Katalog IC10 2022 EN - Układy rozruchowe do szaf sterowniczych Flipbook PDF

Katalog IC10 2022 EN - Układy rozruchowe do szaf sterowniczych
Author:  S

90 downloads 952 Views 21MB Size

Recommend Stories


Technisch Katalog
Válvulas Hidráulicas y Neumáticas para Camión Hydraulic and Pneumatic Valves for Trucks Distributeurs Hydrauliques et Pneumatiques pour Véhicules Indu

KATALOG ALARMNE OPREME
KATALOG ALARMNE OPREME 24.10.2014 24.10.2014. 1 ALARMNA OPREMA - BEŽIČNO – KOMPLETI Šifra Kataloški broj 75 Cijena VPC kn 1.599,00 Šifra Katal

FABULACIONES EN AZUL PDF
Get Instant Access to eBook Fabulaciones En Azul PDF at Our Huge Library FABULACIONES EN AZUL PDF ==> Download: FABULACIONES EN AZUL PDF FABULACIONES

Denne katalog er hentet fra
Telefon: 63836000 Mail: [email protected] REVISED 30.05.2016 Denne katalog er hentet fra INDICE - Table of contains MOTORES COMPLETOS BASES DE MO

Story Transcript

8

© Siemens 2022

Load feeders and motor starters for use in the control cabinet

Price groups PG 14O, 255, 41B, 41D, 41E, 41L, 42C, 42D, 42F, 42G

8/4 8/21 8/29 8/33 8/39 8/44 8/55

Introduction SIRIUS 3RA2 load feeders General data 3RA21 direct-on-line starters - For standard mounting rail or screw fixing - For 60 mm busbars 3RA22 reversing starters - For standard mounting rail or screw fixing - For 60 mm busbars Accessories 3RV29 infeed system for load feeders

8/65 8/66

SIRIUS 3RA6 compact starters General data 3RA61, 3RA62 compact starters - 3RA61 direct-on-line starters - 3RA62 reversing starters

8/67 8/68

3RA64, 3RA65 compact starters for IO-Link - 3RA64 direct-on-line starters - 3RA65 reversing starters

8/69 8/75 8/77

Accessories Add-on modules for AS-Interface Infeed system for 3RA6

8/84

SIRIUS 3RM1 motor starters

8/94

ET 200SP motor starters

8/56

NEW NEU

Click on this video symbol in the catalog PDF for further product information.

Siemens IC 10 · 2022

8

8/2

© Siemens 2022

Load feeders and motor starters for use in the control cabinet Introduction

■ Overview Central and compact starter solutions with each other, have a very compact design and are particularly easy and quick to install and wire up.

Our range offers you many different possibilities for simple and practical starter solutions in the control cabinet. Features common to all our load feeders, compact starters and motor starters: Like all SIRIUS devices they are optimally coordinated

In addition there is a seamless range of SIRIUS 3RW soft starters available for soft starting in the control cabinet (see page 6/2).

SIRIUS pre-assembled combinations

Performance (kW / 400 V)

1200

SIRIUS tested combinations

SINAMICS G120 frequency converter

625

SIRIUS soft starter

ET 200SP motor starter

Fixed Speed

IC01_00738

25 5

Variable Speed

8

Requirement

G120

125

SIRIUS star-delta (wye-delta) starter

G120C

SIRIUS direct-on-line SIRIUS 3RM1 and reversing motor starter starter

G120X

Functionality

SINAMICS V20 frequency converter

3RA2110 3RA2120 3RA2110

3RA2120

3RA2210

3RA2220

3RA2210

3RA2220

3RA2130 3RA2150 Type

Page

SIRIUS 3RA2 load feeders • The 3RA2 fuseless load feeders consist of the 3RV2 motor starter protector and the 3RT2 contactor. The motor starter protector and contactor are prewired and mechanically and electrically connected in preassembled assembly kits (link modules, wiring kits and standard mounting rail or busbar adapters). • 4 sizes (S00, S0, S2, S3) • Can be supplied for direct-on-line start or reversing duty as - a complete unit or - single devices for self-assembly • Can be supplied with screw or spring-loaded terminals 3RA21 direct-on-line starters for snapping onto standard mounting rails or for screw fixing

• Rated control supply voltage 50/60 Hz 230 V AC and 24 V DC

3RA21

8/21

3RA21 direct-on-line starters for 60 mm busbars

• Rated control supply voltage 50/60 Hz 230 V AC and 24 V DC

3RA21

8/29

3RA22 reversing starters for snapping onto standard mounting rails or for screw fixing

• Rated control supply voltage 50/60 Hz 230 V AC and 24 V DC

3RA22

8/33

3RA22 reversing starters for 60 mm busbars

• Rated control supply voltage 50/60 Hz 230 V AC and 24 V DC

3RA22

8/39 8/44

Accessories for 3RA2 direct-on-line and reversing starters Infeed system

8/2

Siemens IC 10 · 2022

• The infeed system is a convenient means of energy supply and distribution for 3RV29 a group of several motor starter protectors or complete load feeders with screw or spring-loaded terminals up to size S0.

7/69, 8/55

© Siemens 2022

Load feeders and motor starters for use in the control cabinet Introduction

3RA61

3RA62

3RA68

3RM12

3RM13

3RK1308

3RK1308

3RK1908-0

3RK1908-1A

Type

Page

SIRIUS 3RA6 compact starters • Integrated functionality of a motor starter protector, contactor and electronic overload relay and various functions of optional mountable accessories • Can be used for direct starting of standard three-phase motors up to 32 A 3RA61 direct-on-line starters

• Up to 15 kW/400 V, weld-free, wide setting range, removable terminals

3RA61

8/65

3RA62 reversing starters

• Up to 15 kW/400 V, weld-free, wide setting range, removable terminals

3RA62

8/66

3RA64 direct-on-line starters for IO-Link

• Up to 15 kW/400 V, weld-free, wide setting range, removable terminals

3RA64

8/67

3RA65 reversing starters for IO-Link

• Up to 15 kW/400 V, weld-free, wide setting range, removable terminals

3RA65

8/68

3RA69

8/69

3RA69

8/75

3RA68

8/77

Accessories for 3RA6 direct-on-line and reversing starters Add-on modules for AS-Interface • Modular expandability, up to 100 A, terminals up to 70 mm2 • 3-phase infeeds and expansion modules

8/80

• Expansion modules

8/81

• Accessories for infeed systems for 3RA6

8/82

8

Infeed system for 3RA6

SIRIUS 3RM1 motor starters • For switching three-phase motors up to 3 kW (at 400 V) and resistive loads up to 10 A at AC voltages up to 500 V under normal operating conditions • Space-saving design (width 22.5 mm) 3RM10 direct-on-line starters

• Direct-on-line starting with electronic overload protection

3RM10

8/90

3RM12 reversing starters

• Reversing functionality with electronic overload protection

3RM12

8/90

3RM11 Failsafe direct-on-line starters

• As 3RM10 plus safety-related shutdown

3RM11

8/90

3RM13 Failsafe reversing starters

• As 3RM12 plus safety-related shutdown

3RM13

8/90

Accessories for 3RM1 motor starters

• 3RM19 3-phase infeed system for the main circuit

3RM19

8/91

• Fuse modules for the use of 3RM1 motor starters on 8US busbar systems and mounting rails

3RM19

8/88

• Adapters

8US1

8/91

• Cover profiles

8US1922

8/92

• Device connectors for the control circuit

3ZY1212

8/92

• Spare terminals for main and control circuits

3ZY11

8/93

• Push-in lugs for wall mounting, integrated sealable cover, coding pins

3ZY1

8/93

ET 200SP motor starters • In hybrid technology in the SIMATIC ET 200SP I/O system • For the switching and protection of three-phase asynchronous motors, single-phase AC motors and single-phase asynchronous motors up to 5.5 kW (at 400 V) 3RK1308 direct-on-line starters

• Direct-on-line starting with electronic overload protection

3RK1308-0A.0

8/100

3RK1308 reversing starters

• Reversing functionality with electronic overload protection

3RK1308-0B.0

8/100

3RK1308 fail-safe direct-on-line starters

• Direct-on-line starting with electronic overload protection

3RK1308-0C.0

8/100

3RK1308 fail-safe reversing starters

• Reversing functionality with electronic overload protection

3RK1308-0D.0

8/100

BaseUnits

• Designed for the infeed and integration into the ET 200SP I/O system

3RK1908-0AP00 8/101

3DI/LC control module

• Module with three digital inputs for the use of additional functions such as "Quick stop", and for manual-local operation

3RK1908-1AA00 8/101

Accessories

• Cover for BaseUnit and infeed bus, additional mechanical mounting unit, fan

3RK19, 3RW49

Siemens IC 10 · 2022

8/102

8/3

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders General data

■ Overview 3RA2 load feeders More information Homepage, see www.siemens.com/sirius-control Industry Mall, see www.siemens.com/product?3RA2 Online configurator, see www.siemens.com/sirius/configurators TIA Selection Tool Cloud (TST Cloud), see www.siemens.com/tstcloud/?node=LoadFeeder

Operating conditions 3RA2 load feeders are climate-proof. They are intended for use in enclosed rooms in which no severe operating conditions (such as dust, caustic vapors, hazardous gases) prevail. Suitable covers must be provided for installation in dusty and damp locations. Behavior in the event of short circuit

3RA22 reversing starters for snapping onto standard mounting rails or for screw fixing with screw terminals

ToC

1

Around 500 preassembled 3RA2 combinations can be ordered for direct-on-line and reversing starting of standard three-phase motors up to 65 A (approx. 37 kW/400 V). Preassembled assembly kits are available as accessories for the power range up to 45 kW. The desired fuseless load feeder can thus be assembled quickly and economically by the customer. A time saving is also achieved in connection with switchgear acceptances, as – unlike with conventional wiring systems – there is no need to rectify possible wiring errors.

ToC

2

In the 3RA2 load feeder, the 3RV2 motor starter protector is responsible for overload and short-circuit protection. Upcircuit protective devices, such as melting fuses or limiters, are superfluous here, as the motor starter protector is short-circuit-proof up to 150 kA at 400 V. The 3RT2 contactor is particularly suitable for extremely complex switching tasks requiring the greatest endurance. The 3RA2 load feeders are available with setting ranges from 0.14 to 65 A in sizes S00, S0 and S2. Load feeders in size S3 up to 100 A are available for customer assembly. Width Direct-on-line starters/ reversing starters

Max. rated current In max

For three-phase motors up to

mm

A

kW

S00

45/90

16

7.5

S0

45/90

32

15

S2

55/120

65

37

S3

70/150

100

45

S00

S0

Size of 3RV2 motor starter protector

S00

S001),

Size of 3RT2 contactor

S00

1)

S2 S2

S3 S3

S0 S0

Siemens IC 10 · 2022

Voltages The specifications for 3-phase systems acc. to IEC 60947-4-1 apply for the following line system configurations: .

Voltage data Line system configurations Ue in the Three-phase Three-phase catalog Four-wire systems Three-wire systems

V

S2

S3

V

230

--

400

230/400

400

440

260/440

440

500

--

500

690

400/690

690 (only from size S3)

-- Not specified

The combination of an S00 motor starter protector with an S0 contactor is possible only for screw terminal versions.

8/4

The types of coordination are indicated in the corresponding tables by the symbols shown on orange backgrounds.

V

The size of the 3RA2 load feeders is based on the size of the contactor: Size 3RA2

Type of coordination "2" There must be no damage to the overload release or to any other component after a short circuit has been cleared. The load feeder can resume operation without needing to be renewed. At most, welding of the contactor contacts is permissible if they can be disconnected easily without any significant deformation.

IC01_00709

Size

Type of coordination "1" The load feeder may be non-operational after a short circuit has been cleared. Damage to the contactor or to the overload release is permissible.

IC01_00703

8

The 3RA2 fuseless load feeders consist of the 3RV2 motor starter protector and the 3RT2 electromechanical contactor. The devices are electrically and mechanically connected using preassembled assembly kits (link modules, wiring kits and standard mounting rail or busbar adapters).

EN 60947-4-1 (VDE 0660 Part 102) and IEC 60947-4-1 make a distinction between two different types of coordination, which are referred to as type of coordination "1" and type of coordination "2". Any short circuits that occur are cleared safely by both types of coordination. The only differences concern the extent of the damage caused to the device by a short circuit.

230

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders General data All 3RA2 load feeders described here are designed for normal starting, in other words for overload tripping times of less than 10 s (CLASS 10). At rated-load operating temperature the tripping times are shorter, depending on the particular equipment and the setting range. The exact values can be derived from the tripping characteristics of the motor starter protectors.

In particular, certain accessories have been optimized for the fuseless load feeders. These include the top-connected, transverse auxiliary switch on the motor starter protector, which is available in a range of different versions. Special auxiliary switches that can be snapped on from below are available for the contactor. These two accessories enable the fuseless load feeders to be wired simply without having to route cables through the device.

Connection methods

Incoming power supply

For all 3RA2 feeders up to 32 A, spring-loaded terminals are available as well as screw terminals. To connect two devices with spring-loaded terminals, there are plug-in connection modules for sizes S00 and S0 which enable very quick mounting of the feeders and a vibration-resistant assembly.

In total, four different energy supply options are available (see "3RV29 infeed system for load feeders" on page 8/55).

To connect a motor starter protector with screw terminals to a contactor with spring-loaded terminals there are special hybrid connection modules for the sizes S00 and S0. Screw terminals

Customer assembly of fuseless load feeders Whereas preassembled 3RA2s can be ordered up to 65 A, combinations in size S3 up to 100 A (approx. 45 kW/400 V) can be assembled by the customer. The standard devices can be combined optimally – in terms of both technical specifications and dimensions, thanks to the modular system of the SIRIUS series.

Spring-loaded terminals

The fuseless load feeders can thus be assembled easily by the customer. It is simply necessary to assemble the standard 3RV2 motor starter protector, the 3RT2 contactor and the appropriate assembly kit.

The terminals are indicated in the corresponding tables by the symbols shown on orange backgrounds.

For single devices and assembly kits, see the "Selection and ordering data" for 3RA21 direct-on-line starters and 3RA22 reversing starters, page 8/21 or 8/33 onwards.

Use of load feeders in conjunction with IE3/IE4 motors Note: For the use of SIRIUS 3RA2 load feeders in conjunction with highly energy-efficient IE3/IE4 motors, please observe the information on dimensioning and configuring, see Application Manual. For more information, see page 1/8. 3RA2 complete units The 3RA2 fuseless load feeders can be ordered as preassembled complete units for direct-on-line starting (3RA21) or for reversing duty (3RA22) with screw or spring-loaded terminals. From size S2, complete units for direct-on-line starting (3RA21) are only available with screw terminals. There are control supply voltages available of 50 Hz 230 V AC and 24 V DC. A distinction is also drawn between whether the feeder is mounted on a 35 mm standard mounting rail, on a flat surface using screws, or on a 60 mm busbar system. 3RA21 load feeders in the S0 size must be configured on standard mounting rail adapters if high vibration and shock loads (railways, Kraftwerk Union, etc.) are involved. A vibration and shock kit is available for mounting on busbar adapters. Accessories As the 3RA2 fuseless load feeders are constructed from 3RV2 motor starter protectors and 3RT2 contactors, the same accessories – such as auxiliary switches, undervoltage releases or door-coupling rotary operating mechanisms – can be used for the 3RA2 fuseless load feeders as for these motor starter protectors and contactors.

For assembly kits for direct-on-line starting or reversing duty for mounting onto standard mounting rails or busbars, see page 8/49. For size S3 direct-on-line starters and sizes S0, S2 and S3 reversing starters, it is imperative that a standard mounting rail adapter is used to ensure the necessary mechanical strength. If a busbar adapter is used (not possible for size S3) then a standard mounting rail adapter is not necessary. SENTRON 3VA circuit breakers and SIRIUS 3RT contactors are available for rated currents >100 A. Special equipment for customer assembly can be ordered if other rated control supply voltages are required. Assembly kits can be used to facilitate assembly. Customers can also assemble tested combinations of motor starter protectors with solid-state controls (soft starters, solidstate contactors) and load feeders with additional monitoring and control devices (3RR monitoring relays, SIMOCODE 3UF). For the electrical and mechanical connection of protection equipment and controls there are preassembled assembly kits (link modules, wiring kits and standard mounting rail or busbar adapters). The following types of configuration are possible: • Direct-on-line/reversing starting • Star-delta (wye-delta) starting • Solid-state/soft starting For more information and assignment tables for combinations of the 3RA2 generation for self-assembly, see • Configuration Manual for load feeders, https://support.industry.siemens.com/cs/ww/en/view/39714188 • Equipment Manual, https://support.industry.siemens.com/cs/ww/en/view/60284351

Siemens IC 10 · 2022

8/5

8

Tripping times

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders General data Customer assembly of fused load feeders The flexible, modular system of SIRIUS also enables the configuration of fused load feeders up to 100 A (approx. 45 kW/400 V). Up to 32 A is also available for 45 mm installation widths. Compact 3NW7...-1 cylindrical fuse holders for IEC fuses size 10 x 38 mm, or 3NW7...-1HG holders for Class CC UL fuses, can be used for this purpose. For more information about fuse systems, see Catalog LV 10. Communications integration using IO-Link Load feeders can also be assembled with IO-Link for connection to the higher-level control system. For each feeder, this requires a contactor with a voltage tap onto which a 3RA2711 function module is plugged (various versions for direct-on-line, reversing and wye-delta starters). The design of the SIRIUS load feeders permits a group of up to four SIRIUS controls to be conveniently connected through the standardized open system IO-Link to a control system, thus reducing wiring considerably compared to the conventional parallel wiring method. The electrical connection is made using only three standard cables. The function modules perform not only the communication (contactor operation and feedback, ready signal) but also the electrical interlocking (for reversing and wye-delta starters) and the timing relay function (wye-delta reversing time).

8

Communication information and control supply voltages are passed on through ribbon cables so that the complete control current wiring on the feeder is no longer needed. The monitoring and maintenance of a plant is made considerably easier by transmitting diverse diagnostics data from the function modules (e.g. missing main and auxiliary voltage, local disconnection…) through IO-Link to the higherlevel control system. Also, feeders equipped for IO-Link can be conveniently controlled from the control cabinet door using the optional operator panel. More information: • For IO-Link, see page 2/87 onwards • For 3RA27 function modules, see pages 3/83, 3/90 and 3/110 Communications integration via AS-Interface Connection of the load feeders to the higher-level control system is possible not only through IO-Link but also through AS-Interface. The AS-Interface connection is recommended wherever load feeders are used in distributed applications. In this case, too, a contactor with a voltage tap is required with a corresponding 3RA2712 function module (various versions for direct-on-line, reversing and wye-delta starters). The devices are implemented in A/B technology, making it easy to connect up to 62 feeders to an AS-i master (regardless of whether they are direct-on-line, reversing or wye-delta starters). This results in a significant reduction of wiring compared to the conventional parallel wiring method. The electrical connection is made using standard cables.

8/6

Siemens IC 10 · 2022

The function modules perform not only the communication (contactor operation and feedback, ready signal) but also the electrical interlocking (for reversing and wye-delta starters) and the timing relay function (wye-delta reversing time). Communication information and control supply voltages are passed on through ribbon cables so that the complete control current wiring on the starter is no longer needed. More information: • For AS-Interface, see page 2/18 onwards • For 3RA27 function modules, see pages 3/83, 3/90 and 3/110 Contactors with voltage tap For configuring load feeders with communication interfaces (AS-i/IO-Link), contactors with voltage taps are required. These contactors are not included as standard in the preassembled 3RA2 load feeders. A load feeder with communication interface must be assembled therefore from single devices. Complete integration in the automation landscape As the result of the communication connection through IO-Link or AS-i, the SIRIUS load feeders are fully integrated in the automation landscape and can draw on all the advantages of TIA (e.g. integration in the TIA Maintenance Station). Mounting 3RA2 fuseless load feeders can be supplied: • For assembly on TH 35 standard mounting rails according to IEC 60715 (depth 15 mm) • For assembly on busbar adapters (busbar center-to-center clearance 60 mm, busbar thickness 5 to 10 mm with beveled edges) The fuseless load feeders are also suitable for screw fixing using two 3RV2928-0B push-in lugs. 3RA2 fuseless load feeders can also be installed using the 3RV29 infeed system (S0 and S00 only, see page 7/69).

