Local Government

Office of Project Development Services Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. WD21-02 WATER DISTRIBUTION

W

W

150mm 0.90m Ø CONCRETE PAD IN GRAVEL OR DIRT ROADWAYS & OUTSIDE OF TRAVELLED ROADWAYS

PLAN

0.50

32mm

0.15

GROUND LEVEL HINGED CAST IRON FRAME & COVER MARKED " W "

CRUSHED ROCK 0.10m (max) AROUND & ABOVE VALVE

150mm CL 150 PVC WATER PIPE GATE VALVE WATER MAIN

150mm CL 150 PVC WATER PIPE

VARIABLE 150mm (min)

0.75m (min)

VALVE STEM EXTENSION. WHERE DEPTH OF OPERATING NUT EXCEED 1.50m

VARIABLE

50mm SQUARE OPERATING NUT

125mm CL 150 PVC WATER PIPE

12mm REBAR AROUND VALVE CONCRETE BLOCK FOR 200mm VALVE & LARGER

UNDISTURBED EARTH

SECTION

DETAILS

NOTES: 1.

ALL DIMENSIONS ARE IN METERS UNLESS OTHERWISE SHOWN.

2.

VALVES SHALL HAVE A MINIMUM COVER OF 0.30M MEASURED TO THE TOP OF THE OPERATING NUT.

3.

VALVES SHALL BE INSTALLED ON EXTENSION OF PROPERTY LINES EXCEPT WHERE OTHERWISE SHOWN OR SPECIFIED.

4.

USE FLANGED END GATE VALVES ON STEEL AND PVC PIPELINE INSTALLATION

5.

CAST IRON OR STEEL COVER SHALL BE ADEQUATELY DESIGNED TO CARRY TRAFFIC LOADS

6.

CONCRETE BLOCKS MAYBE OMITTED ON WELDED STEEL PIPELINES AT OPTION OF CONTRACTOR.

Title

Department of the Interior and Local Government

Office of Project Development Services

INSTALLATION OF BURIED GATE VALVE 300mm and SMALLER

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. WD21-03 WATER DISTRIBUTION

4-12Ø Ring Bars w/ 12-10Ø Ties @150 o.c.

0.30 CONCRETE PAVED SURFACE

0.15

UNPAVED / ASPHALT SURFACE

0.15

0.90 x 0.90 CONCRETE PAD

18-12mm TIES 2-12mm RING BARS

0.15 - 0.20

VARIES

SLIDE TYPE VALVE BOX (See Detail " 1 ")

GATE VALVE

NOTES: 1.

IN CASE WHERE THE WIDTH OF PAVEMENT RESTORATION IS LESS THAN 900mm A RECTANGULAR PAD MAY BE PROVIDED WITH WIDTH EQUAL TO THE WIDTH OF PAVEMENT RESTORATION.

Title

Department of the Interior and Local Government

Office of Project Development Services

INSTALLATION OF BURIED GATE VALVE (Maynilad Standard Drawing)

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. WD21-04A WATER DISTRIBUTION

PROVIDE DEBRIS SHIELD (See Detail) 16mmØ STAINLESS PIN

PIPE

GATE VALVE

COVER 750 750 750 900 900 900 1200

50 75 100 150 200 250 300

A

B

500 400 600 500 700 600 900 700 900 800 1000 900 1100 1000

C

D

200 200 200 250 250 250 300

150 150 150 200 200 200 200

12mm D NOTES: 1.

CAST IRON CONFORMING TO ASTM A-48 CLASS 30 C.

2.

STAINLESS STEEL CONFORMING TO ASTM 276 CLASS 304

0.20 (max)

"B"

0.10

0.50

Max. Adjustment " A "

SIZE OF

0.40

0.125

0.20

DIMENSIONS (mm)

0.50

0.50

"C"

SECTIONAL ELEVATION SEE LOCK ASSEMBLY DETAIL

W

SEE HINGE DETAIL

TOP VIEW OF FRAME

Title

Department of the Interior and Local Government

Office of Project Development Services

INSTALLATION OF BURIED GATE VALVE (Maynilad Standard Drawing)

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. WD21-04B WATER DISTRIBUTION

60mm

50mm

STAINLESS STEEL HINGE PIN

20

14

14

HINGE DETAIL

BRASS WASHER

ECCENTRIC LOCKING PIECE S.S. CUT WASHER HEXAGON NUT

LOCK ASSEMBLY Title

Department of the Interior and Local Government

Office of Project Development Services

INSTALLATION OF BURIED GATE VALVE (Maynilad Standard Drawing)

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. WD21-04C WATER DISTRIBUTION

L-SHAPED PIPE TO BE CONNECTED ONLY WHEN FLUSHING

0.60

GATE VALVE

0.60

PLASTIC PIPE

ADAPTOR G. I. PIPE

PLAN

L-SHAPED PIPE TO BE CONNECTED ONLY WHEN FLUSHING

HANDLE CONCRETE COVER

GROUND LEVEL

0.75

4" CHB PLUG-IN WHEN NOT IN USE

GATE VALVE

G. I. COUPLING 10mm ANCHOR BAR

GRAVEL PLASTIC PIPE ADAPTOR

G.I. PIPE

SECTION NOTES: 1.