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders General data Direct-on-line starting • For standard rail mounting or screw fixing • Sizes S00 and S0 1

1

1 2 push-in lugs 3RV2928-0B (only for screw fixing)

1

2 Motor starter protector Size S00/S0 Screw terminals

3

2

2

3 Motor starter protector Size S00/S0 Spring-loaded terminals 4 Link module (Screw terminals) 3RA1921-1DA00 (for S00) 3RA2921-1AA00 (for S0, AC contactor) 3RA2921-1BA00 (for S0, DC contactor)

5

6

7 Contactor Size S00/S0 Screw terminals

8

8

IC01_00636

7

8 Contactor Size S00/S0 Spring-loaded terminals

8

4

5 Link module (Spring-loaded terminals) 3RA2911-2AA00 for S00 3RA2921-2AA00 for S0 6 Link module (Hybrid) 3RA2911-2FA00 for S00 3RA2921-2FA00 for S0

Left: 3RA21 load feeder with screw terminals Center: 3RA21 load feeder with spring-loaded terminals Right: Motor starter protector combination with screw terminals, with contactor with spring-loaded terminals 1

1 2 push-in lugs 3RV2928-0B (only for screw fixing)

1

2 Motor starter protector Size S00/S0 Screw terminals

3 2

3 Motor starter protector Size S00/S0 Screw terminals/spring-loaded terminals 4 Link module 3RA2921-1BA00 (Screw terminals) 5 Link module 3RA2921-1BA00 for S00/S0 and screw terminals 3RA2911-2GA00 for S00 and spring-loaded terminals 3RA2921-2GA00 for S0 and spring-loaded terminals 4

6 Solid-state switching device (Screw terminals)

5

7 Soft starter Size S00/S0 Screw terminals/spring-loaded terminals

6

IC01_00637

7

Left: Right:

Motor starter protector combination with solid-state switching device with screw terminals Motor starter protector combination with soft starter with spring-loaded terminals

Siemens IC 10 · 2022

8/7

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders General data Direct-on-line starting • For standard rail mounting • Size S2 2

1

1 Motor starter protector Size S2 Screw terminals

3

2 Standard mounting rail adapter (optional) 3RA2932-1AA00 Alternatively, the device can be mounted on two standard mounting rails spaced at a distance of 175 mm without a standard mounting rail adapter.

1

3 Standard mounting rail adapter 3RA2932-1CA00

IC01_00638

4 Link module 3RA2931-1AA00 Screw terminals

4

5

6

8

4

Left: Right:

8/8

3RA21 load feeder with screw terminals Motor starter protector combination with soft starter with screw terminals

Siemens IC 10 · 2022

5 Contactor Size S2 Screw terminals 6 Soft starter Size S2 Screw terminals

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders General data Direct-on-line starting • For standard rail mounting • Size S3 2

3

1 Motor starter protector Size S3 Screw terminals 2 Standard mounting rail adapter 3RA2942-1AA00

1

1

3 Mounting plate 4 Link module 3RA1941-1AA00 Screw terminals 5 Contactor Size S3 Screw terminals 6 Soft starter Size S3 Screw terminals

4

5

6

8

IC01_00655b

4

3RA21 load feeder for direct-on-line starting and standard rail mounting in size S3 (the version with screw terminals is shown in the figure)

Direct-on-line starting • For 60 mm busbar systems • Sizes S00 and S0 2

1

5

7

4

6

8

3 Motor starter protector Size S00/S0 Screw terminals 4 Motor starter protector Size S00/S0 Spring-loaded terminals

IC01_00639

3

1 60 mm busbar adapter for screw terminals 8US1251-5DS10 for S00 8US1251-5NT10 for S0 2 60 mm busbar adapter for spring-loaded terminals 8US1251-5DT11 for S00 8US1251-5NT11 for S0

5 Link module Screw terminals 3RA1921-1DA00 for S00 3RA2921-1AA00 for S0, AC contactor 3RA2921-1BA00 for S0, DC contactor 6 Link module 3RA2911-2AA00 for S00 3RA2921-2AA00 for S0 (additional 3RA2911-1CA00 spacer for height compensation on AC contactors size S0 with spring-loaded terminals) 7 Contactor Size S00/S0 Screw terminals 8 Contactor Size S00/S0 Spring-loaded terminals

Left: Right:

3RA21 load feeder for direct-on-line starting with busbar adapter with screw terminals 3RA21 load feeder for direct-on-line starting with busbar adapter with spring-loaded terminals Siemens IC 10 · 2022

8/9

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders General data Direct-on-line starting • For 60 mm busbar systems • Size S2

2

1 Motor starter protector Size S2 Screw terminals 2 Busbar adapter 60 mm 8US1261-6MT10 3 Link module 3RA2931-1AA00 Screw terminals 4 Contactor Size S2 Screw terminals

IC01_00640

1

3

8

4

3RA21 load feeder for direct-on-line starting with busbar adapter with screw terminals

8/10

Siemens IC 10 · 2022

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders General data Reversing duty • For standard rail mounting or screw fixing • Size S00 1

1 Push-in lug 3RV2928-0B (only for screw fixing)

1

2 Motor starter protector Size S00/S0 Screw terminals

3

2

3 Motor starter protector Size S00/S0 Spring-loaded terminals 4 Link module Screw terminals 3RA1921-1DA00 for S00 3RA2921-1AA00 for S0, AC contactor 3RA2921-1BA00 for S0, DC contactor

4

5 Link module Spring-loaded terminals 3RA2911-2AA00 for S00 3RA2921-2AA00 for S0

5

6 Contactor Size S00/S0 Screw terminals 7 Contactor Size S00/S0 Spring-loaded terminals

e a

6

7

6

c

7

h

b

Wiring kit 3RA2913-2AA1 a Upper wiring module

IC01_00641

d

f

Wiring kit 3RA2913-2AA2 e Upper wiring module

b Lower wiring module c Two connecting clips for two contactors

f Lower wiring module g Two connecting clips for two contactors

d Mechanical interlock (can be removed if necessary)

h Mechanical interlock (can be removed if necessary)

Left: Right:

8

g

3RA22 load feeder with screw terminals with push-in lugs with two contactors for reversing duty and 3RA2913-2AA1 wiring kit for connection of the contactors (incl. mechanical interlock and connecting clips) 3RA22 load feeder with spring-loaded terminals with push-in lugs with two contactors for reversing duty and 3RA2913-2AA2 wiring kit (incl. mechanical interlock and connecting clips)

Siemens IC 10 · 2022

8/11

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders General data Reversing duty • For standard rail mounting • Size S0 2

2

RH assembly kit for reversing duty and standard rail mounting in size S0 Screw terminals 3RA2923-1BB1 Spring-loaded terminals 1) 3RA2923-1BB2 Consisting of: • Wiring kit for the main and auxiliary circuits • Two standard mounting rail adapters • Two connecting wedges • Mechanical interlock • Two connecting clips • Fixing accessories

1

1 Motor starter protector Size S0 Screw terminals/spring-loaded terminals

3

2 Standard mounting rail adapters 3RA2922-1AA00 with two connecting wedges 8US1998-1AA00 a 4

4

IC01_00642

8

c

d

b

3 Link module Screw terminals 3RA2921-1AA00 for S0, AC contactor 3RA2921-1BA00 for S0, DC contactor Spring-loaded terminals 2) 3RA2921-2AA00 4 Contactor Size S0 Screw terminals/spring-loaded terminals Wiring kit Screw terminals 3RA2923-2AA1 Spring-loaded terminals 3RA2923-2AA2 a Upper wiring module b Lower wiring module c Two connecting clips for two contactors d Mechanical interlock (can be removed if necessary)

1) Contains two 3RA2911-1CA00 spacers for

height compensation on AC contactors size S0 with spring-loaded terminals. 2)

3RA22 load feeder for reversing duty and standard rail mounting in size S0 (the version with screw terminals is shown in the figure)

RH assembly kits for reversing duty and standard rail mounting in size S0, see page 8/51.

8/12

Siemens IC 10 · 2022

Additionally two 3RA2911-1CA00 spacers for height compensation on AC contactors size S0 with spring-loaded terminals.

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders General data Reversing duty • For standard rail mounting • Size S2 2 2

RH assembly kit for reversing duty and standard rail mounting in size S2 3RA2933-1BB1 Consisting of: • Wiring kit for the main and auxiliary circuits • Two standard mounting rail adapters • Two side modules • Four connecting wedges • Mechanical interlock • Two connectors for two contactors • Fixing accessories

IC01_00643

1

3

1 Motor starter protector Size S2 Screw terminals 2 Standard mounting rail adapter 3RA2932-1AA00 with two side modules 3RA2902-1B and four connecting wedges 8US1998-1AA00 3 Link module 3RA2931-1AA00 Screw terminals

a 4

c

Wiring kit Screw terminals 3RA2933-2AA1 a Upper wiring module

d

8

4

4 Contactor Size S2 Screw terminals

b Lower wiring module c Two connectors for two contactors d Mechanical interlock 3RA2934-2B (not part of the wiring kit, must be ordered separately) b

3RA22 load feeder for reversing duty and standard rail mounting in size S2 (the version with screw terminals is shown in the figure)

RH assembly kits for reversing duty and standard rail mounting in size S2, see page 8/51.

Siemens IC 10 · 2022

8/13

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders General data Reversing duty • For standard rail mounting • Size S3 2 2

RH assembly kit for reversing duty and standard rail mounting in size S3

3RA2943-1BB1 Consisting of: • Wiring kit for the main and auxiliary circuits • Two standard mounting rail adapters • Three side modules • Six connecting wedges • Mechanical interlock • Two connectors for two contactors • Fixing accessories

IC01_00656b

1

3

a

4

4

c

1 Motor starter protector Size S3 2 Standard mounting rail adapter 3RA2942-1AA00 with two side modules 3RA2902-1B and four connecting wedges 8US1998-1AA00 3 Link module 3RA1941-1AA00 4 Contactor Size S3 Wiring kit Screw terminals 3RA2943-2AA1 a Upper wiring module

d

8

b Lower wiring module c Two connectors for two contactors d Mechanical interlock 3RA2934-2B (not part of the wiring kit, must be ordered separately) b

3RA22 load feeder for reversing duty and standard rail mounting in size S3 (the version with screw terminals is shown in the figure)

RH assembly kits for reversing duty and standard rail mounting in size S3, see page 8/51.

8/14

Siemens IC 10 · 2022

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders General data Reversing duty • For 60 mm busbar systems • Sizes S00 and S0 3

RS assembly kit for reversing duty and busbar mounting in size S00/S0

3

Screw terminals 3RA2913-1DB1 for S00 3RA2923-1DB1 for S0 Spring-loaded terminals 3RA2913-1DB2 for S00 3RA2923-1DB2 for S0 1) Consisting of: • Wiring kit for the main and auxiliary circuits • Busbar adapter • Device holder • Two connecting wedges • Mechanical interlock • Two connecting clips for two contactors • Fixing accessories

1

2

1 Motor starter protector Size S00/S0 Screw terminals/spring-loaded terminals 2 Link module Screw terminals 3RA1921-1DA00 for S00 3RA2921-1AA00 for S0, AC contactor 3RA2921-1BA00 for S0, DC contactor Spring-loaded terminals 3RA2911-2AA00 for S00 3RA2921-2AA00 for S0 2)

4

4

IC01_00644

c

d

b

Wiring kit Screw terminals 3RA2913-2AA1 for S00 3RA2923-2AA1 for S0 Spring-loaded terminals 3RA2913-2AA2 for S00 3RA2923-2AA2 for S0 a Upper wiring module b Lower wiring module c Two connecting clips for two contactors d Mechanical interlock (can be removed if necessary)

3 60 mm busbar adapter Screw terminals 8US1251-5DS10 for S00/S0 8US1251-5NT10 for S0 Spring-loaded terminals 8US1251-5DT11 for S00/S0 8US1251-5NT11 for S0 2 connecting wedges 8US1998-1AA00

8

a

60 mm device holder 8US1250-5AS10 or 8US1250-5AT10 (according to length of left adapter) 4 Contactor Size S00/S0 Screw terminals/spring-loaded terminals

1) Contains two 3RA2911-1CA00 spacers

for height compensation on AC contactors size S0 with spring-loaded terminals. 2) Additionally two 3RA2911-1CA00 spacers

for height compensation on AC contactors size S0 with spring-loaded terminals.

3RA22 load feeder for reversing duty and 60 mm busbar (the version with screw terminals is shown in the figure)

RS assembly kits for reversing duty and busbar mounting in size S00/S0, see page 8/53.

Siemens IC 10 · 2022

8/15

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders General data Reversing duty • For 60 mm busbar systems • Size S2 RS assembly kit for reversing duty and busbar mounting in size S2 2 3RA2933-1DB1 Consisting of: • Wiring kit for the main and auxiliary circuits • Busbar adapter • Mechanical interlock • Two connectors for two contactors • Fixing accessories

1

1 Motor starter protector Size S2 Screw terminals 2 Busbar adapter 60 mm 8US1211-6MT10 3 Link module 3RA2931-1AA00 Screw terminals 4 Contactor Size S2 Screw terminals

3

Wiring kit Screw terminals 3RA2933-2AA1 a Upper wiring module b Lower wiring module c Two connectors for two contactors

8

a 4

4

c

IC01_00645

d

b

3RA22 load feeder for reversing duty and 60 mm busbar in size S2 (the version with screw terminals is shown in the figure)

RS assembly kits for reversing duty and busbar mounting in size S2, see page 8/53.

8/16

Siemens IC 10 · 2022

d Mechanical interlock 3RA2934-2B (not part of the wiring kit, must be ordered separately)

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders General data Article No. scheme Product versions

Article number 3RA2 @ @ 0 – @ @ @ @ @ – @ @ @ @

SIRIUS load feeders Product function

Direct-on-line starter Reversing starter

Size

S00 S0 e.g. 3 = S2 e.g. 5 = S2

Setting range of the overload release

e.g. 0B = 0.14 ... 0.2 A

Assembly, assembly type, connection method

e.g. A = S00, S0, S2

Contactor size, rated power at 400 V AC

e.g. 15 = S00/3 kW

Version of auxiliary switches on the contactor

e.g. 0 = S0, S2 e.g. 1 = S00 e.g. 2 = S00

Operating range of solenoid coil (contactor)

e.g. A = S00, S0, S2

Rated control supply voltage (contactor)

230 V AC 24 V DC

Example

For motor standard output 0.06 ... 45 kW For motor standard output 0.06 ... 45 kW

1 2 1 2 @ @

At Iq = 100 kA at 400 V At Iq = 150 kA at 400 V @@ @

Direct mounting, screw terminals

@@

@ @ @

1 NO + 1 NC integrated in contactor 1 NO integrated in contactor 1 NC integrated in contactor @

AC 0.8 x Us min ... 1.1 x Us max, standard coil without RC circuit P 0 50/60 Hz AC for S00, 50 Hz AC for S0 ... S3 B 4

3RA2 1 1 0 – 0 B A 1 5 – 1 A P 0

8

Note: The Article No. scheme shows an overview of product versions for better understanding of the logic behind the article numbers. For your orders, please use the article numbers quoted in the selection and ordering data.

■ Benefits • Minimum planning and assembly work and far less wiring with the preassembled complete units (only one article number 3RA2) • Plug-in connectors from the motor starter protector to all types of SIRIUS controls, for quicker and error-free assembly of feeders with screw and spring-loaded terminals • High planning reliability through consistent combination tests for fuseless and fused configuration in accordance with IEC and UL/CSA • Comprehensive approvals for use world-wide on request, see page 16/7 onwards • High operational reliability through short-circuit breaking capacity of 150 kA with type of coordination "1" and "2"

• Uniform accessories for sizes S00, S0, S2 and S3 • Spring-loaded terminals possible throughout: Enhanced operational reliability (vibration-resistant wiring) and less wiring work thanks to plug-in connections (S00 and S0 only) • Power loss 5 to 10% smaller than for comparable devices, hence lower energy consumption • Connection of feeders to the control system through standardized system connection (IO-Link and AS-i), for fast integration in TIA and less wiring work

Siemens IC 10 · 2022

8/17

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders General data

■ Technical specifications More information Industry Mall, see www.siemens.com/product?3RA2

FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16289/faq

Equipment Manual, see https://support.industry.siemens.com/cs/ww/en/view/60284351 Configuration Manual, see https://support.industry.siemens.com/cs/ww/en/view/39714188 Direct-on-line starters/ reversing starters

Size

Connection method

Mounting

Control voltage

Width W

Height H Depth D

mm

mm

mm

Mounting dimensions Direct-on-line starters

S00

3RA21.

3RA211.

Screw terminals

Standard mounting rails

AC/DC

45

167

97

Busbar adapters

AC/DC

45

200

155

AC/DC

45

198

97

Busbar adapters

AC/DC

45

260

155

Standard mounting rails

AC

45

193

97

DC

45

193

107

AC

45

260

155

DC

45

260

165

AC/DC

45

243

107

Busbar adapters

AC/DC

45

260

165

Standard mounting rails

AC/DC

55

274

150

3RA213./3RA215.

Busbar adapters

AC/DC

55

350

208

S3 Screw terminals (self-assembly only)

Standard mounting rail adapters

AC/DC

70

333

198

Standard mounting rails

AC/DC

90

170

97

Busbar adapters

AC/DC

90

200

155

AC/DC

90

204

97

Busbar adapters

AC/DC

90

260

155

Standard mounting rail adapters

AC

90

265

120.3

DC

90

265

130

Busbar adapters

AC

90

260

155

DC

90

260

165

AC/DC

90

270

131

Busbar adapters

(Size S3 or larger is only available for self-assembly)

Spring-loaded terminals Standard mounting rails S0

Screw terminals

H

3RA212.

W

D

Busbar adapters Spring-loaded terminals Standard mounting rails

Reversing starters

S00

3RA22.

3RA221.

(Size S2 or larger is only available for self-assembly)

Screw terminals

Screw terminals

Spring-loaded terminals Standard mounting rails S0

Screw terminals

3RA222.

Spring-loaded terminals Standard mounting rail adapters

AC/DC

90

260

165

S2 Screw terminals (self-assembly only)

Standard mounting rails

AC/DC

120

295

175

Busbar adapters

AC/DC

120

361

208

S3 Screw terminals (self-assembly only)

Standard mounting rail adapters

AC/DC

150

333

198

Type

3RA2.1

3RA2.2

For self-assembly

S0 3

3RA213, 3RA215 S2 3

Size Number of poles

S00 3

0.8 ... 2.3

2.2 ... 2.5

4.0 ... 4.2

S3 3

Mechanics and environment Permissible ambient temperature • During operation • During storage and transport

°C °C

-20 ... +60 -55 ... +80

Weight

kg

0.6 ... 1.5

Permissible mounting position

22,5° 22,5° 90°

90°

NSB0_00369

8

S2

Important: Acc. to DIN 43602 start command "I" at the right or top IEC 60068-2-27

Degree of protection IP on the front

According to IEC 60529

IP20

Touch protection on the front

According to IEC 60529

Finger-safe for vertical touching from the front

8/18

Siemens IC 10 · 2022

g/ms

6/11 (sine pulse)

Shock resistance

On request

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders General data Type

3RA2.1

3RA2.2

Size Number of poles

S00 3

S0 3

3RA213, 3RA215 S2 3

For self-assembly

65

100

3RA213: 100 3RA215: 150

With 3RV2041: 100 With 3RV2042: 150

S3 3

Electrical specifications • IEC 60947-1, EN 60947-1 (VDE 0660 Part 100)

Standards

• IEC 60947-2, EN 60947-2 (VDE 0660 Part 101) • IEC 60947-4-1, EN 60947-4-1 (VDE 0660 Part 102) Max. rated current In max (= max. rated operational current Ie)

A

16

Rated operational voltage Ue

V

690

Rated frequency

Hz

50/60

Rated insulation voltage Ui (pollution degree 3)

V

690

kV

6

Rated impulse withstand voltage Uimp

32

Trip class (CLASS)

Acc. to IEC 60947-4-1, EN 60947-4-1 (VDE 0660 Part 102)

10

Rated short-circuit current Iq at AC 50/60 Hz 400 V

Acc. to IEC 60947-4-1, kA EN 60947-4-1 (VDE 0660 Part 102)

150

Types of coordination

Acc. to IEC 60947-4-1, EN 60947-4-1 (VDE 0660 Part 102)

See "Selection and ordering data", page 8/21 onwards

Power loss Pv of all main conducting paths Dependent on rated current In (upper setting range)

See technical specifications of the individual devices:

Power consumption of the solenoid coils with contactors

See technical specifications of the contactor, page 3/26 onwards

• "Switching Devices – Contactors and Contactor Assemblies", page 3/25 onwards • "Protection Equipment"  "Motor starter protectors/circuit breakers", page 7/19 onwards

8

Magnetic coil operating range with contactors Endurance of the motor starter protector • Mechanical service life • Electrical endurance • Max. switching frequency per hour (motor starts)

Oper- 100 000 ating cycles Oper- 100 000 ating cycles 15 1/h

Up to 52 A: 50 000 25 000 From 59 A: 20 000 25 000

Endurance of contactor • Mechanical service life

Oper- 30 million 10 million ating cycles Oper- See endurance characteristic curves of the contactors, page 3/26 onwards ating cycles

• Electrical endurance

Phase failure sensitivity of the motor starter protector

Acc. to IEC 60947-1, EN 60947-1 (VDE 0660 Part 102)



Isolating features of the motor starter protector

Acc. to IEC 60947-2, EN 60947-2 (VDE 0660 Part 101)



Main and EMERGENCY STOP switch characteristics of the motor starter protector and accessories

Acc. to IEC 60204-1, EN 60204-1 (VDE 0113 Part 1)

✓ (With overvoltage releases of category "1" under conditions of proper use)

Protective separation between main and auxiliary circuits

Acc. to EN 60947-1, Appendix N

Mirror contacts for contactors Integrated auxiliary switches

V

Up to 400 ✓ Acc. to IEC 60947-4-1, Annex F

✓ Function available

Siemens IC 10 · 2022

8/19

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders General data Conductor cross-sections of main circuit Type

3RA2.10

3RA2.20

3RA2130-4E..., 3RA2130-4P..., 3RA2130-4U..., 3RA2130-4V...

Size

S00

S0

S2

Connection type

3RA2130-4W..., For 3RA2130-4X..., self-assembly 3RA2130-4J..., 3RA2130-4K..., 3RA2150 S3

Screw terminals

Terminal screw

Screw terminals with box terminal

M3, Pozidriv size 2

M4, Pozidriv size 2

M6, Pozidriv size 2

4 mm Allen screw

Operating devices

mm

 5 ... 6

 5 ... 6

 5 ... 6

Allen screw

Prescribed tightening torque

Nm

0.8 ... 1.2

2 ... 2.5

3.0 ... 4.5

4.5 ... 6

• Solid or stranded

mm2

2 x (0.75 ... 2.5)1), 2 x (1 ... 2.5)1), 2 x (0.5 ... 1.5)1), 2 x (2.5 ... 10)1) only for contactor 2x4

2 x (1 ... 25)1), 1 x (1 ... 35)1)

2 x (1 ... 35)1), 1 x (1 ... 50)1)

2 x (2.5 ... 16)1), 2 x (10 ... 50)1), 1 x (10 ... 70)1)

• Finely stranded with end sleeve (DIN 46228)

mm2

2 x (0.5 ... 1.5)1), 2 x (0.75 ... 2.5)1)

2 x (1 ... 2.5)1), 2 x (2.5 ... 6)1), 1 x 10

2 x (1 ... 16)1), 1 x (1 ... 25)1)

2 x (1 ... 25)1), 1 x (1 ... 35)1)

2 x (2.5 ... 35)1), 1 x (2.5... 50)1)

• AWG cables, solid or stranded

AWG

2 x (20 ... 16)1), 2 x (16 ... 12)1), only for contactor 2 x (14 ... 8)1) 2 x (18 ... 14)1), 2 x 12

2 x (18 ... 3)1), 1 x (18 ... 2)1)

2 x (18 ... 2)1), 1 x (18 ... 1)1)

2 x (10 ... 1/0)1), 1 x (10... 2/0)1)

Conductor cross-sections (min./max.), 1 or 2 conductors can be connected

• Ribbon cable conductors (Number x Width x Thickness) mm

--

8

Operating devices

2 x (6 x 9 x 0.8) Spring-loaded terminals

Connection type mm

3.0 x 0.5 and 3.5 x 0.5

Conductor cross-sections (min./max.), 1 or 2 conductors can be connected • Solid or stranded

mm2

2 x (0.5 ... 4)

2 x (1 ... 10)

--

• Finely stranded without end sleeve

mm2

2 x (0.5 ... 2.5)

2 x (1 ... 6)

--

• Finely stranded with end sleeve (DIN 46228)

mm2

2 x (0.5 ... 2.5)

2 x (1 ... 6)

--

• AWG cables, solid or stranded

AWG

2 x (20 ... 12)

2 x (18 ... 8)

--

Max. external diameter of the conductor insulation

mm

3.6

3.6

--

1)

If two different conductor cross-sections are connected to one clamping point, both cross-sections must be in the range specified.

Conductor cross-sections for auxiliary and control circuits Type

3RA2110 3RA2210

3RA2120 3RA2220

3RA2130 3RA2150

For self-assembly

Size

S00

S0

S2

S3

Connection type

Screw terminals M3, Pozidriv size 2

Terminal screw Operating devices

mm

 5 ... 6

Prescribed tightening torque

Nm

0.8 ... 1.2

• Solid or stranded

mm2

2 x (0.5 ... 1.5)1), 2 x (0.75 ... 2.5)1)

• Finely stranded with end sleeve (DIN 46228)

mm2

2 x (0.5 ... 1.5)1), 2 x (0.75 ... 2.5)1)

• AWG cables, solid or stranded

AWG

2 x (18 ... 14)1), 2 x (20 ... 16)1), 2 x 12 for contactor S00 only

Conductor cross-sections (min./max.), 1 or 2 conductors can be connected

Spring-loaded terminals

Connection type mm

3.0 x 0.5 and 3.5 x 0.5

• Solid or stranded

mm2

2 x (0.5 ... 2.5)

• Finely stranded without end sleeve

mm2

2 x (0.5 ... 2.5)

• Finely stranded with end sleeve (DIN 46228)

mm2

2 x (0.5 ... 1.5)

• AWG cables, solid or stranded

AWG

2 x (20 ... 14)

Max. external diameter of the conductor insulation

mm

3.6

Operating devices Conductor cross-sections (min./max.), 1 or 2 conductors can be connected

1)

If two different conductor cross-sections are connected to one clamping point, both cross-sections must be in the range specified.

8/20

Siemens IC 10 · 2022

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders 3RA21 direct-on-line starters > for standard mounting rail or for screw fixing

■ Selection and ordering data Direct-on-line start

3RA2110 Size

3RA2120

• Screw fixing with two push-in lugs per load feeder possible1) • The motor starter protector and contactor are mechanically and electrically connected by means of the link module. • Auxiliary switches2) on the motor starter protector and the contactor can be easily fitted thanks to the modular system. • Integrated auxiliary switches: Contactor size S00: 1 NO, Contactor sizes S0, S2 and S3: 1 NO + 1 NC

3RA2150

Adjustable current response value of the inversetime delayed overload Motor current I release (guide value)

Rated control supply voltage 50/60 Hz 230 V AC for S00, 50 Hz 230 V AC for S0, S2 and S3 With screw terminals

Standard three-phase motor 4-pole at 400 V AC3)

Consisting of the following single devices

Standard output P

Motor starter protector

SD

+ Contactor + Link module

Fuseless load feeder

A

A

PS*

PG

Screw terminals

Article No. kW

PU (UNIT, SET, M)

d

Basic price per PU

Type of coordination "2" at Iq = 150 kA at 400 V (also compatible with type of coordination "1")

S0

S2

S3

3RT20

3RA

15-1AP01

1921-1DA00 2 2 2

3RA2110-0BA15-1AP0 3RA2110-0CA15-1AP0 3RA2110-0DA15-1AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

ToC

2

0.06 0.06 0.09

0.2 0.2 0.3

0.14 ... 0.2 0.18 ... 0.25 0.22 ... 0.32

11-0BA10 11-0CA10 11-0DA10

0.09 0.12 0.18

0.3 0.4 0.6

0.28 ... 0.4 0.35 ... 0.5 0.45 ... 0.63

11-0EA10 11-0FA10 11-0GA10

2 2 2

3RA2110-0EA15-1AP0 3RA2110-0FA15-1AP0 3RA2110-0GA15-1AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

0.18 0.25 0.37

0.6 0.85 1.1

0.55 ... 0.8 0.7 ... 1 0.9 ... 1.25

11-0HA10 11-0JA10 11-0KA10

2 2 2

3RA2110-0HA15-1AP0 3RA2110-0JA15-1AP0 3RA2110-0KA15-1AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

0.55 0.75 0.75

1.5 1.9 1.9

1.1 ... 1.6 1.4 ... 2 1.8 ... 2.5

11-1AA10 11-1BA10 11-1CA10

2 2 2

3RA2110-1AA15-1AP0 3RA2110-1BA15-1AP0 3RA2110-1CA15-1AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1.1 1.5

2.7 3.6

2.2 ... 3.2 2.8 ... 4

11-1DA10 11-1EA10

2 2

3RA2110-1DA15-1AP0 3RA2110-1EA15-1AP0

1 1

1 unit 1 unit

41D 41D

1.5 2.2 3 4 5.5

3.6 4.9 6.5 8.5 11.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8 7 ... 10 9 ... 12.5

11-1FA10 11-1GA10 11-1HA10 11-1JA10 11-1KA10

24-1AP00

2921-1AA00 2 2 2 2 2

3RA2120-1FA24-0AP0 3RA2120-1GA24-0AP0 3RA2120-1HA24-0AP0 3RA2120-1JA24-0AP0 3RA2120-1KA24-0AP0

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

7.5

15.5

10 ... 16

21-4AA10

26-1AP00

2

3RA2120-4AA26-0AP0

1

1 unit

41D

7.5 11 11 15 15

15.5 22 22 28 294)

13 ... 20 16 ... 22 18 ... 25 23 ... 28 27 ... 32

21-4BA10 21-4CA10 21-4DA10 21-4NA10 21-4EA10

27-1AP00

5 2 2 2 2

3RA2120-4BA27-0AP0 3RA2120-4CA27-0AP0 3RA2120-4DA27-0AP0 3RA2120-4NA27-0AP0 3RA2120-4EA27-0AP0

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

15 18.5 18.5

29 35 35

22 ... 32 28 ... 36 32 ... 40

32-4EA10 32-4PA10 32-4UA10

35-1AP00

2931-1AA00 2 2 2

3RA2150-4EA35-0AP0 3RA2150-4PA35-0AP0 3RA2150-4UA35-0AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

22 22

41 41

35 ... 45 42 ... 50

32-4VA10 32-4WA10

36-1AP00

2 2

3RA2150-4VA36-0AP0 3RA2150-4WA36-0AP0

1 1

1 unit 1 unit

41D 41D

30 30

55 55

49 ... 59 54 ... 65

32-4XA10 32-4JA10

37-1AP00

2 2

3RA2150-4XA37-0AP0 3RA2150-4JA37-0AP0

1 1

1 unit 1 unit

41D 41D

375)

66

62 ... 75

32-4KA10

38-1AP00

2

3RA2150-4KA38-0AP0

1

1 unit

41D

Size S3 available on request

Size S3 is only available for self-assembly

1)

For push-in lugs, see "Accessories", page 8/51. For auxiliary switches, see "Accessories", page 8/44. 3) The actual starting and rated data of the motor to be protected must be considered when selecting the units. 4) Suitable for use with IE3/IE4 motors up to a starting current of 256 A. For higher starting currents we recommend using size S2. 5) Maximum permissible current setting at motor starter protector 65 A, as the maximum permissible current of the 3RA2931-1AA00 link module is 65 A. 2)

* You can order this quantity or a multiple thereof. Illustrations are approximate

Siemens IC 10 · 2022

8/21

8

S00

3RV20

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders 3RA21 direct-on-line starters > for standard mounting rail or for screw fixing Direct-on-line start

Rated control supply voltage 50/60 Hz 230 V AC for S00 With screw terminals

• Screw fixing with two push-in lugs per load feeder possible1) • The motor starter protector and contactor are mechanically and electrically connected by means of the link module. • Auxiliary switches2) on the motor starter protector and the contactor can be easily fitted thanks to the modular system. • Integrated auxiliary switches: Contactor size S00: 1 NO 3RA2110 Size

Standard three-phase motor 4-pole at 400 V AC3)

Adjustable current response value of the inversetime delayed overload Motor current I release (guide value)

Consisting of the following single devices

Standard output P

Motor starter protector

SD

+ Contactor + Link module

Fuseless load feeder

A

A

PS*

PG

Screw terminals

Article No. kW

PU (UNIT, SET, M)

Basic price per PU

d

Type of coordination "1" at Iq = 150 kA at 400 V (motor starter protector is compatible with type of coordination "2") 3RV20

3RT20

3RA

ToC

1

8

S00

For load feeders for lower outputs, see table for type of coordination "2" on the previous page. 1.5 2.2 3

3.6 4.9 6.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8

11-1FA10 11-1GA10 11-1HA10

15-1AP01

1921-1DA00 2 2 2

3RA2110-1FA15-1AP0 3RA2110-1GA15-1AP0 3RA2110-1HA15-1AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

4 5.5 7.5

8.5 11.5 15.5

7 ... 10 9 ... 12.5 10 ... 16

11-1JA10 11-1KA10 11-4AA10

16-1AP01 17-1AP01 18-1AP01

2 2 2

3RA2110-1JA16-1AP0 3RA2110-1KA17-1AP0 3RA2110-4AA18-1AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1)

For push-in lugs, see "Accessories", page 8/51. For auxiliary switches, see "Accessories", page 8/44. 3) The actual starting and rated data of the motor to be protected must be considered when selecting the units. 2)

8/22

Siemens IC 10 · 2022

* You can order this quantity or a multiple thereof. Illustrations are approximate

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders 3RA21 direct-on-line starters > for standard mounting rail or for screw fixing Direct-on-line start

Rated control supply voltage 50 Hz 230 V AC for S2 and S3 With screw terminals

• Screw fixing with two push-in lugs per load feeder possible1) • The motor starter protector and contactor are mechanically and electrically connected by means of the link module. • Auxiliary switches2) on the motor starter protector and the contactor can be easily fitted thanks to the modular system. • Integrated auxiliary switches: Contactor sizes S2 and S3: 1 NO + 1 NC 3RA2130 Size

Standard three-phase motor 4-pole at 400 V AC3)

Adjustable current response value of the inversetime delayed overload Motor current I release (guide value)

Consisting of the following single devices

Standard output P

Motor starter protector

SD

+ Contactor + Link module

Fuseless load feeder

A

A

PS*

PG

Screw terminals

Article No. kW

PU (UNIT, SET, M)

d

Basic price per PU

Type of coordination "2" at Iq = 100 kA at 400 V (motor starter protector is compatible with type of coordination "2")

S3

3RT20

3RA

35-1AP00

2931-1AA00 2 2 2 2 2

3RA2130-4EA35-0AP0 3RA2130-4PA35-0AP0 3RA2130-4UA35-0AP0 3RA2130-4VA36-0AP0 3RA2130-4WA36-0AP0

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

ToC

2

15 18.5 18.5 22 22

29 35 35 41 41

22 ... 32 28 ... 36 32 ... 40 35 ... 45 42 ... 50

31-4EA10 31-4PA10 31-4UA10 31-4VA10 31-4WA10

30 30

55 55

49 ... 59 54 ... 65

31-4XA10 31-4JA10

37-1AP00

2 2

3RA2130-4XA37-0AP0 3RA2130-4JA37-0AP0

1 1

1 unit 1 unit

41D 41D

374)

66

62 ... 73

31-4KA10

38-1AP00

2

3RA2130-4KA38-0AP0

1

1 unit

41D

36-1AP00

Size S3 available on request

Size S3 is only available for self-assembly

1)

For push-in lugs, see "Accessories", page 8/51. For auxiliary switches, see "Accessories", page 8/44. 3) The actual starting and rated data of the motor to be protected must be considered when selecting the units. 4) Maximum permissible current setting at motor starter protector 65 A, as the maximum permissible current of the 3RA2931-1AA00 link module is 65 A. 2)

* You can order this quantity or a multiple thereof. Illustrations are approximate

Siemens IC 10 · 2022

8/23

8

S2

3RV20

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders 3RA21 direct-on-line starters > for standard mounting rail or for screw fixing Direct-on-line start

3RA2110 Size

Rated control supply voltage 50/60 Hz 230 V AC for S00, 50 Hz 230 V AC for S0 With spring-loaded terminals

• Screw fixing with two push-in lugs per load feeder possible1) • The motor starter protector and contactor are mechanically and electrically connected by means of the link module. • Auxiliary switches2) on the motor starter protector and the contactor can be easily fitted thanks to the modular system. • Integrated auxiliary switches: Contactor size S00: 1 NO, Contactor size S0: 1 NO + 1 NC

3RA2120 Standard three-phase motor 4-pole at 400 V AC3)

Adjustable current response value of the inversetime delayed overload Motor current I release (guide value)

Consisting of the following single devices

Standard output P

Motor starter protector

SD

+ Contactor + Link module

Fuseless load feeder

A

A

PS*

PG

Spring-loaded terminals

Article No. kW

PU (UNIT, SET, M)

Basic price per PU

d

Type of coordination "2" at Iq = 150 kA at 400 V (also compatible with type of coordination "1")

8

S00

S0

3RV20

3RT20

3RA29

15-2AP01

11-2AA00

0.06 0.06 0.09

0.2 0.2 0.3

0.14 ... 0.2 0.18 ... 0.25 0.22 ... 0.32

11-0BA20 11-0CA20 11-0DA20

0.09 0.12 0.18

0.3 0.4 0.6

0.28 ... 0.4 0.35 ... 0.5 0.45 ... 0.63

0.18 0.25 0.37

0.6 0.85 1.1

0.55 0.75 0.75

ToC

2

2 2 2

3RA2110-0BE15-1AP0 3RA2110-0CE15-1AP0 3RA2110-0DE15-1AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

11-0EA20 11-0FA20 11-0GA20

2 2 2

3RA2110-0EE15-1AP0 3RA2110-0FE15-1AP0 3RA2110-0GE15-1AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

0.55 ... 0.8 0.7 ... 1 0.9 ... 1.25

11-0HA20 11-0JA20 11-0KA20

2 2 2

3RA2110-0HE15-1AP0 3RA2110-0JE15-1AP0 3RA2110-0KE15-1AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1.5 1.9 1.9

1.1 ... 1.6 1.4 ... 2 1.8 ... 2.5

11-1AA20 11-1BA20 11-1CA20

2 2 2

3RA2110-1AE15-1AP0 3RA2110-1BE15-1AP0 3RA2110-1CE15-1AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1.1 1.5

2.7 3.6

2.2 ... 3.2 2.8 ... 4

11-1DA20 11-1EA20

2 2

3RA2110-1DE15-1AP0 3RA2110-1EE15-1AP0

1 1

1 unit 1 unit

41D 41D

1.5 2.2 3 4 5.5

3.6 4.9 6.5 8.5 11.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8 7 ... 10 9 ... 12.5

21-1FA20 21-1GA20 21-1HA20 21-1JA20 21-1KA20

24-2AP00

5 5 5 5 5

3RA2120-1FE24-0AP0 3RA2120-1GE24-0AP0 3RA2120-1HE24-0AP0 3RA2120-1JE24-0AP0 3RA2120-1KE24-0AP0

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

7.5 7.5 11 11 15 15

15.5 15.5 22 22 28 294)

10 ... 16 13 ... 20 16 ... 22 18 ... 25 23 ... 28 27 ... 32

21-4AA20 21-4BA20 21-4CA20 21-4DA20 21-4NA20 21-4EA20

26-2AP00 27-2AP00

2 5 2 2 2 2

3RA2120-4AE26-0AP0 3RA2120-4BE27-0AP0 3RA2120-4CE27-0AP0 3RA2120-4DE27-0AP0 3RA2120-4NE27-0AP0 3RA2120-4EE27-0AP0

1 1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D 41D

21-2AA00

Type of coordination "1" at Iq = 150 kA at 400 V (motor starter protector is compatible with type of coordination "2") S00

For load feeders for lower outputs, see this table at type of coordination "2".