ALL DIMENSIONS ARE IN METERS UNLESS OTHERWISE SHOWN.

2.

SIZE OF FLUSH PIPE TO MATCH SIZE OF MAIN LINE.

3.

G. I. PIPES SHOULD BE SCHEDULE 40

Title

Department of the Interior and Local Government

Office of Project Development Services

END-OF-LINE BLOW-OFF ASSEMBLY

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. WD21-05 WATER DISTRIBUTION

b 600 L-SHAPED PIPE TO BE CONNECTED ONLY WHEN FLUSHING GATE VALVE MAIN LINE

0.60

a

ADAPTOR

PLAN

HANDLE

CONCRETE COVER

L-SHAPED PIPE TO BE CONNECTED ONLY WHEN FLUSHING

HANDLE

PLUG-IN WHEN NOT IN USE

GROUND LEVEL

4" CHB

0.75

10mm ANCHOR BAR

GATE VALVE

MAIN LINE GRAVEL

GRAVEL

ADAPTOR MAIN LINE

SECTION " b "

SECTION " a " NOTES: 1.

ALL DIMENSIONS ARE IN METERS UNLESS OTHERWISE SHOWN.

2.

SIZE OF FLUSH PIPE TO MATCH SIZE OF MAIN LINE.

3.

G. I. PIPES SHOULD BE SCHEDULE 40

Title

Department of the Interior and Local Government

Office of Project Development Services

IN-LINE BLOW-OFF ASSEMBLY

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. WD21-06 WATER DISTRIBUTION

L-SHAPED PIPE TO BE CONNECTED ONLY WHEN FLUSHING

G. I. PLUG G. I. COUPLING

0.40

CONCRETE (0.60 x 0.60)

GATE VALVE

STANDARD VALVE BOX G. I. PIPE COMPANION FLANGE

FABRICATED 90° ELBOW

SECTION TEE WITH FLANGED BRANCH

NOTES: 1.

ALL DIMENSIONS ARE IN METERS UNLESS OTHERWISE SHOWN.

2.

SIZE OF FLUSH PIPE TO MATCH SIZE OF MAIN LINE.

3.

G. I. PIPES SHOULD BE SCHEDULE 40

STANDARD VALVE BOX

C. I. GATE VALVE C. I. COMPANION FLANGE G. I. PIPE

C. I. COMPANION FLANGE C. I. FLANGE ADAPTOR uPVC MAINLINE

C. I. TEE

uPVC MAINLINE

C. I. FLANGE ADAPTOR

PLAN Title

Department of the Interior and Local Government

Office of Project Development Services

IN-LINE BLOW-OFF ASSEMBLY (100mm and Above Mainline)

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. WD21-07 WATER DISTRIBUTION

EXPOSED MAIN LINE

GATE VALVE

FLUSHING PIPE

PLAN EXPOSED MAIN LINE

FLUSHING PIPE

EXPOSED MAIN LINE

NOTES:

ELEVATION

1.

G. I. PIPES SHOULD BE SCHEDULE 40.

2.

LENGTH OF FLUSHING PIPE IS TO BE APPROVED BY THE ENGINEER.

3.

PROVIDE SITE DRAINAGE TO AVOID STANDING WATER.

4.

THIS ARRANGEMENT CAN BE DONE ONLY WITH THE APPROVAL OF THE ENGINEER.

Title

Department of the Interior and Local Government

Office of Project Development Services

IN-LINE BLOW-OFF ASSEMBLY (for exposed G.I. Pipes)

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. WD21-08 WATER DISTRIBUTION

3.00m (max)

GROUND LEVEL

CAST IRON MECHANICAL ADAPTOR

w.s. PVC / HDPE PIPE (90mmØ & Above)

G.I. PIPE SCH. 40

3.00m (max)

GROUND LEVEL

C.I.

MECHANICAL ELBOW

w.s. G.I. PIPE SCH. 40

PVC / HDPE PIPE (90mmØ & Above)

3.00m (max)

GROUND LEVEL

C.I.