ToC

1

1.5 2.2 3

3.6 4.9 6.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8

11-1FA20 11-1GA20 11-1HA20

15-2AP01

4 5.5 7.5

8.5 11.5 15.5

7 ... 10 9 ... 12.5 10 ... 16

11-1JA20 11-1KA20 11-4AA20

16-2AP01 17-2AP01 18-2AP01

11-2AA00

2 2 2

3RA2110-1FE15-1AP0 3RA2110-1GE15-1AP0 3RA2110-1HE15-1AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

2 2 2

3RA2110-1JE16-1AP0 3RA2110-1KE17-1AP0 3RA2110-4AE18-1AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1)

For push-in lugs, see "Accessories", page 8/51. For auxiliary switches, see "Accessories", page 8/44. 3) The actual starting and rated data of the motor to be protected must be considered when selecting the units. 4) Suitable for use with IE3/IE4 motors up to a starting current of 256 A. For higher starting currents we recommend using size S2. 2)

8/24

Siemens IC 10 · 2022

* You can order this quantity or a multiple thereof. Illustrations are approximate

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders 3RA21 direct-on-line starters > for standard mounting rail or for screw fixing Direct-on-line start

3RA2110 Size

• Screw fixing with two push-in lugs per load feeder possible1) • The motor starter protector and contactor are mechanically and electrically connected by means of the link module. • Auxiliary switches2) on the motor starter protector and the contactor can be easily fitted thanks to the modular system. • Integrated auxiliary switches: Contactor size S00: 1 NO, Contactor sizes S0, S2 and S3: 1 NO + 1 NC

3RA2150

3RA2120

Adjustable current response value of the inversetime delayed overload Motor current I release (guide value)

Rated control supply voltage 24 V DC With screw terminals

Standard three-phase motor 4-pole at 400 V AC3)

Consisting of the following single devices

Standard output P

Motor starter protector

SD

+ Contactor + Link module

Fuseless load feeder

A

A

PS*

PG

Screw terminals

Article No. kW

PU (UNIT, SET, M)

d

Basic price per PU

Type of coordination "2" at Iq = 150 kA at 400 V (also compatible with type of coordination "1")

S0

S2

S3

3RT20

3RA

15-1BB41

1921-1DA00 2 2 2

3RA2110-0BA15-1BB4 3RA2110-0CA15-1BB4 3RA2110-0DA15-1BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

ToC

2

0.06 0.06 0.09

0.2 0.2 0.3

0.14 ... 0.2 0.18 ... 0.25 0.22 ... 0.32

11-0BA10 11-0CA10 11-0DA10

0.09 0.12 0.18

0.3 0.4 0.6

0.28 ... 0.4 0.35 ... 0.5 0.45 ... 0.63

11-0EA10 11-0FA10 11-0GA10

2 2 2

3RA2110-0EA15-1BB4 3RA2110-0FA15-1BB4 3RA2110-0GA15-1BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

0.18 0.25 0.37

0.6 0.85 1.1

0.55 ... 0.8 0.7 ... 1 0.9 ... 1.25

11-0HA10 11-0JA10 11-0KA10

2 2 2

3RA2110-0HA15-1BB4 3RA2110-0JA15-1BB4 3RA2110-0KA15-1BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

0.55 0.75 0.75

1.5 1.9 1.9

1.1 ... 1.6 1.4 ... 2 1.8 ... 2.5

11-1AA10 11-1BA10 11-1CA10

2 2 2

3RA2110-1AA15-1BB4 3RA2110-1BA15-1BB4 3RA2110-1CA15-1BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1.1 1.5

2.7 3.6

2.2 ... 3.2 2.8 ... 4

11-1DA10 11-1EA10

2 2

3RA2110-1DA15-1BB4 3RA2110-1EA15-1BB4

1 1

1 unit 1 unit

41D 41D

1.5 2.2 3 4 5.5

3.6 4.9 6.5 8.5 11.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8 7 ... 10 9 ... 12.5

11-1FA10 11-1GA10 11-1HA10 11-1JA10 11-1KA10

24-1BB40

2921-1BA00 2 2 2 2 2

3RA2120-1FA24-0BB4 3RA2120-1GA24-0BB4 3RA2120-1HA24-0BB4 3RA2120-1JA24-0BB4 3RA2120-1KA24-0BB4

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

7.5

15.5

10 ... 16

21-4AA10

26-1BB40

2

3RA2120-4AA26-0BB4

1

1 unit

41D

7.5 11 11 15 15

15.5 22 22 28 294)

13 ... 20 16 ... 22 18 ... 25 23 ... 28 27 ... 32

21-4BA10 21-4CA10 21-4DA10 21-4NA10 21-4EA10

27-1BB40

5 2 2 2 2

3RA2120-4BA27-0BB4 3RA2120-4CA27-0BB4 3RA2120-4DA27-0BB4 3RA2120-4NA27-0BB4 3RA2120-4EA27-0BB4

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

15 18.5 18.5 22 22

29 35 35 41 41

22 ... 32 28 ... 36 32 ... 40 35 ... 45 42 ... 50

32-4EA10 32-4PA10 32-4UA10 32-4VA10 32-4WA10

35-1NB30

2931-1AA00 2 2 2 2 2

3RA2150-4EA35-0NB3 3RA2150-4PA35-0NB3 3RA2150-4UA35-0NB3 3RA2150-4VA36-0NB3 3RA2150-4WA36-0NB3

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

30 30 375)

55 55 66

49 ... 59 54 ... 65 62 ... 73

32-4XA10 32-4JA10 32-4KA10

2 2 2

3RA2150-4XA37-0NB3 3RA2150-4JA37-0NB3 3RA2150-4KA38-0NB3

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

36-1NB30 37-1NB30 38-1NB30

Size S3 available on request

Size S3 is only available for self-assembly

1)

For push-in lugs, see "Accessories", page 8/51. For auxiliary switches, see "Accessories", page 8/44. 3) The actual starting and rated data of the motor to be protected must be considered when selecting the units. 4) Suitable for use with IE3/IE4 motors up to a starting current of 256 A. For higher starting currents we recommend using size S2. 5) Maximum permissible current setting at motor starter protector 65 A, as the maximum permissible current of the 3RA2931-1AA00 link module is 65 A. 2)

* You can order this quantity or a multiple thereof. Illustrations are approximate

Siemens IC 10 · 2022

8/25

8

S00

3RV20

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders 3RA21 direct-on-line starters > for standard mounting rail or for screw fixing Direct-on-line start

Rated control supply voltage 24 V DC With screw terminals

• Screw fixing with two push-in lugs per load feeder possible1) • The motor starter protector and contactor are mechanically and electrically connected by means of the link module. • Auxiliary switches2) on the motor starter protector and the contactor can be easily fitted thanks to the modular system. • Integrated auxiliary switches: Contactor size S00: 1 NO 3RA2110 Size

Standard three-phase motor 4-pole at 400 V AC3)

Adjustable current response value of the inversetime delayed overload Motor current I release (guide value)

Consisting of the following single devices

Standard output P

Motor starter protector

SD

+ Contactor + Link module

Fuseless load feeder

A

A

PS*

PG

Screw terminals

Article No. kW

PU (UNIT, SET, M)

Basic price per PU

d

Type of coordination "1" at Iq = 150 kA at 400 V (motor starter protector is compatible with type of coordination "2") 3RV20

3RT20

3RA

ToC

1

8

S00

For load feeders for lower outputs, see table for type of coordination "2" on the previous page. 1.5 2.2 3

3.6 4.9 6.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8

11-1FA10 11-1GA10 11-1HA10

15-1BB41

1921-1DA00 2 2 2

3RA2110-1FA15-1BB4 3RA2110-1GA15-1BB4 3RA2110-1HA15-1BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

4 5.5 7.5

8.5 11.5 15.5

7 ... 10 9 ... 12.5 10 ... 16

11-1JA10 11-1KA10 11-4AA10

16-1BB41 17-1BB41 18-1BB41

2 2 2

3RA2110-1JA16-1BB4 3RA2110-1KA17-1BB4 3RA2110-4AA18-1BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1)

For push-in lugs, see "Accessories", page 8/51. For auxiliary switches, see "Accessories", page 8/44. 3) The actual starting and rated data of the motor to be protected must be considered when selecting the units. 2)

8/26

Siemens IC 10 · 2022

* You can order this quantity or a multiple thereof. Illustrations are approximate

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders 3RA21 direct-on-line starters > for standard mounting rail or for screw fixing Direct-on-line start

Rated control supply voltage 24 V DC With screw terminals

• Screw fixing with two push-in lugs per load feeder possible1) • The motor starter protector and contactor are mechanically and electrically connected by means of the link module. • Auxiliary switches2) on the motor starter protector and the contactor can be easily fitted thanks to the modular system. • Integrated auxiliary switches: Contactor sizes S2 and S3: 1 NO + 1 NC 3RA2130 Size

Standard three-phase motor 4-pole at 400 V AC3)

Adjustable current response value of the inversetime delayed overload Motor current I release (guide value)

Consisting of the following single devices

Standard output P

Motor starter protector

SD

+ Contactor + Link module

Fuseless load feeder

A

A

PS*

PG

Screw terminals

Article No. kW

PU (UNIT, SET, M)

d

Basic price per PU

Type of coordination "2" at Iq = 100 kA at 400 V (motor starter protector is compatible with type of coordination "2")

S3

3RT20

3RA

35-1NB30

2931-1AA00 2 2 2 2 2

3RA2130-4EA35-0NB3 3RA2130-4PA35-0NB3 3RA2130-4UA35-0NB3 3RA2130-4VA36-0NB3 3RA2130-4WA36-0NB3

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

2 2 2

3RA2130-4XA37-0NB3 3RA2130-4JA37-0NB3 3RA2130-4KA38-0NB3

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

15 18.5 18.5 22 22

29 35 35 41 41

22 ... 32 28 ... 36 32 ... 40 35 ... 45 42 ... 50

31-4EA10 31-4PA10 31-4UA10 31-4VA10 31-4WA10

30 30 374)

55 55 66

49 ... 59 54 ... 65 62 ... 73

31-4XA10 31-4JA10 31-4KA10

36-1NB30 37-1NB30 38-1NB30

Size S3 available on request

ToC

2

Size S3 is only available for self-assembly

1)

For push-in lugs, see "Accessories", page 8/51. For auxiliary switches, see "Accessories", page 8/44. 3) The actual starting and rated data of the motor to be protected must be considered when selecting the units. 4) Maximum permissible current setting at motor starter protector 65 A, as the maximum permissible current of the 3RA2931-1AA00 link module is 65 A. 2)

* You can order this quantity or a multiple thereof. Illustrations are approximate

Siemens IC 10 · 2022

8/27

8

S2

3RV20

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders 3RA21 direct-on-line starters > for standard mounting rail or for screw fixing Direct-on-line start

Rated control supply voltage 24 V DC With spring-loaded terminals

• Screw fixing with two push-in lugs per load feeder possible1) • The motor starter protector and contactor are mechanically and electrically connected by means of the link module. • Auxiliary switches2) on the motor starter protector and the contactor can be easily fitted thanks to the modular system. • Integrated auxiliary switches: Contactor size S00: 1 NO, Contactor size S0: 1 NO + 1 NC 3RA2110 Size

3RA2120 Standard three-phase motor 4-pole at 400 V AC3)

Adjustable current response value of the inversetime delayed overload Motor current I release (guide value)

Consisting of the following single devices

Standard output P

Motor starter protector

SD

+ Contactor + Link module

Fuseless load feeder

A

A

PS*

PG

Spring-loaded terminals

Article No. kW

PU (UNIT, SET, M)

Basic price per PU

d

Type of coordination "2" at Iq = 150 kA at 400 V (also compatible with type of coordination "1")

8

S00

S0

3RV20

3RT20

3RA29

15-2BB41

11-2AA00

0.06 0.06 0.09

0.2 0.2 0.3

0.14 ... 0.2 0.18 ... 0.25 0.22 ... 0.32

11-0BA20 11-0CA20 11-0DA20

0.09 0.12 0.18

0.3 0.4 0.6

0.28 ... 0.4 0.35 ... 0.5 0.45 ... 0.63

0.18 0.25 0.37

0.6 0.85 1.1

0.55 0.75 0.75

ToC

2

2 2 2

3RA2110-0BE15-1BB4 3RA2110-0CE15-1BB4 3RA2110-0DE15-1BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

11-0EA20 11-0FA20 11-0GA20

2 2 2

3RA2110-0EE15-1BB4 3RA2110-0FE15-1BB4 3RA2110-0GE15-1BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

0.55 ... 0.8 0.7 ... 1 0.9 ... 1.25

11-0HA20 11-0JA20 11-0KA20

2 2 2

3RA2110-0HE15-1BB4 3RA2110-0JE15-1BB4 3RA2110-0KE15-1BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1.5 1.9 1.9

1.1 ... 1.6 1.4 ... 2 1.8 ... 2.5

11-1AA20 11-1BA20 11-1CA20

2 2 2

3RA2110-1AE15-1BB4 3RA2110-1BE15-1BB4 3RA2110-1CE15-1BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1.1 1.5

2.7 3.6

2.2 ... 3.2 2.8 ... 4

11-1DA20 11-1EA20

2 2

3RA2110-1DE15-1BB4 3RA2110-1EE15-1BB4

1 1

1 unit 1 unit

41D 41D

1.5 2.2 3 4 5.5

3.6 4.9 6.5 8.5 11.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8 7 ... 10 9 ... 12.5

21-1FA20 21-1GA20 21-1HA20 21-1JA20 21-1KA20

24-2BB40

5 5 5 5 5

3RA2120-1FE24-0BB4 3RA2120-1GE24-0BB4 3RA2120-1HE24-0BB4 3RA2120-1JE24-0BB4 3RA2120-1KE24-0BB4

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

7.5

15.5

10 ... 16

21-4AA20

26-2BB40

2

3RA2120-4AE26-0BB4

1

1 unit

41D

7.5 11 11 15 15

15.5 22 22 28 294)

13 ... 20 16 ... 22 18 ... 25 23 ... 28 27 ... 32

21-4BA20 21-4CA20 21-4DA20 21-4NA20 21-4EA20

27-2BB40

5 2 2 2 2

3RA2120-4BE27-0BB4 3RA2120-4CE27-0BB4 3RA2120-4DE27-0BB4 3RA2120-4NE27-0BB4 3RA2120-4EE27-0BB4

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

21-2AA00

Type of coordination "1" at Iq = 150 kA at 400 V (motor starter protector is compatible with type of coordination "2") S00

For load feeders for lower outputs, see this table at type of coordination "2".

ToC

1

1.5 2.2 3

3.6 4.9 6.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8

11-1FA20 11-1GA20 11-1HA20

15-2BB41

4 5.5 7.5

8.5 11.5 15.5

7 ... 10 9 ... 12.5 10 ... 16

11-1JA20 11-1KA20 11-4AA20

16-2BB41 17-2BB41 18-2BB40

11-2AA00

2 2 2

3RA2110-1FE15-1BB4 3RA2110-1GE15-1BB4 3RA2110-1HE15-1BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

2 2 2

3RA2110-1JE16-1BB4 3RA2110-1KE17-1BB4 3RA2110-4AE18-1BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1)

For push-in lugs, see "Accessories", page 8/51. For auxiliary switches, see "Accessories", page 8/44. 3) The actual starting and rated data of the motor to be protected must be considered when selecting the units. 4) Suitable for use with IE3/IE4 motors up to a starting current of 256 A. For higher starting currents we recommend using size S2. 2)

8/28

Siemens IC 10 · 2022

* You can order this quantity or a multiple thereof. Illustrations are approximate

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders 3RA21 direct-on-line starters > for 60 mm busbars

■ Selection and ordering data Direct-on-line start

Rated control supply voltage 50/60 Hz 230 V AC for S00, 50 Hz 230 V AC for S0 and S2 With screw terminals

• With busbar adapter • The motor starter protector and contactor are mechanically and electrically connected by means of the link module. • Auxiliary switches1) on the motor starter protector and the contactor can be easily fitted thanks to the modular system. • Integrated auxiliary switches: Contactor size S00: 1 NO, Contactor sizes S0 and S2: 1 NO + 1 NC 3RA2110 Size

3RA2120 Standard three-phase motor 4-pole at 400 V AC2) Standard output P

Adjustable current response value of the inversetime delayed overload Motor current I release (guide value)

SD

Consisting of the following single devices Motor starter protector

+ Contactor + Link module + Busbar adapter

Fuseless load feeder

A

A

PS*

PG

Screw terminals

Article No. kW

PU (UNIT, SET, M)

d

Basic price per PU

Type of coordination "2" at Iq = 150 kA at 400 V (also compatible with type of coordination "1")

S0

S2

3RT20

3RA

15-1AP01

1921-1DA00 2 + 8US1251- 2 5DS10 2

3RA2110-0BD15-1AP0 3RA2110-0CD15-1AP0 3RA2110-0DD15-1AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

ToC

2

0.06 0.06 0.09

0.2 0.2 0.3

0.14 ... 0.2 0.18 ... 0.25 0.22 ... 0.32

11-0BA10 11-0CA10 11-0DA10

0.09 0.12 0.18

0.3 0.4 0.6

0.28 ... 0.4 0.35 ... 0.5 0.45 ... 0.63

11-0EA10 11-0FA10 11-0GA10

2 2 2

3RA2110-0ED15-1AP0 3RA2110-0FD15-1AP0 3RA2110-0GD15-1AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

0.18 0.25 0.37

0.6 0.85 1.1

0.55 ... 0.8 0.7 ... 1 0.9 ... 1.25

11-0HA10 11-0JA10 11-0KA10

2 2 2

3RA2110-0HD15-1AP0 3RA2110-0JD15-1AP0 3RA2110-0KD15-1AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

0.55 0.75 0.75

1.5 1.9 1.9

1.1 ... 1.6 1.4 ... 2 1.8 ... 2.5

11-1AA10 11-1BA10 11-1CA10

2 2 2

3RA2110-1AD15-1AP0 3RA2110-1BD15-1AP0 3RA2110-1CD15-1AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1.1 1.5

2.7 3.6

2.2 ... 3.2 2.8 ... 4

11-1DA10 11-1EA10

2 2

3RA2110-1DD15-1AP0 3RA2110-1ED15-1AP0

1 1

1 unit 1 unit

41D 41D

1.5 2.2 3 4 5.5

3.6 4.9 6.5 8.5 11.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8 7 ... 10 9 ... 12.5

11-1FA10 11-1GA10 11-1HA10 11-1JA10 11-1KA10

24-1AP00

2921-1AA00 2 + 8US1251- 2 5DT10 2 2 2

3RA2120-1FD24-0AP0 3RA2120-1GD24-0AP0 3RA2120-1HD24-0AP0 3RA2120-1JD24-0AP0 3RA2120-1KD24-0AP0

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

2921-1AA00 2 + 8US1251- 5 5NT10 2 2 2 2

3RA2120-4AD26-0AP0

1

1 unit

41D

3RA2120-4BD27-0AP0 3RA2120-4CD27-0AP0 3RA2120-4DD27-0AP0 3RA2120-4ND27-0AP0 3RA2120-4ED27-0AP0

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

2931-1AA00 + 8US12616MT10

Size S2 is only available for self-assembly.

7.5

15.5

10 ... 16

21-4AA10

26-1AP00

7.5 11 11 15 15

15.5 22 22 28 293)

13 ... 20 16 ... 22 18 ... 25 23 ... 28 27 ... 32

21-4BA10 21-4CA10 21-4DA10 21-4NA10 21-4EA10

27-1AP00

15 18.5 18.5 22 22

29 35 35 41 41

22 ... 32 28 ... 36 32 ... 40 35 ... 45 42 ... 50

32-4EA10 32-4PA10 32-4UA10 32-4VA10 32-4WA10

35-1AP00

30 30 374)

55 55 66

49 ... 59 54 ... 65 62 ... 73

32-4XA10 32-4JA10 32-4KA10

36-1AP00 37-1AP00 38-1AP00

Type of coordination "1" at Iq = 150 kA at 400 V (motor starter protector is compatible with type of coordination "2") S00

For load feeders for lower outputs, see this table at type of coordination "2".

ToC

1

1) 2)

1.5 2.2 3

3.6 4.9 6.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8

11-1FA10 11-1GA10 11-1HA10

15-1AP01

1921-1DA00 2 + 8US1251- 2 5DS10 2

3RA2110-1FD15-1AP0 3RA2110-1GD15-1AP0 3RA2110-1HD15-1AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

4 5.5 7.5

8.5 11.5 15.5

7 ... 10 9 ... 12.5 10 ... 16

11-1JA10 11-1KA10 11-4AA10

16-1AP01 17-1AP01 18-1AP01

2 2 2

3RA2110-1JD16-1AP0 3RA2110-1KD17-1AP0 3RA2110-4AD18-1AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

For auxiliary switches, see "Accessories", page 8/44. The actual starting and rated data of the motor to be protected must be considered when selecting the units.

* You can order this quantity or a multiple thereof. Illustrations are approximate

3)

Suitable for use with IE3/IE4 motors up to a starting current of 256 A. For higher starting currents we recommend using size S2. 4) Maximum permissible current setting at motor starter protector 65 A, as the maximum permissible current of the 3RA2931-1AA00 link module is 65 A.