MECHANICAL ELBOW

0.60 (min)

w.s.

PVC / HDPE PIPE (90mmØ & Above)

Title

PVC / HDPE PIPE (90mmØ & Above)

Department of the Interior and Local Government

Office of Project Development Services

PIPE CROSSING CANAL / CREEK

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. WD21-09 WATER DISTRIBUTION

10.00 (max)

G.I. PIPE SCH. 40

1.50m

SEE DETAIL " A "

max flood level

0.15 x 0.15 CONCRETE SUPPORT PVC / HDPE PIPE (90mmØ & Above)

SECTION

G.I. PIPE SCH. 40

0.30m (min)

4mm x 25mm STRAP ANCHOR BOLT

1.00m

4 - 12mm VERT BARS w/ 10mm TIES @ 200mm o.c.

0.40m

DETAIL " A "

Title

Department of the Interior and Local Government

Office of Project Development Services

PIPE CROSSING CANAL / CREEK (Maximum 10.00 Meters)

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. WD21-10 WATER DISTRIBUTION

NO JOINT / FITTING 1.00M

0.60M (min)

1.00M

ROAD FINISHED GRADE PLASTIC PIPE

0.15

COMPACTED SAND

CULVERT

TOP OF CULVERT ≥ 0.75M BELOW GRADE

0.60M (min)

ROAD FINISHED GRADE

PLASTIC PIPE

COMPACTED SAND CULVERT

TOP OF CULVERT ≤ 0.75M BELOW GRADE

G. I. PIPE

0.60M (min)

ROAD FINISHED GRADE

PLASTIC PIPE

COMPACTED SAND CULVERT

TOP OF CULVERT ≤ 0.75M BELOW GRADE Title

Department of the Interior and Local Government

Office of Project Development Services

PIPE CROSSING CULVERT

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. WD21-11 WATER DISTRIBUTION

See Table for Area

See T for able Are a

45 deg ELBOW TEE

REDUCER

e bl Ta a e Are Se for

See T for able Are a

90deg ELBOW or BEND

TABLE OF MINIMUM THRUST BLOCK BEARING AREAS IN SQUARE METERS FOR PIPE SIZES 75mmTO 600mm Ø PIPE SIZE (mm)

OFFSETS AND BENDS NOTES: 1. 2. 3. 4. 5. 6. 7.

POUR ALL THRUST BLOCKS IN UNDISTURBED SOIL. ABOVE AREAS BASED ON AN ASSUMED SOIL BEARING PRESSURE OF 6kPa (2000psf.) REDUCE OR INCREASE AREAS PROPORTIONATELY TO SUIT ACTUAL FIELD CONDITIONS UPON APPROVAL OF ENGINEER. CONCRETE FOR THRUST BLOCK SHALL BE 13.8M Pa (2000psi.) ALL CONCRETE SHALL BE POURED TO AVOID INTERFERENCE WITH JOINTS. WHERE PIPE CONNECTS TO A FITTING IN A STEEL PIPELINE, THE STEEL PIPELINE SHALL BE BLOCKED AS SHOWN HEREON. BEARING AREAS BASED ON THE INTERNAL PRESSURE OF 106M (150PSI)

Title

TEE & DEAD END

90° BEND

45° BEND

22 1/2° BEND

75 ( 3")

0.05

0.07

0.04

0.02

100 ( 4")

0.09

0.12

0.07

0.04

150 ( 6")

0.20

0.28

0.15

0.08

200 ( 8")

0.35

0.50

0.27

0.14 0.21

250 ( 10")

0.55

0.77

0.42

300 ( 12")

0.79

0.79

0.79

0.79

350 ( 14")

1.07

1.52

0.82

0.42

400 ( 16")

1.40

1.98

1.07

0.55

450 ( 18")

1.77

2.51

1.36

0.69

500 ( 20") 2.19

3.10

1.68

0.85

3.15

4.46

2.42

1.23

600 ( 24")

Department of the Interior and Local Government

Office of Project Development Services

THRUST BLOCKS

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. WD21-12A WATER DISTRIBUTION

Trench Width "W"

GROUND LEVEL

le) iab var Ø( C

CONCRETE THRUST BLOCKS

B n) i 0m (0.3

POUR AGAINTS UNDISTURBED SOIL

A

BEARING AREA = A x B

SECTION

TABLE OF MINIMUM THRUST BLOCK DIMENSIONS FOR PIPE SIZES 75MM TO 600 MM Ø PIPE SIZES

"C"

THRUST BLOCK BEARING AREAS IN SQ. METERS

MM (IN)

METERS

90° BEND

45° BEND

75(3") & 100(4")

0.25

0.14

0.12

*

150 (6")

0.25

0.31

0.17

0.12

22 1/2° BEND

200 (8")

0.25

0.85

0.30

0.15

250 (10")

0.25

0.25

0.46

0.24

300 (12")

0.30

1.23

0.66

0.34

350 (14")

0.30

1.67

0.90

0.46

0.30

2.18

1.18

0.60

0.35

2.76

1.49

0.76 0.94 1.35

400 (16") 450 (18") 500 (20")

0.35

3.41

1.84

600 (24")

0.40

4.91

2.65

* THRUST BLOCK NOT REQUIRED

NOTES: 1. ABOVE AREAS BASED ON AN ASSUMED SOIL BEARING PRESSURE 96kPa (2000psf.) 2. REDUCE OR INCREASE AREAS PROPORTIONATELY TO SUIT ACTUAL FIELD CONDITIONS UPON APPROVAL OF ENGINEER. 3. CONCRETE FOR THRUST BLOCK SHALL BE 13.8 MPa (2000 psf) 4. THRUST BLOCKS NOT REQUIRED ON STEEL PIPELINES WITH WELDED OR FLANGED JOINTS OR ON SOLVENT WELDED PVC PIPE. 5. WHERE PIPE CONNECTS TO A FITTING AN A STEEL PIPE LINE THE STEEL PIPE LINE SHALL BE BLOCKED AS SHOWN HEREON. 6. BEARING AREAS BASED ON INTERNAL PRESSURE OR 106MM (150psf)

Title

Department of the Interior and Local Government

Office of Project Development Services

THRUST BLOCKS

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. WD21-12B WATER DISTRIBUTION

1.00M 50mm AIR VENT

0.10

5mm ROOF PLATE

LADDER

INLET PIPE

5mm SHELL PLATE

3.00M

OVERFLOW PIPE

SUPPLY PIPE

7mm BOTTOM PLATE

EARTHMOUND

ELEVATION

Title

Department of the Interior and Local Government

Office of Project Development Services

PRESSURE BREAKER TANK

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. WD21-13 WATER DISTRIBUTION

ROADWAY (Including R.O.W)

0.75 (min)

1.00 (min)

SEE END DETAIL

PVC/HDPE PIPELINE

G.I. PIPE CASING

WITH G.I. PIPE CASING

ROADWAY (Including R.O.W)

1.00

0.75 (min)

1.00 (min)

PVC/HDPE PIPELINE

PVC PIPE CASING

WITH PVC PIPE CASING PIPELINE

NOTES:

WOODEN CLOSURE

1.

2. PIPE CASING PVC/HDPE PIPELINE

END DETAIL 3.

Title

FOR PVC PIPE, USE PROPER FITTINGS FOR GRADE NEGOTIATIONS, FOR PE PIPE, NO FITTINGS NECESSARY PVC CASING MAYBE JOINED BY RUBBER RING, G.I. PIPE MAYBE JOINED BY WELDING OR THREADED COUPLING PVC PIPE SHALL BE SDR 18 OF CLASS 12.5.

Department of the Interior and Local Government

Office of Project Development Services

INSTALLATION OF PIPE IN ROAD CROSSINGS

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. WD21-14 WATER DISTRIBUTION

NOTES : 1. POLYETHYLENE PIPE

2. 3.

COMPRESSION FEMALE ADAPTOR CORPORATION STOP

4. SADDLE CLAMP

5.

PVC PIPE

6.

7. 8. POLYETHYLENE PIPE

9. COMPRESSION FEMALE ADAPTOR

ALL DIMENSIONS ARE IN METERS EXCEPT OTHERWISE SHOWN. PRESSURE TEST PRIOR TO BACKFILLING. SERVICE LINE TO LAID IN CONSTANT SLOPE UP FROM WATER MAIN TO THE METER NO DIPS OR POCKET IN THE LINE WILL BE PERMITTED THE SERVICE CONNECTION WILL BE LOCATED AS DETERMINED BY THE WATER SERVICE PROVIDER 100mm (4") MINIMUM SIZE MAIN TO BE TAPPED. USE COPPER TO I.P. THREAD CORPORATION STOP IN LIEU OF COPPER TO I.P. THREAD COUPLING FOR WET TAP. MINIMUM TUBING TRENCH WIDTH SHALL BE 0.15M. ALL G.I. PIPE AND FITTING SHALL BE SCHEDULE 40 INSTALL TEE IN LIEU OF SADDLE FOR 25mm PIPE.