Siemens IC 10 · 2022

8/29

8

S00

3RV20

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders 3RA21 direct-on-line starters > for 60 mm busbars Direct-on-line start

Rated control supply voltage 50/60 Hz 230 V AC for S00, 50 Hz 230 V AC for S0 With spring-loaded terminals

• With busbar adapter • The motor starter protector and contactor are mechanically and electrically connected by means of the link module. • Auxiliary switches1) on the motor starter protector and the contactor can be easily fitted thanks to the modular system. • Integrated auxiliary switches: Contactor size S00: 1 NO, Contactor size S0: 1 NO + 1 NC 3RA2110 Size

3RA2120 Standard three-phase motor 4-pole at 400 V AC2)

Adjustable current response value of the inverse-time delayed Motor current I overload (guide release value)

Consisting of the following single devices

Standard output P

Motor starter protector

SD

+ Contactor + Link module + Busbar adapter

Fuseless load feeder

A

A

PS*

PG

Spring-loaded terminals

Article No. kW

PU (UNIT, SET, M)

Basic price per PU

d

Type of coordination "2" at Iq = 150 kA at 400 V (also compatible with type of coordination "1")

8

S00

S0

3RV20

3RT20

3RA29

15-2AP01

11-2AA00 + 8US12515DT11

0.06 0.06 0.09

0.2 0.2 0.3

0.14 ... 0.2 0.18 ... 0.25 0.22 ... 0.32

11-0BA20 11-0CA20 11-0DA20

0.09 0.12 0.18

0.3 0.4 0.6

0.28 ... 0.4 0.35 ... 0.5 0.45 ... 0.63

0.18 0.25 0.37

0.6 0.85 1.1

0.55 0.75 0.75

ToC

2

2 2 2

3RA2110-0BH15-1AP0 3RA2110-0CH15-1AP0 3RA2110-0DH15-1AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

11-0EA20 11-0FA20 11-0GA20

2 2 2

3RA2110-0EH15-1AP0 3RA2110-0FH15-1AP0 3RA2110-0GH15-1AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

0.55 ... 0.8 0.7 ... 1 0.9 ... 1.25

11-0HA20 11-0JA20 11-0KA20

2 2 2

3RA2110-0HH15-1AP0 3RA2110-0JH15-1AP0 3RA2110-0KH15-1AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1.5 1.9 1.9

1.1 ... 1.6 1.4 ... 2 1.8 ... 2.5

11-1AA20 11-1BA20 11-1CA20

2 2 2

3RA2110-1AH15-1AP0 3RA2110-1BH15-1AP0 3RA2110-1CH15-1AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1.1 1.5

2.7 3.6

2.2 ... 3.2 2.8 ... 4

11-1DA20 11-1EA20

2 2

3RA2110-1DH15-1AP0 3RA2110-1EH15-1AP0

1 1

1 unit 1 unit

41D 41D

1.5 2.2 3 4 5.5

3.6 4.9 6.5 8.5 11.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8 7 ... 10 9 ... 12.5

21-1FA20 21-1GA20 21-1HA20 21-1JA20 21-1KA20

24-2AP00

5 5 5 5 5

3RA2120-1FH24-0AP0 3RA2120-1GH24-0AP0 3RA2120-1HH24-0AP0 3RA2120-1JH24-0AP0 3RA2120-1KH24-0AP0

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

7.5

15.5

10 ... 16

21-4AA20

26-2AP00

2

3RA2120-4AH26-0AP0

1

1 unit

41D

7.5 11 11 15 15

15.5 22 22 28 294)

13 ... 20 16 ... 22 18 ... 25 23 ... 28 27 ... 32

21-4BA20 21-4CA20 21-4DA20 21-4NA20 21-4EA20

27-2AP00

5 2 2 2 2

3RA2120-4BH27-0AP0 3RA2120-4CH27-0AP0 3RA2120-4DH27-0AP0 3RA2120-4NH27-0AP0 3RA2120-4EH27-0AP0

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

21-2AA00 + 8US12515NT113)

Type of coordination "1" at Iq = 150 kA at 400 V (motor starter protector is compatible with type of coordination "2") S00

For load feeders for lower outputs, see this table at type of coordination "2". 1.5 2.2 3

3.6 4.9 6.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8

11-1FA20 11-1GA20 11-1HA20

15-2AP01

4 5.5 7.5

8.5 11.5 15.5

7 ... 10 9 ... 12.5 10 ... 16

11-1JA20 11-1KA20 11-4AA20

16-2AP01 17-2AP01 18-2AP01

ToC

1

11-2AA00 + 8US12515DT11

2 2 2

3RA2110-1FH15-1AP0 3RA2110-1GH15-1AP0 3RA2110-1HH15-1AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

2 2 2

3RA2110-1JH16-1AP0 3RA2110-1KH17-1AP0 3RA2110-4AH18-1AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1)

For auxiliary switches, see "Accessories", page 8/44. The actual starting and rated data of the motor to be protected must be considered when selecting the units. 3) A 3RA2911-1CA00 spacer for height compensation on AC contactors size S0 with spring-loaded terminals is included in the scope of supply. 4) Suitable for use with IE3/IE4 motors up to a starting current of 256 A. For higher starting currents we recommend using size S2. 2)

8/30

Siemens IC 10 · 2022

* You can order this quantity or a multiple thereof. Illustrations are approximate

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders 3RA21 direct-on-line starters > for 60 mm busbars Direct-on-line start

Rated control supply voltage 24 V DC With screw terminals

• With busbar adapter • The motor starter protector and contactor are mechanically and electrically connected by means of the link module. • Auxiliary switches1) on the motor starter protector and the contactor can be easily fitted thanks to the modular system. • Integrated auxiliary switches: Contactor size S00: 1 NO, Contactor sizes S0 and S2: 1 NO + 1 NC 3RA2110 Size

3RA2120 Standard three-phase motor 4-pole at 400 V AC2)

Adjustable current response value of the inversetime delayed overload Motor current I release (guide value)

Consisting of the following single devices

Standard output P

Motor starter protector

SD

+ Contactor + Link module + Busbar adapter

Fuseless load feeder

A

PS*

PG

Screw terminals

Article No. kW

PU (UNIT, SET, M)

A

d

Basic price per PU

Type of coordination "2" at Iq = 150 kA at 400 V (also compatible with type of coordination "1")

S0

S2

3RT20

3RA

15-1BB41

1921-1DA00 2 + 8US1251- 2 5DS10 2

3RA2110-0BD15-1BB4 3RA2110-0CD15-1BB4 3RA2110-0DD15-1BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

ToC

2

0.06 0.06 0.09

0.2 0.2 0.3

0.14 ... 0.2 0.18 ... 0.25 0.22 ... 0.32

11-0BA10 11-0CA10 11-0DA10

0.09 0.12 0.18

0.3 0.4 0.6

0.28 ... 0.4 0.35 ... 0.5 0.45 ... 0.63

11-0EA10 11-0FA10 11-0GA10

2 2 2

3RA2110-0ED15-1BB4 3RA2110-0FD15-1BB4 3RA2110-0GD15-1BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

0.18 0.25 0.37

0.6 0.85 1.1

0.55 ... 0.8 0.7 ... 1 0.9 ... 1.25

11-0HA10 11-0JA10 11-0KA10

2 2 2

3RA2110-0HD15-1BB4 3RA2110-0JD15-1BB4 3RA2110-0KD15-1BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

0.55 0.75 0.75

1.5 1.9 1.9

1.1 ... 1.6 1.4 ... 2 1.8 ... 2.5

11-1AA10 11-1BA10 11-1CA10

2 2 2

3RA2110-1AD15-1BB4 3RA2110-1BD15-1BB4 3RA2110-1CD15-1BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1.1 1.5

2.7 3.6

2.2 ... 3.2 2.8 ... 4

11-1DA10 11-1EA10

2 2

3RA2110-1DD15-1BB4 3RA2110-1ED15-1BB4

1 1

1 unit 1 unit

41D 41D

1.5 2.2 3 4 5.5

3.6 4.9 6.5 8.5 11.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8 7 ... 10 9 ... 12.5

11-1FA10 11-1GA10 11-1HA10 11-1JA10 11-1KA10

24-1BB40

2921-1BA00 2 + 8US1251- 2 5DT10 2 2 2

3RA2120-1FD24-0BB4 3RA2120-1GD24-0BB4 3RA2120-1HD24-0BB4 3RA2120-1JD24-0BB4 3RA2120-1KD24-0BB4

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

7.5

15.5

10 ... 16

21-4AA10

26-1BB40

1

1 unit

41D

15.5 22 22 28 293)

13 ... 20 16 ... 22 18 ... 25 23 ... 28 27 ... 32

21-4BA10 21-4CA10 21-4DA10 21-4NA10 21-4EA10

27-1BB40

2921-1BA00 2 + 8US1251- 5 5NT10 2 2 2 2

3RA2120-4AD26-0BB4

7.5 11 11 15 15

3RA2120-4BD27-0BB4 3RA2120-4CD27-0BB4 3RA2120-4DD27-0BB4 3RA2120-4ND27-0BB4 3RA2120-4ED27-0BB4

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

15 18.5 18.5 22 22

29 35 35 41 41

22 ... 32 28 ... 36 32 ... 40 35 ... 45 42 ... 50

32-4EA10 32-4PA10 32-4UA10 32-4VA10 32-4WA10

35-1NB30

2931-1AA00 + 8US12616MT10

Size S2 is only available for self-assembly.

30 30 374)

55 55 66

49 ... 59 54 ... 65 62 ... 73

32-4XA10 32-4JA10 32-4KA10

36-1NB30 37-1NB30 38-1NB30

Type of coordination "1" at Iq = 150 kA at 400 V (motor starter protector is compatible with type of coordination "2") S00

For load feeders for lower outputs, see this table at type of coordination "2".

ToC

1

1.5 2.2 3

3.6 4.9 6.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8

11-1FA10 11-1GA10 11-1HA10

15-1BB41

1921-1DA00 2 + 8US1251- 2 5DS10 2

3RA2110-1FD15-1BB4 3RA2110-1GD15-1BB4 3RA2110-1HD15-1BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

4 5.5 7.5

8.5 11.5 15.5

7 ... 10 9 ... 12.5 10 ... 16

11-1JA10 11-1KA10 11-4AA10

16-1BB41 17-1BB41 18-1BB41

2 2 2

3RA2110-1JD16-1BB4 3RA2110-1KD17-1BB4 3RA2110-4AD18-1BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1)

For auxiliary switches, see "Accessories", page 8/44. The actual starting and rated data of the motor to be protected must be considered when selecting the units. 3) Suitable for use with IE3/IE4 motors up to a starting current of 256 A. For higher starting currents we recommend using size S2. 2)

* You can order this quantity or a multiple thereof. Illustrations are approximate

4)

Maximum permissible current setting at motor starter protector 65 A, as the maximum permissible current of the 3RA2931-1AA00 link module is 65 A.

Siemens IC 10 · 2022

8/31

8

S00

3RV20

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders 3RA21 direct-on-line starters > for 60 mm busbars Direct-on-line start

Rated control supply voltage 24 V DC With spring-loaded terminals

• With busbar adapter • The motor starter protector and contactor are mechanically and electrically connected by means of the link module. • Auxiliary switches1) on the motor starter protector and the contactor can be easily fitted thanks to the modular system. • Integrated auxiliary switches: Contactor size S00: 1 NO, Contactor size S0: 1 NO + 1 NC 3RA2110 Size

3RA2120 Standard three-phase motor 4-pole at 400 V AC2)

Adjustable current response value of the inversetime delayed overload Motor current I release (guide value)

Consisting of the following single devices

Standard output P

Motor starter protector

SD

+ Contactor + Link module + Busbar adapter

Fuseless load feeder

A

A

PS*

PG

Spring-loaded terminals

Article No. kW

PU (UNIT, SET, M)

Basic price per PU

d

Type of coordination "2" at Iq = 150 kA at 400 V (also compatible with type of coordination "1")

8

S00

S0

3RV20

3RT20

3RA29

15-2BB41

11-2AA00 + 8US12515DT11

0.06 0.06 0.09

0.2 0.2 0.3

0.14 ... 0.2 0.18 ... 0.25 0.22 ... 0.32

11-0BA20 11-0CA20 11-0DA20

0.09 0.12 0.18

0.3 0.4 0.6

0.28 ... 0.4 0.35 ... 0.5 0.45 ... 0.63

0.18 0.25 0.37

0.6 0.85 1.1

0.55 0.75 0.75

ToC

2

2 2 2

3RA2110-0BH15-1BB4 3RA2110-0CH15-1BB4 3RA2110-0DH15-1BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

11-0EA20 11-0FA20 11-0GA20

2 2 2

3RA2110-0EH15-1BB4 3RA2110-0FH15-1BB4 3RA2110-0GH15-1BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

0.55 ... 0.8 0.7 ... 1 0.9 ... 1.25

11-0HA20 11-0JA20 11-0KA20

2 2 2

3RA2110-0HH15-1BB4 3RA2110-0JH15-1BB4 3RA2110-0KH15-1BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1.5 1.9 1.9

1.1 ... 1.6 1.4 ... 2 1.8 ... 2.5

11-1AA20 11-1BA20 11-1CA20

2 2 2

3RA2110-1AH15-1BB4 3RA2110-1BH15-1BB4 3RA2110-1CH15-1BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1.1 1.5

2.7 3.6

2.2 ... 3.2 2.8 ... 4

11-1DA20 11-1EA20

2 2

3RA2110-1DH15-1BB4 3RA2110-1EH15-1BB4

1 1

1 unit 1 unit

41D 41D

1.5 2.2 3 4 5.5

3.6 4.9 6.5 8.5 11.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8 7 ... 10 9 ... 12.5

21-1FA20 21-1GA20 21-1HA20 21-1JA20 21-1KA20

24-2BB40

5 5 5 5 5

3RA2120-1FH24-0BB4 3RA2120-1GH24-0BB4 3RA2120-1HH24-0BB4 3RA2120-1JH24-0BB4 3RA2120-1KH24-0BB4

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

7.5

15.5

10 ... 16

21-4AA20

26-2BB40

2

3RA2120-4AH26-0BB4

1

1 unit

41D

7.5 11 11 15 15

15.5 22 22 28 293)

13 ... 20 16 ... 22 18 ... 25 23 ... 28 27 ... 32

21-4BA20 21-4CA20 21-4DA20 21-4NA20 21-4EA20

27-2BB40

5 2 2 2 2

3RA2120-4BH27-0BB4 3RA2120-4CH27-0BB4 3RA2120-4DH27-0BB4 3RA2120-4NH27-0BB4 3RA2120-4EH27-0BB4

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

21-2AA00 + 8US12515NT11

Type of coordination "1" at Iq = 150 kA at 400 V (motor starter protector is compatible with type of coordination "2") S00

For load feeders for lower outputs, see this table at type of coordination "2".

ToC

1

1.5 2.2 3

3.6 4.9 6.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8

11-1FA20 11-1GA20 11-1HA20

15-2BB41

4 5.5 7.5

8.5 11.5 15.5

7 ... 10 9 ... 12.5 10 ... 16

11-1JA20 11-1KA20 11-4AA20

16-2BB41 17-2BB41 18-2BB40

11-2AA00 + 8US12515DT11

2 2 2

3RA2110-1FH15-1BB4 3RA2110-1GH15-1BB4 3RA2110-1HH15-1BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

2 2 2

3RA2110-1JH16-1BB4 3RA2110-1KH17-1BB4 3RA2110-4AH18-1BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1)

For auxiliary switches, see "Accessories", page 8/44. The actual starting and rated data of the motor to be protected must be considered when selecting the units. 3) Suitable for use with IE3/IE4 motors up to a starting current of 256 A. For higher starting currents we recommend using size S2. 2)

8/32

Siemens IC 10 · 2022

* You can order this quantity or a multiple thereof. Illustrations are approximate

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders 3RA22 reversing starters > for standard mounting rail or for screw fixing

■ Selection and ordering data Reversing duty

3RA2210 Size

Rated control supply voltage 50/60 Hz 230 V AC for S00, 50 Hz 230 V AC for S0, S2 and S3 With screw terminals

• Screw fixing with two push-in lugs per load feeder possible1) • Without standard mounting rail adapter for size S00 • With 2 standard mounting rail adapters for size S0 for mechanical reinforcement (included in the scope of supply) • The motor starter protector and contactor are mechanically and electrically connected by means of the link module. • Auxiliary switches2) on the motor starter protector and the contactor can be easily fitted thanks to the modular system. • With contactor sizes S0, S2 and S3, an integrated NO contact is still available for free use.

3RA2220 Standard three-phase motor 4-pole at 400 V AC3)

Adjustable current response value of the inversetime delayed overload Motor current I release (guide value)

Consisting of the following single devices

Standard output P

Motor starter protector

+2 contactors

SD

+ Link module + Assembly kit RH4)/ Wiring kit

Fuseless load feeder

A

A

PS*

PG

Screw terminals

Article No. kW

PU (UNIT, SET, M)

d

Basic price per PU

Type of coordination "2" at Iq = 150 kA at 400 V (also compatible with type of coordination "1")

S0

S2

3RA

15-1AP02

1921-1DA00 2 + 2913-2AA1 2 2

3RA2210-0BA15-2AP0 3RA2210-0CA15-2AP0 3RA2210-0DA15-2AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

ToC

2

0.06 0.06 0.09

0.2 0.2 0.3

0.14 ... 0.2 0.18 ... 0.25 0.22 ... 0.32

11-0BA10 11-0CA10 11-0DA10

0.09 0.12 0.18

0.3 0.4 0.6

0.28 ... 0.4 0.35 ... 0.5 0.45 ... 0.63

11-0EA10 11-0FA10 11-0GA10

2 2 2

3RA2210-0EA15-2AP0 3RA2210-0FA15-2AP0 3RA2210-0GA15-2AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

0.18 0.25 0.37

0.6 0.85 1.1

0.55 ... 0.8 0.7 ... 1 0.9 ... 1.25

11-0HA10 11-0JA10 11-0KA10

2 2 2

3RA2210-0HA15-2AP0 3RA2210-0JA15-2AP0 3RA2210-0KA15-2AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

0.55 0.75 0.75

1.5 1.9 1.9

1.1 ... 1.6 1.4 ... 2 1.8 ... 2.5

11-1AA10 11-1BA10 11-1CA10

2 2 2

3RA2210-1AA15-2AP0 3RA2210-1BA15-2AP0 3RA2210-1CA15-2AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1.1 1.5

2.7 3.6

2.2 ... 3.2 2.8 ... 4

11-1DA10 11-1EA10

2 2

3RA2210-1DA15-2AP0 3RA2210-1EA15-2AP0

1 1

1 unit 1 unit

41D 41D

1.5 2.2 3 4 5.5

3.6 4.9 6.5 8.5 11.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8 7 ... 10 9 ... 12.5

11-1FA10 11-1GA10 11-1HA10 11-1JA10 11-1KA10

24-1AP00

2921-1AA00 2 + 2923-1BB1 2 2 2 2

3RA2220-1FB24-0AP0 3RA2220-1GB24-0AP0 3RA2220-1HB24-0AP0 3RA2220-1JB24-0AP0 3RA2220-1KB24-0AP0

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

7.5

15.5

10 ... 16

21-4AA10

26-1AP00

2

3RA2220-4AB26-0AP0

1

1 unit

41D

7.5 11 11 15 15

15.5 22 22 28 295)

13 ... 20 16 ... 22 18 ... 25 23 ... 28 27 ... 32

21-4BA10 21-4CA10 21-4DA10 21-4NA10 21-4EA10

27-1AP00

5 2 2 2 2

3RA2220-4BB27-0AP0 3RA2220-4CB27-0AP0 3RA2220-4DB27-0AP0 3RA2220-4NB27-0AP0 3RA2220-4EB27-0AP0

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

15 18.5 18.5 22 22

29 35 35 41 41

22 ... 32 28 ... 36 32 ... 40 35 ... 45 42 ... 50

32-4EA10 32-4PA10 32-4UA10 32-4VA10 32-4WA10

35-1AP00

30 30

55 55

49 ... 59 54 ... 65

32-4XA10 32-4JA10

37-1AP00

66

62 ... 73

32-4KA10

38-1AP00

6)

37 S3

3RT20

2931-1AA00 + 2933-1BB1

36-1AP00

Size S3 available on request

1)

For push-in lugs, see "Accessories", page 8/51. 2) For auxiliary switches, see "Accessories", page 8/44. 3) The actual starting and rated data of the motor to be protected must be considered when selecting the units. 4) RH = assembly kit for reversing duty and standard rail mounting in sizes S0 and S2.

* You can order this quantity or a multiple thereof. Illustrations are approximate

Size S2 is only available for self-assembly.

Size S3 is only available for self-assembly 5)

Suitable for use with IE3/IE4 motors up to a starting current of 256 A. For higher starting currents we recommend using size S2. 6) Maximum permissible current setting at motor starter protector 65 A, as the maximum permissible current of the 3RA2931-1AA00 link module is 65 A.

Siemens IC 10 · 2022

8/33

8

S00

3RV20

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders 3RA22 reversing starters > for standard mounting rail or for screw fixing Reversing duty

• Screw fixing with two push-in lugs per load feeder possible1) • Without standard mounting rail adapter for size S00 • The motor starter protector and contactor are mechanically and electrically connected by means of the link module. • Auxiliary switches2) on the motor starter protector and the contactor can be easily fitted thanks to the modular system.

3RA2210 Size

Rated control supply voltage 50/60 Hz 230 V AC for S00, 50 Hz 230 V AC for S0 With screw terminals

Standard three-phase motor 4-pole at 400 V AC3)

Adjustable current response value of the inversetime delayed overload Motor current I release (guide value)

Consisting of the following single devices

Standard output P

Motor starter protector

SD

+2 + Link contactors module + Assembly kit RH4)/ Wiring kit

Fuseless load feeder

A

A

PS*

PG

Screw terminals

Article No. kW

PU (UNIT, SET, M)

Basic price per PU

d

Type of coordination "1" at Iq = 150 kA at 400 V (motor starter protector is compatible with type of coordination "2") 3RV20

3RT20

3RA

ToC

1

8

S00

For load feeders for lower outputs, see table for type of coordination "2" on the previous page. 1.5 2.2 3

3.6 4.9 6.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8

11-1FA10 11-1GA10 11-1HA10

15-1AP02

1921-1DA00 2 + 2913-2AA1 2 2

3RA2210-1FA15-2AP0 3RA2210-1GA15-2AP0 3RA2210-1HA15-2AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

4 5.5 7.5

8.5 11.5 15.5

7 ... 10 9 ... 12.5 10 ... 16

11-1JA10 11-1KA10 11-4AA10

16-1AP02 17-1AP02 18-1AP02

2 2 2

3RA2210-1JA16-2AP0 3RA2210-1KA17-2AP0 3RA2210-4AA18-2AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1)

For push-in lugs, see "Accessories", page 8/51. For auxiliary switches, see "Accessories", page 8/44. 3) The actual starting and rated data of the motor to be protected must be considered when selecting the units. 4) RH = assembly kit for reversing duty and standard rail mounting in sizes S0 and S2. 2)

8/34

Siemens IC 10 · 2022

* You can order this quantity or a multiple thereof. Illustrations are approximate

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders 3RA22 reversing starters > for standard mounting rail or for screw fixing Reversing duty

3RA2210 Size

Rated control supply voltage 50/60 Hz 230 V AC for S00, 50 Hz 230 V AC for S0 With spring-loaded terminals

• Screw fixing with two push-in lugs per load feeder possible1) • Without standard mounting rail adapter for size S00 • With two standard mounting rail adapters for size S0 for mechanical reinforcement (included in the scope of supply) • The motor starter protector and contactor are mechanically and electrically connected by means of the link module. • Auxiliary switches2) on the motor starter protector and the contactor can be easily fitted thanks to the modular system. • With the contactor S0, an integrated NO contact is still available for free use.

3RA2220 Standard three-phase motor 4-pole at 400 V AC3)

Adjustable current response value of the inversetime delayed overload Motor current release I (guide value)

Consisting of the following single devices

Standard output P

Motor starter protector

SD

+2 + Link module contactors + Assembly kit RH4)/ Wiring kit

Fuseless load feeder

A

A

PS*

PG

Spring-loaded terminals

Article No. kW

PU (UNIT, SET, M)

d

Basic price per PU

Type of coordination "2" at Iq = 150 kA at 400 V (also compatible with type of coordination "1")

S0

3RT20

3RA29

15-2AP02

11-2AA00 + 2913-2AA2

0.06 0.06 0.09

0.2 0.2 0.3

0.14 ... 0.2 0.18 ... 0.25 0.22 ... 0.32

11-0BA20 11-0CA20 11-0DA20

0.09 0.12 0.18

0.3 0.4 0.6

0.28 ... 0.4 0.35 ... 0.5 0.45 ... 0.63

0.18 0.25 0.37

0.6 0.85 1.1

0.55 0.75 0.75

ToC

2

2 2 2

3RA2210-0BE15-2AP0 3RA2210-0CE15-2AP0 3RA2210-0DE15-2AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

11-0EA20 11-0FA20 11-0GA20

2 2 2

3RA2210-0EE15-2AP0 3RA2210-0FE15-2AP0 3RA2210-0GE15-2AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

0.55 ... 0.8 0.7 ... 1 0.9 ... 1.25

11-0HA20 11-0JA20 11-0KA20

2 2 2

3RA2210-0HE15-2AP0 3RA2210-0JE15-2AP0 3RA2210-0KE15-2AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1.5 1.9 1.9

1.1 ... 1.6 1.4 ... 2 1.8 ... 2.5

11-1AA20 11-1BA20 11-1CA20

2 2 2

3RA2210-1AE15-2AP0 3RA2210-1BE15-2AP0 3RA2210-1CE15-2AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1.1 1.5

2.7 3.6

2.2 ... 3.2 2.8 ... 4

11-1DA20 11-1EA20

2 2

3RA2210-1DE15-2AP0 3RA2210-1EE15-2AP0

1 1

1 unit 1 unit

41D 41D

1.5 2.2 3 4 5.5

3.6 4.9 6.5 8.5 11.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8 7 ... 10 9 ... 12.5

21-1FA20 21-1GA20 21-1HA20 21-1JA20 21-1KA20

24-2AP00

5 21-2AA00 + 2923-1BB25) 5 5 5 5

3RA2220-1FF24-0AP0 3RA2220-1GF24-0AP0 3RA2220-1HF24-0AP0 3RA2220-1JF24-0AP0 3RA2220-1KF24-0AP0

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

7.5

15.5

10 ... 16

21-4AA20

26-2AP00

2

3RA2220-4AF26-0AP0

1

1 unit

41D

7.5 11 11 15 15

15.5 22 22 28 296)

13 ... 20 16 ... 22 18 ... 25 23 ... 28 27 ... 32

21-4BA20 21-4CA20 21-4DA20 21-4NA20 21-4EA20

27-2AP00

5 2 2 2 2

3RA2220-4BF27-0AP0 3RA2220-4CF27-0AP0 3RA2220-4DF27-0AP0 3RA2220-4NF27-0AP0 3RA2220-4EF27-0AP0

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

Type of coordination "1" at Iq = 150 kA at 400 V (motor starter protector is compatible with type of coordination "2") S00

For load feeders for lower outputs, see this table at type of coordination "2". 1.5 2.2 3

3.6 4.9 6.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8

11-1FA20 11-1GA20 11-1HA20

15-2AP02

4 5.5 7.5

8.5 11.5 15.5

7 ... 10 9 ... 12.5 10 ... 16

11-1JA20 11-1KA20 11-4AA20

16-2AP02 17-2AP02 18-2AP02

1)

ToC

1

11-2AA00 + 2913-2AA2

For push-in lugs, see "Accessories", page 8/51. For auxiliary switches, see "Accessories", page 8/44. 3) The actual starting and rated data of the motor to be protected must be considered when selecting the units. 4) RH = assembly kit for reversing duty and standard rail mounting in size S0.

5)

2)

* You can order this quantity or a multiple thereof. Illustrations are approximate

6)

2 2 2

3RA2210-1FE15-2AP0 3RA2210-1GE15-2AP0 3RA2210-1HE15-2AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

2 2 2

3RA2210-1JE16-2AP0 3RA2210-1KE17-2AP0 3RA2210-4AE18-2AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

The RH assembly kit also includes the 3RA2911-1CA00 spacer for height compensation on AC contactors size S0 with spring-loaded terminals. Suitable for use with IE3/IE4 motors up to a starting current of 256 A. For higher starting currents we recommend using size S2.

Siemens IC 10 · 2022

8/35

8

S00

3RV20

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders 3RA22 reversing starters > for standard mounting rail or for screw fixing Reversing duty

3RA2210 Size

• Screw fixing with two push-in lugs per load feeder possible1) • Without standard mounting rail adapter for size S00 • With two standard mounting rail adapters for size S0 for mechanical reinforcement (included in the scope of supply) • The motor starter protector and contactor are mechanically and electrically connected by means of the link module. • Auxiliary switches2) on the motor starter protector and the contactor can be easily fitted thanks to the modular system. • With contactor sizes S0, S2 and S3, an integrated NO contact is still available for free use.

3RA2220 Standard three-phase motor 4-pole at 400 V AC3) Standard output P

Rated control supply voltage 24 V DC With screw terminals

Adjustable current response value of the inverse-time delayed Motor current I overload (guide release value)

Consisting of the following single devices Motor starter protector

+2 contactors

SD

+ Link module + Assembly kit RH4)/ Wiring kit

Fuseless load feeder

A

A

PS*

PG

Screw terminals

Article No. kW

PU (UNIT, SET, M)

Basic price per PU

d

Type of coordination "2" at Iq = 150 kA at 400 V (also compatible with type of coordination "1")

8

S00

S0

S2

S3 1) 2) 3) 4) 5) 6)

3RV20

3RT20

3RA

15-1BB42

1921-1DA00 + 2913-2AA1

0.06 0.06 0.09

0.2 0.2 0.3

0.14 ... 0.2 0.18 ... 0.25 0.22 ... 0.32

11-0BA10 11-0CA10 11-0DA10

0.09 0.12 0.18

0.3 0.4 0.6

0.28 ... 0.4 0.35 ... 0.5 0.45 ... 0.63

0.18 0.25 0.37

0.6 0.85 1.1

0.55 0.75 0.75

ToC

2

2 2 2

3RA2210-0BA15-2BB4 3RA2210-0CA15-2BB4 3RA2210-0DA15-2BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

11-0EA10 11-0FA10 11-0GA10

2 2 2

3RA2210-0EA15-2BB4 3RA2210-0FA15-2BB4 3RA2210-0GA15-2BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

0.55 ... 0.8 0.7 ... 1 0.9 ... 1.25

11-0HA10 11-0JA10 11-0KA10

2 2 2

3RA2210-0HA15-2BB4 3RA2210-0JA15-2BB4 3RA2210-0KA15-2BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1.5 1.9 1.9

1.1 ... 1.6 1.4 ... 2 1.8 ... 2.5

11-1AA10 11-1BA10 11-1CA10

2 2 2

3RA2210-1AA15-2BB4 3RA2210-1BA15-2BB4 3RA2210-1CA15-2BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1.1 1.5

2.7 3.6

2.2 ... 3.2 2.8 ... 4

11-1DA10 11-1EA10

2 2

3RA2210-1DA15-2BB4 3RA2210-1EA15-2BB4

1 1

1 unit 1 unit

41D 41D

1.5 2.2 3 4 5.5

3.6 4.9 6.5 8.5 11.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8 7 ... 10 9 ... 12.5

11-1FA10 11-1GA10 11-1HA10 11-1JA10 11-1KA10

24-1BB40

2 2 2 2 2

3RA2220-1FB24-0BB4 3RA2220-1GB24-0BB4 3RA2220-1HB24-0BB4 3RA2220-1JB24-0BB4 3RA2220-1KB24-0BB4

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

7.5

15.5

10 ... 16

21-4AA10

26-1BB40

2

3RA2220-4AB26-0BB4

1

1 unit

41D

7.5 11 11 15 15

15.5 22 22 28 295)

13 ... 20 16 ... 22 18 ... 25 23 ... 28 27 ... 32

21-4BA10 21-4CA10 21-4DA10 21-4NA10 21-4EA10

27-1BB40

5 2 2 2 2

3RA2220-4BB27-0BB4 3RA2220-4CB27-0BB4 3RA2220-4DB27-0BB4 3RA2220-4NB27-0BB4 3RA2220-4EB27-0BB4

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

15

29 35 35 41 41

22 ... 32 28 ... 36 32 ... 40 35 ... 45 42 ... 50

32-4EA10 32-4PA10 32-4UA10 32-4VA10 32-4WA10

35-1NB30

18.5 18.5 22 22 30 30 376)

55 55 66

49 ... 59 54 ... 65 62 ... 73

32-4XA10 32-4JA10 32-4KA10

2921-1BA00 + 2923-1BB1

2931-1AA00 + 2933-1BB1

Size S2 is only available for self-assembly.

36-1NB30 37-1NB30 38-1NB30

Size S3 available on request

Size S3 is only available for self-assembly.

For push-in lugs, see "Accessories", page 8/51. For auxiliary switches, see "Accessories", page 8/44. The actual starting and rated data of the motor to be protected must be considered when selecting the units. RH = assembly kit for reversing duty and standard rail mounting in sizes S0 and S2. Suitable for use with IE3/IE4 motors up to a starting current of 256 A. For higher starting currents we recommend using size S2. Maximum permissible current setting at motor starter protector 65 A, as the maximum permissible current of the 3RA2931-1AA00 link module is 65 A.

8/36

Siemens IC 10 · 2022

* You can order this quantity or a multiple thereof. Illustrations are approximate

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders 3RA22 reversing starters > for standard mounting rail or for screw fixing Reversing duty

Rated control supply voltage 24 V DC With screw terminals

• Screw fixing with two push-in lugs per load feeder possible1) • Without standard mounting rail adapter for size S00 • The motor starter protector and contactor are mechanically and electrically connected by means of the link module. • Auxiliary switches2) on the motor starter protector and the contactor can be easily fitted thanks to the modular system.

3RA2210 Size

Standard three-phase motor 4-pole at 400 V AC3) Standard output P

Adjustable current response value of the inverse-time delayed Motor current I overload (guide release value)

Consisting of the following single devices Motor starter protector

+2 contactors

SD

Fuseless load feeder

A

PS*

PG

+ Link module + Wiring kit Screw terminals

Article No. kW

PU (UNIT, SET, M)

A

d

Basic price per PU

Type of coordination "1" at Iq = 150 kA at 400 V (motor starter protector is compatible with type of coordination "2") 3RV20

3RT20

3RA

ToC

1

For load feeders for lower outputs, see table for type of coordination "2" on the previous page. 1.5 2.2 3

3.6 4.9 6.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8

11-1FA10 11-1GA10 11-1HA10

15-1BB42

4 5.5 7.5

8.5 11.5 15.5

7 ... 10 9 ... 12.5 10 ... 16

11-1JA10 11-1KA10 11-4AA10

16-1BB42 17-1BB42 18-1BB42

1921-1DA00 + 2913-2AA1

2 2 2

3RA2210-1FA15-2BB4 3RA2210-1GA15-2BB4 3RA2210-1HA15-2BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

2 2 2

3RA2210-1JA16-2BB4 3RA2210-1KA17-2BB4 3RA2210-4AA18-2BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1)

For push-in lugs, see "Accessories", page 8/51. For auxiliary switches, see "Accessories", page 8/44. 3) The actual starting and rated data of the motor to be protected must be considered when selecting the units. 2)

* You can order this quantity or a multiple thereof. Illustrations are approximate

Siemens IC 10 · 2022

8/37

8

S00

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders 3RA22 reversing starters > for standard mounting rail or for screw fixing Reversing duty

3RA2210 Size

• Screw fixing with two push-in lugs per load feeder possible1) • Without standard mounting rail adapter for size S00 • With two standard mounting rail adapters for size S0 for mechanical reinforcement (included in the scope of supply) • The motor starter protector and contactor are mechanically and electrically connected by means of the link module. • Auxiliary switches2) on the motor starter protector and the contactor can be easily fitted thanks to the modular system. • With the contactor S0, an integrated NO contact is still available for free use.

3RA2220 Adjustable current response value of the inverse-time Motor delayed current overload I (guide release value)

Rated control supply voltage 24 V DC With spring-loaded terminals

Standard three-phase motor 4-pole at 400 V AC3)

Consisting of the following single devices

Standard output P

Motor starter protector

+2 contactors

SD

+ Link module + Assembly kit RH4)/ Wiring kit

Fuseless load feeder

A

A

PS*

PG

Spring-loaded terminals

Article No. kW

PU (UNIT, SET, M)

Basic price per PU

d

Type of coordination "2" at Iq = 150 kA at 400 V (also compatible with type of coordination "1")

8

S00

S0

3RV20

3RT20

3RA29

15-2BB42

11-2AA00 + 2913-2AA2

0.06 0.06 0.09

0.2 0.2 0.3

0.14 ... 0.2 0.18 ... 0.25 0.22 ... 0.32

11-0BA20 11-0CA20 11-0DA20

0.09 0.12 0.18

0.3 0.4 0.6

0.28 ... 0.4 0.35 ... 0.5 0.45 ... 0.63

0.18 0.25 0.37

0.6 0.85 1.1

0.55 0.75 0.75

ToC

2

2 2 2

3RA2210-0BE15-2BB4 3RA2210-0CE15-2BB4 3RA2210-0DE15-2BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

11-0EA20 11-0FA20 11-0GA20

2 2 2

3RA2210-0EE15-2BB4 3RA2210-0FE15-2BB4 3RA2210-0GE15-2BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

0.55 ... 0.8 0.7 ... 1 0.9 ... 1.25

11-0HA20 11-0JA20 11-0KA20

2 2 2

3RA2210-0HE15-2BB4 3RA2210-0JE15-2BB4 3RA2210-0KE15-2BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1.5 1.9 1.9

1.1 ... 1.6 1.4 ... 2 1.8 ... 2.5

11-1AA20 11-1BA20 11-1CA20

2 2 2

3RA2210-1AE15-2BB4 3RA2210-1BE15-2BB4 3RA2210-1CE15-2BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1.1 1.5

2.7 3.6

2.2 ... 3.2 2.8 ... 4

11-1DA20 11-1EA20

2 2

3RA2210-1DE15-2BB4 3RA2210-1EE15-2BB4

1 1

1 unit 1 unit

41D 41D

1.5 2.2 3 4 5.5

3.6 4.9 6.5 8.5 11.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8 7 ... 10 9 ... 12.5

21-1FA20 21-1GA20 21-1HA20 21-1JA20 21-1KA20

24-2BB40

5 5 5 5 5

3RA2220-1FF24-0BB4 3RA2220-1GF24-0BB4 3RA2220-1HF24-0BB4 3RA2220-1JF24-0BB4 3RA2220-1KF24-0BB4

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

7.5

15.5

10 ... 16

21-4AA20

26-2BB40

2

3RA2220-4AF26-0BB4

1

1 unit

41D

7.5 11 11 15 15

15.5 22 22 28 295)

13 ... 20 16 ... 22 18 ... 25 23 ... 28 27 ... 32

21-4BA20 21-4CA20 21-4DA20 21-4NA20 21-4EA20

27-2BB40

5 2 2 2 2

3RA2220-4BF27-0BB4 3RA2220-4CF27-0BB4 3RA2220-4DF27-0BB4 3RA2220-4NF27-0BB4 3RA2220-4EF27-0BB4

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

21-2AA00 + 2923-1BB2

Type of coordination "1" at Iq = 150 kA at 400 V (motor starter protector is compatible with type of coordination "2") S00

For load feeders for lower outputs, see this table at type of coordination "2". 1.5 2.2 3

3.6 4.9 6.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8

11-1FA20 11-1GA20 11-1HA20

15-2BB42

4 5.5 7.5

8.5 11.5 15.5

7 ... 10 9 ... 12.5 10 ... 16

11-1JA20 11-1KA20 11-4AA20

16-2BB42 17-2BB42 18-2BB42

ToC

1

11-2AA00 + 2913-2AA2

2 2 2

3RA2210-1FE15-2BB4 3RA2210-1GE15-2BB4 3RA2210-1HE15-2BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

2 2 2

3RA2210-1JE16-2BB4 3RA2210-1KE17-2BB4 3RA2210-4AE18-2BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1)

For push-in lugs, see "Accessories", page 8/51. For auxiliary switches, see "Accessories", page 8/44. 3) The actual starting and rated data of the motor to be protected must be considered when selecting the units. 4) RH = assembly kit for reversing duty and standard rail mounting in size S0. 5) Suitable for use with IE3/IE4 motors up to a starting current of 256 A. For higher starting currents we recommend using size S2. 2)

8/38

Siemens IC 10 · 2022

* You can order this quantity or a multiple thereof. Illustrations are approximate

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders 3RA22 reversing starters > for 60 mm busbars

■ Selection and ordering data Reversing duty

Rated control supply voltage 50/60 Hz 230 V AC for S00, 50 Hz 230 V AC for S0 and S2 With screw terminals

• With busbar adapter and device holder (included in the scope of supply) • The motor starter protector and contactor are mechanically and electrically connected by means of the link module. • Auxiliary switches1) on the motor starter protector and the contactor can be easily fitted thanks to the modular system. • With contactor sizes S0 and S2, an integrated NO contact is still available for free use. 3RA2210 Size

3RA2220 Standard three-phase motor 4-pole at 400 V AC2)

Adjustable current response value of the inversetime delayed overload Motor current I release (guide value)

Consisting of the following single devices

Standard output P

Motor starter protector

+2 contactors

SD

+ Link module + Assembly kit RS3)/ Wiring kit

Fuseless load feeder

A

A

PS*

PG

Screw terminals

Article No. kW

PU (UNIT, SET, M)

d

Basic price per PU

Type of coordination "2" at Iq = 150 kA at 400 V (also compatible with type of coordination "1")

S0

S2

3RT20

3RA

15-1AP02

1921-1DA00 2 + 2913-1DB1 2 2

3RA2210-0BD15-2AP0 3RA2210-0CD15-2AP0 3RA2210-0DD15-2AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

ToC

2

0.06 0.06 0.09

0.2 0.2 0.3

0.14 ... 0.2 0.18 ... 0.25 0.22 ... 0.32

11-0BA10 11-0CA10 11-0DA10

0.09 0.12 0.18

0.3 0.4 0.6

0.28 ... 0.4 0.35 ... 0.5 0.45 ... 0.63

11-0EA10 11-0FA10 11-0GA10

2 2 2

3RA2210-0ED15-2AP0 3RA2210-0FD15-2AP0 3RA2210-0GD15-2AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

0.18 0.25 0.37

0.6 0.85 1.1

0.55 ... 0.8 0.7 ... 1 0.9 ... 1.25

11-0HA10 11-0JA10 11-0KA10

2 2 2

3RA2210-0HD15-2AP0 3RA2210-0JD15-2AP0 3RA2210-0KD15-2AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

0.55 0.75 0.75

1.5 1.9 1.9

1.1 ... 1.6 1.4 ... 2 1.8 ... 2.5

11-1AA10 11-1BA10 11-1CA10

2 2 2

3RA2210-1AD15-2AP0 3RA2210-1BD15-2AP0 3RA2210-1CD15-2AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1.1 1.5

2.7 3.6

2.2 ... 3.2 2.8 ... 4

11-1DA10 11-1EA10

2 2

3RA2210-1DD15-2AP0 3RA2210-1ED15-2AP0

1 1

1 unit 1 unit

41D 41D

1.5 2.2 3 4 5.5

3.6 4.9 6.5 8.5 11.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8 7 ... 10 9 ... 12.5

11-1FA10 11-1GA10 11-1HA10 11-1JA10 11-1KA10

24-1AP00

2921-1AA00 2 + 2923-1DB1 2 2 2 2

3RA2220-1FD24-0AP0 3RA2220-1GD24-0AP0 3RA2220-1HD24-0AP0 3RA2220-1JD24-0AP0 3RA2220-1KD24-0AP0

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

7.5

15.5

10 ... 16

21-4AA10

26-1AP00

2

3RA2220-4AD26-0AP0

1

1 unit

41D

7.5 11 11 15 15

15.5 22 22 28 294)

13 ... 20 16 ... 22 18 ... 25 23 ... 28 27 ... 32

21-4BA10 21-4CA10 21-4DA10 21-4NA10 21-4EA10

27-1AP00

5 2 2 2 2

3RA2220-4BD27-0AP0 3RA2220-4CD27-0AP0 3RA2220-4DD27-0AP0 3RA2220-4ND27-0AP0 3RA2220-4ED27-0AP0

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

15 18.5 18.5 22 22

29 35 35 41 41

22 ... 32 28 ... 36 32 ... 40 35 ... 45 42 ... 50

32-4EA10 32-4PA10 32-4UA10 32-4VA10 32-4WA10

35-1AP00

30 30

55 55

49 ... 59 54 ... 65

32-4XA10 32-4JA10

37-1AP00

375)

66

62 ... 73

32-4KA10

38-1AP00

2931-1AA00 + 2933-1DB1

Size S2 is only available for self-assembly.