CORPORATION STOP

SADDLE CLAMP

0.60m

WATER METER

G.I. PIPE

BRASS STOP COCK or GATE VALVE

POLYETHYLENE PIPE

0.40m

GROUND LEVEL

G.I. PIPE SCH 40

COMPRESSION FEMALE ADAPTOR CORPORATION STOP G.I. ELBOW POLYETHYLENE PIPE

STEEL PIPE

Title

Department of the Interior and Local Government

Office of Project Development Services

SERVICE CONNECTION

Drawn by: Engr. C. O. De Ocampo September 2021

Reviewed by:

Sheet No. WD21-15 WATER DISTRIBUTION

W

PERSPECTIVE SCALE

N

S

NTS

E 3

2

TO BRGY. POBLACION I

SITE

LOT PLAN SCALE

NTS

ADMIN BUILDING PROPOSED TOILET FACILITY

1

MUNICIPAL HALL

4

TO POBLACION III

LOCATION MAP SCALE

NTS

Title

PUBLIC TOILET FACILITY (PERSPECTIVE)

Drawn by: OPDS-UPMO|WSS

Reviewed by:

Sheet No. PTF21-01 ARCHITECTURAL PLANS-1

A

B

C

7 3.5

3.5 1.7

1.7

LS

2

CS

1

3.8

1 UP

FD

1.7

HANDWASHING FACILITY

FD WC FD

WC

WC

FD

FD

RAMP DOWN

UNGLAZED TILES FLOOR FINISH

LAV

WC

LAV

FD

W.U

WC

WC

1

STAINLESS STEEL RAILINGS FOR PWD

1.2

UP

PUBLIC TOILET FACILITY FLOOR PLAN SCALE

1:80

A

B

C

ROOF APEX LINE ROOF BEAM

REPUBLIC OF THE PHILIPPINES REGION MUNICIPALITY OF

FEMALE

LOCAL GOVERNMENT SUPPORT FUND FY

0.8

2.7

3.5

MALE

GROUND FLOOR FINISHED LINE FINISHED GROUND LINE

FRONT VIEW SCALE

1:80

Title

PUBLIC TOILET FACILITY (PLAN AND ELEVATION)

Drawn by: OPDS-UPMO|WSS

Reviewed by:

Sheet No. PTF21-02 ARCHITECTURAL PLANS-2

B

C

A

ROOF APEX LINE

3.5

2.7

ROOF BEAM

GROUND FLOOR FINISHED LINE FINISHED GROUND LINE

REAR VIEW SCALE

1:80

2

1 ROOF APEX LINE

0.9

2.7

0.3

3.5

ROOF BEAM

GROUND FLOOR FINISHED LINE SLOPE OF 1:12

FINISHED GROUND LINE

2.8

LEFT SIDE VIEW SCALE

1:80

Title

PUBLIC TOILET FACILITY (ELEVATIONS)

Drawn by: OPDS-UPMO|WSS

Reviewed by:

Sheet No. PTF21-03 ARCHITECTURAL PLANS-3

2

1 ROOF APEX LINE

NOTE: LGU MAY OPT TO ADD PROVISION FOR ECCD IN TERMS OF HEIGHT OF THE LAVATORY/ HANDWASHING FACILITY

0.8

0.9

2.7

3.5

ROOF BEAM

GROUND FLOOR FINISHED LINE FINISHED GROUND LINE

RIGHT SIDE VIEW SCALE

1:80

2

1

CEILING FINISH LINE TOP OF WALL PARTITION TILE WALL FINISHED

WALL MOUNTED URINAL

0.9

0.48

1.5

2.1

DIA.50mmSTAINLESS STEEL BAR

GROUND FLOOR FINISHED LINE FINISHED GROUND LINE

CROSS SECTION SCALE

1:80

Title

PUBLIC TOILET FACILITY (ELEVATIONS AND SECTION)

Drawn by: OPDS-UPMO|WSS

Reviewed by:

Sheet No. PTF21-04 ARCHITECTURAL PLANS-4

A

B

C

ROOF APEX LINE ROOF BEAM

TILE WALL FINISHED

0.8

0.9

0.8

1.5

DIA.50mmSTAINLESS STEEL BAR

GROUND FLOOR FINISHED LINE FINISHED GROUND LINE

LONGITUDINAL SECTION SCALE

0.86

1.78

1.6

C 1.88

0.88

FL

FL

0.84

2

0.71

1.4

1.03

0.53

1

B

HANDWASHING FACILITY

A

1:80

2.84

2.91

REFLECTED CEILING PLAN SCALE

1:80

Title

PUBLIC TOILET FACILITY (SECTION AND CEILING PLAN)

Drawn by: OPDS-UPMO|WSS

Reviewed by:

Sheet No. PTF21-05 ARCHITECTURAL PLANS-5

TAPPING POINT GV

FD

UP

HANDWASHING FACILITY

WC

WC

FD

WC FD

FD

RAMP DOWN

UNGLAZED TILES FLOOR FINISH

LAV

WC

LAV

FD

W.U

WC

CWL

FD

FROM MAIN WATER LINE

CWL

WC

GV

STAINLESS STEEL RAILINGS FOR PWD

UP

COLD WATERLINE LAYOUT SCALE

1:80

TO SEPTIC TANK/ EXISTING STP C.O VP

WC

TO MAIN SEWER

FD

UP

WC

WC

FD

WC FD

FD

RAMP DOWN

UNGLAZED TILES FLOOR FINISH

LAV

WC

LAV

FD

W.U

VP

WC

VSTR

VSTR

HANDWASHING FACILITY

C.O

FD

VP

STAINLESS STEEL RAILINGS FOR PWD

UP

SEWERLINE LAYOUT SCALE

1:80

Title

PUBLIC TOILET FACILITY (SANITARY/PLUMBING PLANS)

Drawn by: OPDS-UPMO|WSS

Reviewed by:

Sheet No. PTF21-06 PLUMBING PLANS-1

DS

DS

DS

TAPPING POINT

DRUM/TANK

FD WC FD

WC FD

UP

FD FD

WC

LAV

LAV

WC FD

RAMP DOWN

UNGLAZED TILES FLOOR FINISH

HANDWASHING FACILITY

FROM MAIN WATER LINE

W.U

WC

GV

WC

GV

STAINLESS STEEL RAILINGS FOR PWD

UP INLET

OUTLET TO TANK

FILTER ELEMENT

STORM WATERLINE LAYOUT SCALE

NTS

FILETERED SEDIMENTS/WASTE FLASH OUT TUBE DETAIL SCALE

NTS

FLASH OUT TUBE DOWNSPOUT

OVERFLOW

PIPE SYSTEM

280 L CONTAINER DRUM

NOTE: HEIGHT OF THE DRUM VARIES DEPENDS ON THE HEIGHT/ELEVATION OF THE STRUCTURE/FACILITY TO OBTAIN THE ALLOWABLE PRESSURE ON

CONNECTION TO FIXTURES/ HANDWASHING FAC.

FAUCETS/TAPS

COLUMN FOOTING/ PEDESTAL

RAINWATER FACILITY DETAILS SCALE

NTS

Title

PUBLIC TOILET FACILITY (SANITARY AND RAINWATER)

Drawn by: OPDS-UPMO|WSS

Reviewed by:

Sheet No. PTF21-07 PLUMBING PLANS-2

GENERAL NOTES AND SPECIFICATIONS: 1.

2.

3. 4. 5. 6. 7. 8.

9. 10. 11. 12. 13.

14. 15.