36-1AP00

1)

For auxiliary switches, see "Accessories", page 8/44. The actual starting and rated data of the motor to be protected must be considered when selecting the units. 3) RS = assembly kit for reversing duty and busbar mounting. 4) Suitable for use with IE3/IE4 motors up to a starting current of 256 A. For higher starting currents we recommend using size S2. 5) Maximum permissible current setting at motor starter protector 65 A, as the maximum permissible current of the 3RA2931-1AA00 link module is 65 A. 2)

* You can order this quantity or a multiple thereof. Illustrations are approximate

Siemens IC 10 · 2022

8/39

8

S00

3RV20

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders 3RA22 reversing starters > for 60 mm busbars .

Reversing duty

Rated control supply voltage 50/60 Hz 230 V AC for S00 With screw terminals

• With busbar adapter and device holder (included in the scope of supply) • The motor starter protector and contactor are mechanically and electrically connected by means of the link module. • Auxiliary switches1) on the motor starter protector and the contactor can be easily fitted thanks to the modular system.

3RA2210 Size

Standard three-phase motor 4-pole at 400 V AC2)

Adjustable current response value of the inversetime delayed overload Motor current I release (guide value)

Consisting of the following single devices

Standard output P

Motor starter protector

+2 contactors

SD

+ Link module + Assembly kit RS3)/ Wiring kit

Fuseless load feeder

A

A

PS*

PG

Screw terminals

Article No. kW

PU (UNIT, SET, M)

Basic price per PU

d

Type of coordination "1" at Iq = 150 kA at 400 V (motor starter protector is compatible with type of coordination "2") 3RV20

3RT20

3RA

ToC

1

8

S00

For load feeders for lower outputs, see table for type of coordination "2" on the previous page. 1.5 2.2 3

3.6 4.9 6.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8

11-1FA10 11-1GA10 11-1HA10

15-1AP02

1921-1DA00 2 + 2913-1DB1 2 2

3RA2210-1FD15-2AP0 3RA2210-1GD15-2AP0 3RA2210-1HD15-2AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

4 5.5 7.5

8.5 11.5 15.5

7 ... 10 9 ... 12.5 10 ... 16

11-1JA10 11-1KA10 11-4AA10

16-1AP02 17-1AP02 18-1AP02

2 2 2

3RA2210-1JD16-2AP0 3RA2210-1KD17-2AP0 3RA2210-4AD18-2AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1)

For auxiliary switches, see "Accessories", page 8/44. The actual starting and rated data of the motor to be protected must be considered when selecting the units. 3) RS = assembly kit for reversing duty and busbar mounting. 2)

8/40

Siemens IC 10 · 2022

* You can order this quantity or a multiple thereof. Illustrations are approximate

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders 3RA22 reversing starters > for 60 mm busbars Reversing duty

Rated control supply voltage 50/60 Hz 230 V AC for S00, 50 Hz 230 V AC for S0 With spring-loaded terminals

• With busbar adapter and device holder (included in the scope of supply) • The motor starter protector and contactor are mechanically and electrically connected by means of the link module. • Auxiliary switches1) on the motor starter protector and the contactor can be easily fitted thanks to the modular system. • With the contactor S0, an integrated NO contact is still available for free use. 3RA2210 Size

3RA2220 Standard three-phase motor 4-pole at 400 V AC2)

Adjustable current response value of the inversetime delayed overload Motor current release I (guide value)

Consisting of the following single devices

Standard output P

Motor starter protector

+2 contactors

SD

+ Link module + Assembly kit RS3)/ Wiring kit

Fuseless load feeder

A

A

PS*

PG

Spring-loaded terminals

Article No. kW

PU (UNIT, SET, M)

d

Basic price per PU

Type of coordination "2" at Iq = 150 kA at 400 V (also compatible with type of coordination "1")

S0

3RT20

3RA29

15-2AP02

11-2AA00 + 13-1DB2

0.06 0.06 0.09

0.2 0.2 0.3

0.14 ... 0.2 0.18 ... 0.25 0.22 ... 0.32

11-0BA20 11-0CA20 11-0DA20

0.09 0.12 0.18

0.3 0.4 0.6

0.28 ... 0.4 0.35 ... 0.5 0.45 ... 0.63

0.18 0.25 0.37

0.6 0.85 1.1

0.55 0.75 0.75

ToC

2

2 2 2

3RA2210-0BH15-2AP0 3RA2210-0CH15-2AP0 3RA2210-0DH15-2AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

11-0EA20 11-0FA20 11-0GA20

2 2 2

3RA2210-0EH15-2AP0 3RA2210-0FH15-2AP0 3RA2210-0GH15-2AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

0.55 ... 0.8 0.7 ... 1 0.9 ... 1.25

11-0HA20 11-0JA20 11-0KA20

2 2 2

3RA2210-0HH15-2AP0 3RA2210-0JH15-2AP0 3RA2210-0KH15-2AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1.5 1.9 1.9

1.1 ... 1.6 1.4 ... 2 1.8 ... 2.5

11-1AA20 11-1BA20 11-1CA20

2 2 2

3RA2210-1AH15-2AP0 3RA2210-1BH15-2AP0 3RA2210-1CH15-2AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1.1 1.5

2.7 3.6

2.2 ... 3.2 2.8 ... 4

11-1DA20 11-1EA20

2 2

3RA2210-1DH15-2AP0 3RA2210-1EH15-2AP0

1 1

1 unit 1 unit

41D 41D

1.5 2.2 3 4 5.5

3.6 4.9 6.5 8.5 11.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8 7 ... 10 9 ... 12.5

21-1FA20 21-1GA20 21-1HA20 21-1JA20 21-1KA20

24-2AP00

5 5 5 5 5

3RA2220-1FH24-0AP0 3RA2220-1GH24-0AP0 3RA2220-1HH24-0AP0 3RA2220-1JH24-0AP0 3RA2220-1KH24-0AP0

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

7.5

15.5

10 ... 16

21-4AA20

26-2AP00

2

3RA2220-4AH26-0AP0

1

1 unit

41D

7.5 11 11 15 15

15.5 22 22 28 295)

13 ... 20 16 ... 22 18 ... 25 23 ... 28 27 ... 32

21-4BA20 21-4CA20 21-4DA20 21-4NA20 21-4EA20

27-2AP00

5 2 2 2 2

3RA2220-4BH27-0AP0 3RA2220-4CH27-0AP0 3RA2220-4DH27-0AP0 3RA2220-4NH27-0AP0 3RA2220-4EH27-0AP0

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

21-2AA00 + 23-1DB24)

Type of coordination "1" at Iq = 150 kA at 400 V (motor starter protector is compatible with type of coordination "2") S00

For load feeders for lower outputs, see this table at type of coordination "2". 1.5 2.2 3

3.6 4.9 6.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8

11-1FA20 11-1GA20 11-1HA20

15-2AP02

4 5.5 7.5

8.5 11.5 15.5

7 ... 10 9 ... 12.5 10 ... 16

11-1JA20 11-1KA20 11-4AA20

16-2AP02 17-2AP02 18-2AP02

1)

ToC

1

11-2AA00 + 13-1DB2

For auxiliary switches, see "Accessories", page 8/44. The actual starting and rated data of the motor to be protected must be considered when selecting the units. 3) RS = assembly kit for reversing duty and busbar mounting.

4)

2)

* You can order this quantity or a multiple thereof. Illustrations are approximate

5)

2 2 2

3RA2210-1FH15-2AP0 3RA2210-1GH15-2AP0 3RA2210-1HH15-2AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

2 2 2

3RA2210-1JH16-2AP0 3RA2210-1KH17-2AP0 3RA2210-4AH18-2AP0

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

The RS assembly kit also includes the 3RA2911-1CA00 spacer for height compensation on AC contactors size S0 with spring-loaded terminals. Suitable for use with IE3/IE4 motors up to a starting current of 256 A. For higher starting currents we recommend using size S2.

Siemens IC 10 · 2022

8/41

8

S00

3RV20

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders 3RA22 reversing starters > for 60 mm busbars Reversing duty

Rated control supply voltage 24 V DC With screw terminals

• With busbar adapter and device holder (included in the scope of supply) • The motor starter protector and contactor are mechanically and electrically connected by means of the link module. • Auxiliary switches1) on the motor starter protector and the contactor can be easily fitted thanks to the modular system. • With contactor sizes S0 and S2, an integrated NO contact is still available for free use. 3RA2210 Size

3RA2220 Standard three-phase motor 4-pole at 400 V AC2) Standard output P

Adjustable current response value of the inversetime delayed overload Motor current I release (guide value)

SD

Consisting of the following single devices Motor starter protector

+2 contactors

+ Link module + Assembly kit RS3)/ Wiring kit

Fuseless load feeder

A

A

PS*

PG

Screw terminals

Article No. kW

PU (UNIT, SET, M)

Basic price per PU

d

Type of coordination "2" at Iq = 150 kA at 400 V (also compatible with type of coordination "1")

8

S00

S0

S2

3RV20

3RT20

3RA

15-1BB42

1921-1DA00 2 + 2913-1DB1 2 2

3RA2210-0BD15-2BB4 3RA2210-0CD15-2BB4 3RA2210-0DD15-2BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

ToC

2

0.06 0.06 0.09

0.2 0.2 0.3

0.14 ... 0.2 0.18 ... 0.25 0.22 ... 0.32

11-0BA10 11-0CA10 11-0DA10

0.09 0.12 0.18

0.3 0.4 0.6

0.28 ... 0.4 0.35 ... 0.5 0.45 ... 0.63

11-0EA10 11-0FA10 11-0GA10

2 2 2

3RA2210-0ED15-2BB4 3RA2210-0FD15-2BB4 3RA2210-0GD15-2BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

0.18 0.25 0.37

0.6 0.85 1.1

0.55 ... 0.8 0.7 ... 1 0.9 ... 1.25

11-0HA10 11-0JA10 11-0KA10

2 2 2

3RA2210-0HD15-2BB4 3RA2210-0JD15-2BB4 3RA2210-0KD15-2BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

0.55 0.75 0.75

1.5 1.9 1.9

1.1 ... 1.6 1.4 ... 2 1.8 ... 2.5

11-1AA10 11-1BA10 11-1CA10

2 2 2

3RA2210-1AD15-2BB4 3RA2210-1BD15-2BB4 3RA2210-1CD15-2BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1.1 1.5

2.7 3.6

2.2 ... 3.2 2.8 ... 4

11-1DA10 11-1EA10

2 2

3RA2210-1DD15-2BB4 3RA2210-1ED15-2BB4

1 1

1 unit 1 unit

41D 41D

1.5 2.2 3 4 5.5

3.6 4.9 6.5 8.5 11.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8 7 ... 10 9 ... 12.5

11-1FA10 11-1GA10 11-1HA10 11-1JA10 11-1KA10

24-1BB40

2921-1BA00 2 + 2923-1DB1 2 2 2 2

3RA2220-1FD24-0BB4 3RA2220-1GD24-0BB4 3RA2220-1HD24-0BB4 3RA2220-1JD24-0BB4 3RA2220-1KD24-0BB4

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

7.5

15.5

10 ... 16

21-4AA10

26-1BB40

2

3RA2220-4AD26-0BB4

1

1 unit

41D

7.5 11 11 15 15

15.5 22 22 28 294)

13 ... 20 16 ... 22 18 ... 25 23 ... 28 27 ... 32

21-4BA10 21-4CA10 21-4DA10 21-4NA10 21-4EA10

27-1BB40

5 2 2 2 2

3RA2220-4BD27-0BB4 3RA2220-4CD27-0BB4 3RA2220-4DD27-0BB4 3RA2220-4ND27-0BB4 3RA2220-4ED27-0BB4

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

15 18.5 18.5 22 22

29 35 35 41 41

22 ... 32 28 ... 36 32 ... 40 35 ... 45 42 ... 50

32-4EA10 32-4PA10 32-4UA10 32-4VA10 32-4WA10

35-1NB30

30 30 375)

55 55 66

49 ... 59 54 ... 65 62 ... 73

32-4XA10 32-4JA10 32-4KA10

2931-1AA00 + 2933-1DB1

Size S2 is only available for self-assembly.

36-1NB30 37-1NB30 38-1NB30

Type of coordination "1" at Iq = 150 kA at 400 V (motor starter protector is compatible with type of coordination "2") S00

For load feeders for lower outputs, see this table at type of coordination "2".

ToC

1

1.5 2.2 3

3.6 4.9 6.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8

11-1FA10 11-1GA10 11-1HA10

15-1BB42

1921-1DA00 2 + 2913-1DB1 2 2

3RA2210-1FD15-2BB4 3RA2210-1GD15-2BB4 3RA2210-1HD15-2BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

4 5.5 7.5

8.5 11.5 15.5

7 ... 10 9 ... 12.5 10 ... 16

11-1JA10 11-1KA10 11-4AA10

16-1BB42 17-1BB42 18-1BB42

2 2 2

3RA2210-1JD16-2BB4 3RA2210-1KD17-2BB4 3RA2210-4AD18-2BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1)

For auxiliary switches, see "Accessories", page 8/44. The actual starting and rated data of the motor to be protected must be considered when selecting the units. 3) RS = assembly kit for reversing duty and busbar mounting.

4)

2)

8/42

Siemens IC 10 · 2022

5)

Suitable for use with IE3/IE4 motors up to a starting current of 256 A. For higher starting currents we recommend using size S2. Maximum permissible current setting at motor starter protector 65 A, as the maximum permissible current of the 3RA2931-1AA00 link module is 65 A.

* You can order this quantity or a multiple thereof. Illustrations are approximate

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders 3RA22 reversing starters > for 60 mm busbars Reversing duty

Rated control supply voltage 24 V DC With spring-loaded terminals

• With busbar adapter and device holder (included in the scope of supply) • The motor starter protector and contactor are mechanically and electrically connected by means of the link module. • Auxiliary switches1) on the motor starter protector and the contactor can be easily fitted thanks to the modular system. • With the contactor S0, an integrated NO contact is still available for free use. 3RA2210 Size

3RA2220 Standard three-phase motor 4-pole at 400 V AC2)

Adjustable current response value of the inversetime delayed overload Motor current release I (guide value)

Consisting of the following single devices

Standard output P

Motor starter protector

SD

+2 + Link module contactors + Assembly kit RS3)/ Wiring kit

Fuseless load feeder

A

A

PS*

PG

Spring-loaded terminals

Article No. kW

PU (UNIT, SET, M)

d

Basic price per PU

Type of coordination "2" at Iq = 150 kA at 400 V (also compatible with type of coordination "1")

S0

3RT20

3RA29

15-2BB42

11-2AA00 + 13-1DB2

0.06 0.06 0.09

0.2 0.2 0.3

0.14 ... 0.2 0.18 ... 0.25 0.22 ... 0.32

11-0BA20 11-0CA20 11-0DA20

0.09 0.12 0.18

0.3 0.4 0.6

0.28 ... 0.4 0.35 ... 0.5 0.45 ... 0.63

0.18 0.25 0.37

0.6 0.85 1.1

0.55 0.75 0.75

ToC

2

2 2 2

3RA2210-0BH15-2BB4 3RA2210-0CH15-2BB4 3RA2210-0DH15-2BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

11-0EA20 11-0FA20 11-0GA20

2 2 2

3RA2210-0EH15-2BB4 3RA2210-0FH15-2BB4 3RA2210-0GH15-2BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

0.55 ... 0.8 0.7 ... 1 0.9 ... 1.25

11-0HA20 11-0JA20 11-0KA20

2 2 2

3RA2210-0HH15-2BB4 3RA2210-0JH15-2BB4 3RA2210-0KH15-2BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1.5 1.9 1.9

1.1 ... 1.6 1.4 ... 2 1.8 ... 2.5

11-1AA20 11-1BA20 11-1CA20

2 2 2

3RA2210-1AH15-2BB4 3RA2210-1BH15-2BB4 3RA2210-1CH15-2BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

1.1 1.5

2.7 3.6

2.2 ... 3.2 2.8 ... 4

11-1DA20 11-1EA20

2 2

3RA2210-1DH15-2BB4 3RA2210-1EH15-2BB4

1 1

1 unit 1 unit

41D 41D

1.5 2.2 3 4 5.5

3.6 4.9 6.5 8.5 11.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8 7 ... 10 9 ... 12.5

21-1FA20 21-1GA20 21-1HA20 21-1JA20 21-1KA20

24-2BB40

5 5 5 5 5

3RA2220-1FH24-0BB4 3RA2220-1GH24-0BB4 3RA2220-1HH24-0BB4 3RA2220-1JH24-0BB4 3RA2220-1KH24-0BB4

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

7.5

15.5

10 ... 16

21-4AA20

26-2BB40

2

3RA2220-4AH26-0BB4

1

1 unit

41D

7.5 11 11 15 15

15.5 22 22 28 294)

13 ... 20 16 ... 22 18 ... 25 23 ... 28 27 ... 32

21-4BA20 21-4CA20 21-4DA20 21-4NA20 21-4EA20

27-2BB40

5 2 2 2 2

3RA2220-4BH27-0BB4 3RA2220-4CH27-0BB4 3RA2220-4DH27-0BB4 3RA2220-4NH27-0BB4 3RA2220-4EH27-0BB4

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41D 41D 41D 41D 41D

21-2AA00 + 23-1DB2

Type of coordination "1" at Iq = 150 kA at 400 V (motor starter protector is compatible with type of coordination "2") S00

1) 2)

For load feeders for lower outputs, see this table at type of coordination "2". 1.5 2.2 3

3.6 4.9 6.5

3.5 ... 5 4.5 ... 6.3 5.5 ... 8

11-1FA20 11-1GA20 11-1HA20

15-2BB42

4 5.5 7.5

8.5 11.5 15.5

7 ... 10 9 ... 12.5 10 ... 16

11-1JA20 11-1KA20 11-4AA20

16-2BB42 17-2BB42 18-2BB42

ToC

1

11-2AA00 + 13-1DB2

For auxiliary switches, see "Accessories", page 8/44. The actual starting and rated data of the motor to be protected must be considered when selecting the units.

* You can order this quantity or a multiple thereof. Illustrations are approximate

3) 4)

2 2 2

3RA2210-1FH15-2BB4 3RA2210-1GH15-2BB4 3RA2210-1HH15-2BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

2 2 2

3RA2210-1JH16-2BB4 3RA2210-1KH17-2BB4 3RA2210-4AH18-2BB4

1 1 1

1 unit 1 unit 1 unit

41D 41D 41D

RS = assembly kit for reversing duty and busbar mounting. Suitable for use with IE3/IE4 motors up to a starting current of 256 A. For higher starting currents we recommend using size S2.

Siemens IC 10 · 2022

8/43

8

S00

3RV20

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders Accessories

■ Overview The accessories listed here are parts and add-ons for the 3RA2 direct-on-line and reversing starters as well as

components for the customer assembly of fuseless load feeders.

■ Selection and ordering data Accessories for motor starter protectors PU (UNIT, SET, M) = 1 PS* = 1 unit PG = 41E

3RV2901-1E

3RV2901-2E

Version

3RV2901-1A For motor starter protectors

3RV2901-2A SD

SD

Screw terminals

Article No.

Price per PU

Spring-loaded terminals Article No.

Price per PU

d

Size

d

S00 ... S3

} } }

3RV2901-1D 3RV2901-1E 3RV2901-1F

} }

-3RV2901-2E 3RV2901-2F

}

3RV2901-1A

}

3RV2901-2A

Auxiliary switches1) Transverse auxiliary switches For front mounting

8

1 CO 1 NO + 1 NC 2 NO Lateral auxiliary switches For mounting on the left 1 NO + 1 NC 1)

S00 ... S3

Each motor starter protector can be fitted with one transverse and one lateral auxiliary switch. The lateral auxiliary switches 2 NO + 2 NC are used without transverse auxiliary switches.