IT IS NOT INTENDED THAT THE DRAWINGS SHALL SHOW EVERY PIPE FITTING, VALVE AND APPURTENANCE. ALL SUCH ITEMS WHETHER SPECIFICALLY MENTIONED OR NOT, OR INDICATED ON THE DRAWINGS SHALL BE FURNISHED AND INSTALLED IF NECESSARY TO COMPLETE THE SYSTEM TO THE SATISFACTION OF THE OWNER. ALL PLUMBING WORKS SHALL BE INSTALLED IN ACCORDANCE WITH THE PROVISIONOF THE NATIONAL PLUMBING CODE OF THE PHILIPPINES, THE REQUIREMENTS OF THE LOCAL PLUMBING INSPECTION OFFICE, PERTINENT PROVISIONS OF THE UNIFORM BUILDING CODE AND THE NATIONAL BUILDING CODE OF THE PHILIPPINES. COORDINATE THE DRAWING WITH OTHER RELATED DRAWINGS AND SPECIFICATION. THE ARCHITECT/ ENGINEER SHALL BE NOTIFIED IMMEDIATELY OF ANY DESCREPANCY FOUND THEREIN. ALL PIPES SHALL BE INSTALLED AS INDICATED ON PLANS, ANY STORM RELOCATIONS REQUIRED FOR PROPER EXECUTION OF OTHER TRADE SHALL BE WITH PRIOR APPROVAL OF THE ARCHITECT OR ENGINEER. PROPOSED SANITARY UTILITIES SHALL CONFORM TO THE ACTUAL LOCATION, DEPTH AND INVERT ELEVATION OF ALL EXISTING PIPES AND STRUCTURES AS VERIFIED BY THE CONTRACTOR. ALL SLOPES FOR HORIZONTAL DRAINAGE SHALL MAINTAIN 1% UNLESS OTHERWISE SPECIFIED. SIZE OF WATER SUPPLY PIPES TO FIXTURES SHALL BE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. THE CONTRACTOR SHALL VERIFY ALL EXISTING UTILITIES AT THE SITE, COORDINATE THE WORKS WITH THE SEWER LINE EFFLUENT DISPOSAL POINTAND WATER LINE SERVICE CONNECTING POINT, UNLESS OTHERWISE SPECIFIED. ALL FIXTURES SHALL BE VERIFIED, UNLESS OTHERWISE NOTED. THE INVERT OF THE INLET PIPE OF A SEPTIC TANK SHALL BE AT A LEVEL NOT LESS THAN 50.8mm (2") ABOVE THE INVERT OF THE OUTLET PIPE. NO SEPTIC TANK SHALL BE CONSTRUCTED UNDER THE BUILDING IN ACCORDANCE WITH THE NATIONAL PLUMBING CODE OF THE PHILIPPINES. ALL PIPE SIZE ARE IN MILLIMETERS/INCHES AND ALL DIMENSIONS ARE IN METERS UNLESS OTHERWISE SPECIFIED. MINIMUM SEWAGE PIPE SIZE SHALL BE AS FOLLOWS: SOIL PIPE WASTE PIPE VENT PIPES DOWNSPOUT ALL PLUMBING INSTALLATION INCLUDED HEREIN SHALL BE UNDER THE DIRECT SUPERVISION OF A DULY REGISTERED AND LICENSED MASTER PLUMBER/ SANITARY ENGINEER. THE DESIGNED/CONSTRUCTED SEPTIC TANK MUST BE DESLUDGE ONCE EVERY 3-5 YEARS.

PLUMBING LEGEND: GATE VALVE

STORM DRAIN PIPE

CHECK VALVE M

VSTR

WATER METER COLD WATER LINE WASTE PIPE SOIL PIPE

CB

DS

VENT STACK THRU ROOF CATCH BASIN

DOWNSPOUT

Title

PUBLIC TOILET FACILITY (GENERAL NOTES)

Drawn by: OPDS-UPMO|WSS

Reviewed by:

Sheet No. PTF21-08 PLUMBING PLANS-3

L

2 3

T

L

T

INLET PIPE

W

T

4

1 3

T

L

MANHOLE .5mx.5m

T

MANHOLE .5mx.5m

4

TOP BARS

OUTLET PIPE

PLAN TOP BARS 4

FREEBOARD

t RC WALL PLUS WATER PROOFING WITH RSB BOTHWAYS O.C

OUTLET PIPE

MANHOLE AIRSPACE

300

AIRSPACE

51

H

51

MANHOLE

h

INLET COMPARTMENT SLOPE 1:10

SLOPE 1:10

T

4 SANITARY TEE WITH WIRE MESH ON TOP

SECONDARY COMPARTMENT

RC SLAB WITH RSB BOTHWAYS O.C

WELL COMPACTED GRAVEL FILL

SECTION

SEPTIC TANK DETAILS SCALE

NTS

SEPTIC TANK GENERAL NOTES: 1. 2.

3. 4. 5.

MINIMUM DIMENSION (INSIDE) OF SEPTIC TANK (L=1.5m,W=0.9m,H=1.5m) VOLUME OF THE FIRST COMPARTMENT SHALL BE 23 VOLUME OF THE TOTAL VOLUME OF TANK MINIMUM DIMENSION OF MANHOLE COVER (.5mx.5m) MINIMUM DIMENSION OF INLET PIPE (4in.)

LEVEL EXTENDS TO WITHIN 12 FT (3658 MM) OR LESS OF THE GROUND SURFACE OR WHERE THE UPPER SOIL IS POROUS, AND THE UNDERLYING STRATUM IS ROCK OR

FOR DETAILED: SEE DOH AO 2019-0047 SEC.VI.A.DESIGN CONSIDERATIONS SEE IRR OF PD856 CH.17 SEC.4 DILG MEMORANDUM CIRCULAR 2019-62

Title

PUBLIC TOILET FACILITY (SEPTIC TANK)

Drawn by: OPDS-UPMO|WSS

Reviewed by:

Sheet No. PTF21-09 PLUMBING PLANS-4

OUTLET TO TANK

2

1

INLET

NOTE: ELEVATION OF THE TANK VARIES DEPENDS ON THE HEIGHT/ELEVATION OF THE STRUCTURE/FACILITY TO OBTAIN THE ALLOWABLE PRESSURE ON FAUCETS/TAPS

FILTER ELEMENT

FILETERED SEDIMENTS/WASTE

ROOF APEX LINE

FLASH OUT TUBE ROOF BEAM FLASH OUT TUBE

PIPE SUPPORT/ HANGER

CLEANOUT

0.9

Assistance

2.7

0.3

to

TAP STAND DRAIN PIPE

3.5

2% SLOPE MANHOLE

PLASTIC SCREEN OVERFLOW PIPE

GROUND FLOOR FINISHED LINE SLOPE OF 1:12

BUILDING CONNECTION PEDESTAL SUPPORT

FINISHED GROUND LINE

2.8

LEFT SIDE VIEW SCALE

1:80

B

C

A

ROOF APEX LINE ROOF BEAM DOWNSPOUT

3-1.2x1.2x1M PLASTIC CONTAINER

OVERFLOW

3.5

HEIGHT OF THE DRUM/CONTAINER VARIES DEPENDS ON THE HEIGHT/ELEVATION OF THE STRUCTURE/FACILITY TO OBTAIN THE ALLOWABLE PRESSURE ON FAUCETS/TAPS

2.7

INLET PIPE

NOTE:

BUILDING CONNECTION 1-75mmx75mmx6mm ANGLE BAR FAUCET

GROUND FLOOR FINISHED LINE

DRAIN

FINISHED GROUND LINE

CONCRETE PEDESTAL/FOOTING

REAR VIEW SCALE

1:80

Title

PUBLIC TOILET FACILITY (RAINWATER CATCHMENT FACILITY)

Drawn by: OPDS-UPMO|WSS

Reviewed by:

Sheet No. PTF21-10 RAINWATER FACILITY

References for Sanitation Facilities Presidential Decree No. 856 Code on Sanitation of the Philippines – Ch. 6 School Sanitation and Health Services. Section 6. Sanitary Facilities Requirements Presidential Decree No. 856 Code on Sanitation of the Philippines – Ch. 6 School Sanitation and Health Services.Section6.1.13 Toilet Structure Requirements Presidential Decree No. 856 Code on Sanitation of the Philippines – Ch. 6 School Sanitation and Health Services.Section 6.2 Handwashing Facilities Presidential Decree No. 856 Code on Sanitation of the Philippines – Ch. 6 School Sanitation and Health Services.Section 9. Specific Requirements for DayCare Service, Pre-school Service and Children’s Institutions Presidential Decree No. 856 Code on Sanitation of the Philippines – Ch. 17 Sewage Collection and Disposal, Excreta Disposal and Drainage. Section 2. Definition of Terms Presidential Decree No. 856 Code on Sanitation of the Philippines – Ch. 17 Sewage Collection Disposal, Excreta Disposal and Drainage. Section 3. Individual Excreta and Sewage Disposal

and

Presidential Decree No. 856 Code on Sanitation of the Philippines – Ch. 17 Sewage Collection Disposal, Excreta Disposal and Drainage. Section 4. Design and Construction of Septic Tanks, Leaching Tile Field and House Sewers

and

Presidential Decree No. 856 Code on Sanitation of the Philippines – Ch. 17 Sewage Collection and Disposal, Excreta Disposal and Drainage. Annexes, Table 1. Quantities of Sewage Flow (depends on type of establishment) Revised National Plumbing Code of the Philippines – Article XV Septic Tank Construction Revised National Plumbing Code of the Philippines – Table 13-1 Location of Sewage Disposal System Presidential Decree No. 1096 National Building Code of the Philippines – Rule II. Minimum Requirements for Accessibility Presidential Decree No. 1096 National Building Code of the Philippines – Section G. Design of Public Buildings/Structures Presidential Decree No. 1096 National Building Code of the Philippines – Revised Implementing Rules and Regulations, Section 805 (Ceiling Heights), Section 806 (Sizes and Dimension Of Rooms), Section 807 (Air Space Requirements), Section 808 (Window Openings) Department of Health (DOH) Administrative Order 2019-0047.(“National Standard on the Design, Construction, Operation And Maintenance Of Septic Tank Systems”) DILG MC 2019-062 Dated 22 April 2019 (“Policy Guidelines on Sewage Treatment and Sewage Management System”) Uniform Plumbing Code 2018 Edition Appendix H. Sec. 101.4 Septic Tank and Disposal Field Systems