PU (UNIT, SET, M) = 1 PS* = 1 unit PG = 41E

3RV2902-1A..

3RV2902-2A..

Rated control supply voltage Us

AC 50 Hz

AC 60 Hz

AC 50/60 Hz 100% ON period1)

V

V

V

For motor starter protectors

SD

AC/DC 50/60 Hz, DC 5 s ON period2) V

Article No.

Size

SD

Screw terminals

d

Price per PU

Spring-loaded terminals

Article No.

Price per PU

d

Auxiliary releases for motor starter protectors3) Undervoltage releases 230

240

Shunt release ---

--

--

S00 ... S3

210 ... 240

190 ... 330

S00 ... S3

1)

The voltage range is valid for 100% (infinite) ON period. The response voltage lies at 0.9 of the lower limit of the voltage range. 2) The voltage range is valid for 5 s ON period at 50/60 Hz AC and DC. The response voltage lies at 0.85 of the lower limit of the voltage range. 3) One auxiliary release can be mounted on the right per motor starter protector (does not apply to 3RV21 motor starter protectors with overload relay function).

8/44

Siemens IC 10 · 2022

}

3RV2902-1AP0

}

3RV2902-2AP0

}

3RV2902-1DP0

}

3RV2902-2DP0

For the complete range of accessories for the motor starter protectors, see page 7/48 onwards.

* You can order this quantity or a multiple thereof. Illustrations are approximate

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders Accessories Accessories for contactors For contactors

Version

Size

SD

Article No.

Price per PU

PU (UNIT, SET, M)

PS*

PG

d

Auxiliary switches for snapping onto the front of contactors Screw terminals Cable entry from below S00 ... S3

1-pole - 1 NO - 1 NC

3RH2911-1BA.. S00 ... S3

} }

3RH2911-1BA10 3RH2911-1BA01

1 1

1 unit 1 unit

41B 41B

} }

3RH2911-1MA11 3RH2911-1MA20

1 1

1 unit 1 unit

41B 41B

2-pole - 1 NO + 1 NC - 2 NO

3RH2911-1MA..

Auxiliary switches for contactors, for lateral mounting Screw terminals 2 NC 1 NO + 1 NC 2 NO

} } }

3RH2911-1DA02 3RH2911-1DA11 3RH2911-1DA20

1 1 1

1 unit 1 unit 1 unit

41B 41B 41B

S0/S3 S0/S3 S0/S3

2 NC 1 NO + 1 NC 2 NO

} } }

3RH2921-1DA02 3RH2921-1DA11 3RH2921-1DA20

1 1 1

1 unit 1 unit 1 unit

41B 41B 41B

Spring-loaded terminals S00 S00 S00

2 NC 1 NO + 1 NC 2 NO

2 } }

3RH2911-2DA02 3RH2911-2DA11 3RH2911-2DA20

1 1 1

1 unit 1 unit 1 unit

41B 41B 41B

S0/S3 S0/S3 S0/S3

2 NC 1 NO + 1 NC 2 NO

} } }

3RH2921-2DA02 3RH2921-2DA11 3RH2921-2DA20

1 1 1

1 unit 1 unit 1 unit

41B 41B 41B

3RH2911-2DA..

Connection module (adapter and plug) for contactors with screw terminals (can only be used for direct-on-line starters) The connection module comprises an adapter and a motor feeder connector.

Screw terminals

Adapters Ambient temperature Tu max. = 60 °C 3RT1926-4RD01

S00

Rated operational current Ie at AC-3/400 V: 20 A

5

3RT1916-4RD01

1

1 unit

41B

S0

Rated operational current Ie at AC-3/400 V: 25 A

5

3RT1926-4RD01

1

1 unit

41B

5

3RT1900-4RE01

1

1 unit

41B

Motor feeder connector S00, S0

--

3RT1900-4RE01

For the complete range of accessories for the 3RT contactors, see page 3/79 onwards.

* You can order this quantity or a multiple thereof. Illustrations are approximate

Siemens IC 10 · 2022

8/45

8

3RH2911-1DA..

S00 S00 S00

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders Accessories For contactors

Version

Type

Rated control supply voltage Us1) AC operation

DC operation

V AC

V DC

SD

Article No.2)

Price per PU

PU (UNIT, SET, M)

PS*

PG

d

Surge suppressors without LED for contactors (also for spring-loaded terminals) Size S00 For plugging onto the front side of the contactors (with or without auxiliary switches)

3RT2916-1B.00

3RT2.1

Varistors

24 ... 48 127 ... 240

24 ... 70 150 ... 250

} }

3RT2916-1BB00 3RT2916-1BD00

1 1

1 unit 1 unit

41B 41B

3RT2.1

RC element

24 ... 48 127 ... 240

24 ... 70 150 ... 250

} }

3RT2916-1CB00 3RT2916-1CD00

1 1

1 unit 1 unit

41B 41B

3RT2.1

Interference suppression diode

--

12 ... 250

}

3RT2916-1DG00

1

1 unit

41B

3RT2.1

Diode assemblies -(diode and Zener diode) for DC operation

12 ... 250

}

3RT2916-1EH00

1

1 unit

41B

Size S0 For plugging into the front side of the contactors (before installing the auxiliary switch) 3RT2.2

Varistors2)

24 ... 48 127 ... 240

24 ... 70 150 ... 250

} }

3RT2926-1BB00 3RT2926-1BD00

1 1

1 unit 1 unit

41B 41B

3RT2.2

RC element

24 ... 48 127 ... 240

24 ... 70 150 ... 250

} }

3RT2926-1CB00 3RT2926-1CD00

1 1

1 unit 1 unit

41B 41B

3RT2.2

Diode assemblies for DC operation

---

24 30 ... 250

} }

3RT2926-1ER00 3RT2926-1ES00

1 1

1 unit 1 unit

41B 41B

3RT2926-1E.00

Size S2

8

For plugging into the front side of the contactors (before installing the auxiliary switch) 3RT2.3

Varistors2)

24 ... 48 127 ... 240

---

1 1

3RT2936-1BB00 3RT2936-1BD00

1 1

1 unit 1 unit

41B 41B

3RT2.3

RC element

24 ... 48 127 ... 240

24 ... 70 150 ... 250

1 1

3RT2936-1CB00 3RT2936-1CD00

1 1

1 unit 1 unit

41B 41B

3RT2.3

Diode assemblies for DC operation

---

24 30 ... 250

1 5

3RT2936-1ER00 3RT2936-1ES00

1 1

1 unit 1 unit

41B 41B

3RT2936-1B.00

Size S3 For plugging into the front of the contactors (before mounting the auxiliary switch) 3RT2.4

Varistors2)

24 ... 48 127 ... 240

---

1 1

3RT2936-1BB00 3RT2936-1BD00

1 1

1 unit 1 unit

41B 41B

3RT2.4

Diode assemblies for DC operation

---

24 30 ... 250

1 5

3RT2936-1ER00 3RT2936-1ES00

1 1

1 unit 1 unit

41B 41B

2 1

3RT2946-1CB00 3RT2946-1CD00

1 1

1 unit 1 unit

41B 41B

3RT2936-1B.00 For plugging into the two recesses on the left of the connection block for auxiliary switches and coils A1 and A2. The connection cables are wired to A1 and A2, see also page 3/11. 3RT2.4

RC element

24 ... 48 127 ... 240

24 ... 70 150 ... 250

3RT2946-1C.00 1)

Can be used for AC operation for 50/60 Hz. Other voltages on request. 2) The varistor is already integrated on the AC/DC contactors.

8/46

Siemens IC 10 · 2022

* You can order this quantity or a multiple thereof. Illustrations are approximate

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders Accessories Accessories for the customer assembly of fuseless load feeders For motor starter protectors

For contactors

Size

Size

Actuating voltage of contactor

SD

Article No.

Price per PU

PU (UNIT, SET, M)

PS*

PG

d

Link modules from motor starter protector to contactor1) Connection between motor starter protector and contactor with screw terminals

Screw terminals

Single-unit packaging

3RA2921-1AA00

S00/S0 S00/S0 S00/S0 S2 S3

S00 S0 S0 S2 S3

AC/DC AC DC, AC/DC AC, DC, AC/DC AC, DC, AC/DC

} } } } }

3RA1921-1DA00 3RA2921-1AA00 3RA2921-1BA00 3RA2931-1AA00 3RA1941-1AA00

1 1 1 1 1

1 unit 1 unit 1 unit 1 unit 1 unit

41B 41B 41B 41B 41B

AC/DC AC DC, AC/DC AC, DC, AC/DC AC, DC, AC/DC

} } } } }

3RA1921-1D 3RA2921-1A 3RA2921-1B 3RA2931-1A 3RA1941-1A

1 10 units 1 10 units 1 10 units 1 5 units 1 5 units

41B 41B 41B 41B 41B

3RA2931-1AA00 Multi-unit packaging S00/S0 S00/S0 S00/S0 S2 S3

S00 S0 S0 S2 S3

3RA1941-1AA00 Connection between motor starter protector and contactor with spring-loaded terminals

8

Spring-loaded terminals

Single-unit packaging S00 S0

S00 S0

AC/DC AC2), DC, AC/DC

} }

3RA2911-2AA00 3RA2921-2AA00

1 1

1 unit 1 unit

41B 41B

AC/DC AC2), DC, AC/DC

} }

3RA2911-2A 3RA2921-2A

1 10 units 1 10 units

41B 41B

AC/DC AC2), DC, AC/DC

} }

3RA2911-2FA00 3RA2921-2FA00

1 1

1 unit 1 unit

41B 41B

AC/DC AC2), DC, AC/DC

} }

3RA2911-2F 3RA2921-2F

1 10 units 1 10 units

41B 41B

Multi-unit packaging 3RA2911-2AA00

S00 S0

S00 S0

Hybrid link modules from motor starter protector to contactor3) Connection between motor starter protector with screw terminals and contactor with spring-loaded terminals Single-unit packaging S00 S0

S00 S0

3RA2911-2FA00 Multi-unit packaging S00 S0

S00 S0

3RA2921-2FA00 1)

The link modules from motor starter protector to contactor cannot be used for the 3RV1011, 3RV2.21-4PA1., 3RV2.21-4FA1., 3RV2.31-4K.1., 3RV2.31-4R.1., 3RV2.32-4K.1., 3RV2.32-4R.1., 3RV27 and 3RV28 motor starter protectors/circuit breakers. 2) A spacer for height compensation on AC contactors, size S0, is optionally available, see page 8/53. 3) The hybrid link modules for motor starter protector to contactor cannot be used for the 3RV1011, 3RV2.21-4PA1., 3RV2.21-4FA1., 3RV27 and 3RV28 motor starter protectors/circuit breakers. They are only suitable for constructing direct-on-line starters.

* You can order this quantity or a multiple thereof. Illustrations are approximate

Note: Link modules can be used in • Size S00 up to max. 16 A • Size S0 up to max. 32 A • Size S2 up to max. 65 A Hybrid link modules can be used in • Size S00 up to max. 16 A • Size S0 up to max. 32 A

Siemens IC 10 · 2022

8/47

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders Accessories For motor starter protectors

For 3RW30, 3RW40 soft starters; 3RF34 solid-state contactors

SD

Size

Size

d

Article No.

Price per PU

PU (UNIT, SET, M)

PS*

PG

Link modules for motor starter protector to soft starter1) and motor starter protector to solid-state contactor1) Connection between motor starter protector and soft starter/solid-state contactor with screw terminals

Screw terminals

Single-unit packaging

3RA2921-1BA00

S00/S0

S00/S0

}

3RA2921-1BA00

1

1 unit

41B

S22)

S2

}

3RA2931-1AA00

1

1 unit

41B

S33)

S3

}

3RA1941-1AA00

1

1 unit

41B

Multi-unit packaging S00/S0

S00/S0

}

3RA2921-1B

1 10 units

41B

S22)

S22)

}

3RA2931-1A

1

5 units

41B

S33)

S33)

}

3RA1941-1A

1

5 units

41B

Connection between motor starter protector and soft starter with spring-loaded terminals

Spring-loaded terminals

Single-unit packaging 3RA2931-1AA00

S00

S00

2

3RA2911-2GA00

1

1 unit

41B

S0

S0

2

3RA2921-2GA00

1

1 unit

41B

8

3RA1941-1AA00

3RA2921-2GA00 1)

The link modules from motor starter protector to soft starter and motor starter protector to solid-state contactor cannot be used for the 3RV1011, 3RV2.21-4PA1., 3RV2.21-4FA1., 3RV2.31-4K.1., 3RV2.31-4R.1., 3RV2.32-4K.1., 3RV2.32-4R.1., 3RV27 and 3RV28 motor starter protectors/circuit breakers. 2) To assemble the feeder between a motor starter protector and a soft starter in size S2, the 3RA2932-1CA00 standard mounting rail adapter must be used. 3) It is only permitted to assemble the feeder between the motor starter protector and the soft starter in size S3 on a mounting plate.

8/48

Siemens IC 10 · 2022

Note: Link modules can be used in • Size S00 up to max. 16 A • Size S0 up to max. 32 A • Size S2 up to max. 65 A

* You can order this quantity or a multiple thereof. Illustrations are approximate

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders Accessories PU (UNIT, SET, M) = 1 PS* = 1 unit (unless otherwise specified) PG = 41B

3RA2923-2AA1 For Size contactors

Version

3RA2933-2AA1 SD

Screw terminals

Article No. Type

d

3RA2923-2AA2 SD Spring-loaded terminals Price per PU d

Article No.

Price per PU

Assembly kits for reversing contactor assemblies for making 3-pole contactor assemblies 3RT201

S00-S00

The assembly kit contains: Mechanical interlock, two connecting clips for two contactors, wiring modules on the top and bottom

3RT202

S0-S0

The assembly kit contains: Mechanical interlock, two connecting clips for two contactors, wiring modules on the top and bottom

• For main, auxiliary and control circuits

• For main, auxiliary and control circuits1)

}

3RA2913-2AA1

}

3RA2923-2AA1

• Only for main circuit2) S2-S2

}

• Only for main circuit3) S3-S3

-}

3RA2923-2AA2

The assembly kit contains: Two connectors for two contactors, wiring modules on the top and bottom (3RA2934-2B mechanical interlock must be ordered separately, see page 3/117) • For main and auxiliary circuits

3RT204

3RA2913-2AA2

8

3RT203

--

}

3RA2933-2AA1 --

-5

3RA2933-2AA2

The assembly kit contains: Two connectors for two contactors, wiring modules on the top and bottom (3RA2934-2B mechanical interlock must be ordered separately, see page 3/117) • For main and auxiliary circuits • Only for main circuit3)

2

3RA2943-2AA1 --

-2

3RA2943-2AA2

1)

Use of the 3RA2923-2AA1 assembly kit in conjunction with the 3RT202.-.....-3MA0 contactors is limited because the auxiliary switches in the basic unit are not allowed to be used on account of the permanently mounted auxiliary switch. 2) Version in size S0 with spring-loaded terminals: Only the wiring modules for the main circuit are included. No connecting clips are included for the auxiliary and control circuit. 3) Version in sizes S2 and S3 with spring-loaded terminals in the auxiliary and control circuits: Only the wiring modules for the main circuit are included. A cable set is included for the auxiliary circuit.

* You can order this quantity or a multiple thereof. Illustrations are approximate

Siemens IC 10 · 2022

8/49

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders Accessories For Version contactors

SD

Size

d

Article No.

Price per PU

PU (UNIT, SET, M)

PS*

PG

1 1 1

1 unit 1 unit 1 unit

41B 41B 41B

PU (UNIT, SET, M)

PS*

PG

14O

Safety main circuit connectors for two contactors For switching two contactors in series S00 S0 S2

Screw terminals 2 2 }

3RA2916-1A 3RA2926-1A 3RA2936-1A

SD

Article No.

3RA2916-1A For motor For constarter tactors protectors

Version

Price per PU

d

Mounting rails for mounting contactors for the customer assembly of 3RA21 load feeders with busbar adapters for 60 mm systems For the discrete configuration of directon-line starters a further mounting rail is needed for the contactor in addition to the mounting rail for the motor starter protector existing on the busbar adapter. --

S0

For pushing onto the device adapter, including fixing screws

2

8US1998-7CB45

1 10 units

8US1998-7CB45

Standard mounting rail adapters

8

For mechanical fixing of motor starter protector and contactor; for snapping onto standard mounting rail or for screw fixing

3RA2922-1AA00

S00, S00

S00, S00 Short, single-unit packaging

2

3RA2922-1BA00

1

1 unit

41B

S00, S00

S00, S00 Short, multi-unit packaging

2

3RA2922-1B

1

5 units

41B

S00, S0

S00, S0

Single-unit packaging

}

3RA2922-1AA00

1

1 unit

41B

S00, S0

S00, S0

Multi-unit packaging

2

3RA2922-1A

1

5 units

41B

S2

S2

Single-unit packaging

}

3RA2932-1AA00

1

1 unit

41B

S2

S2

Multi-unit packaging

2

3RA2932-1A

1

5 units

41B

S3

S3

Single-unit packaging

2

3RA2942-1AA00

1

1 unit

41B

S3

S3

Multi-unit packaging

2

3RA2942-1A

1

5 units

41B

2

3RA2932-1CA00

1

1 unit

41B

2

3RA2902-1B

1 10 units

41B

For mechanical fixing of motor starter protector and soft starter; for snapping onto standard mounting rail or for screw fixing S2

S2

Single-unit packaging

3RA2932-1CA00

Side modules for standard mounting rail adapters S00 ... S3 S00 ... S3 For standard mounting rail adapters 10 mm wide, 96 mm long, For widening standard mounting rail adapters when using lateral auxiliary switches, 2 units required

3RA2902-1B

8/50

Siemens IC 10 · 2022

* You can order this quantity or a multiple thereof. Illustrations are approximate

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders Accessories For motor For constarter tactors protectors

Version

SD

Article No.

d

Price per PU

PU (UNIT, SET, M)

PS*

PG

RH assembly kits for reversing duty and standard rail mounting RH assembly kits for screw terminals

Screw terminals

S0

3RA2923-1BB1

1

1 unit

41B

3RA2933-1BB1

1

1 unit

41B

3RA2943-1BB1

1

1 unit

41B

1

1 unit

41B

100 10 units

41E

S0

Consisting of: 2 • Wiring kit for main and auxiliary circuit • Two standard mounting rail adapters • Two connecting wedges • Mechanical interlocks • Two connecting clips for two contactors • Fixing accessories Link modules must be ordered separately.

3RA2923-1BB1 S2

S2

Consisting of: 2 • Wiring kit for main and auxiliary circuit • Two standard mounting rail adapters • Two side modules • Four connecting wedges • Mechanical interlocks • Two connectors for two contactors • Fixing accessories Link modules must be ordered separately.

S3

S3

Consisting of: 2 • Wiring kit for main and auxiliary circuit • Two standard mounting rail adapters • Three side modules • Six connecting wedges • Mechanical interlocks • Two connectors for two contactors • Fixing accessories

8

3RA2933-1BB1

Link modules must be ordered separately.

3RA2943-1BB1

RH assembly kits for spring-loaded terminals

Spring-loaded terminals

S0

3RA2923-1BB2

S0

Consisting of: 2 • Wiring kit for main and auxiliary circuit • Two standard mounting rail adapters • Two connecting wedges • Mechanical interlocks • Two connecting clips for two contactors • Two spacers • Fixing accessories Link modules must be ordered separately.

3RA2923-1BB2

Push-in lugs for screw fixing S00, S0

--

For screw fixing of the motor starter protector (of the load feeder) onto mounting plates; 2 units are required for each motor starter protector

2

3RV2928-0B

3RV2928-0B

For graphic overviews for RH assembly kits, see page 8/12 onwards.

* You can order this quantity or a multiple thereof. Illustrations are approximate

Siemens IC 10 · 2022

8/51

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders Accessories Busbar adapters

8US1251-5DS10

8US1251-5DT11

8US1250-5AS10

8US1250-5AT10

For load feeders

Rated current

Connec- Adapter tion cable length

Adapter width

Rated voltage

SD

Size

A

AWG

mm

V

d

mm

Article No.

Price per PU

PU (UNIT, SET, M)

PS*

PG

Busbar adapters for 60 mm systems For flat copper profiles according to DIN 46433 Width: 12 mm and 30 mm Thickness: 5 mm and 10 mm and for T and double-T special profiles

8

• For load feeders with screw terminals

Screw terminals

S00/S0

25

12

200

45

690

2

8US1251-5DS10

1

1 unit

14O

S00 (motor starter protector)/ S0 (contactor)

25

12

260

45

690

2

8US1251-5DT10

1

1 unit

14O

S0

32

10

200

45

690

3

8US1251-5NS10

1

1 unit

14O

S0

32

10

260

45

690

2

8US1251-5NT10

1

1 unit

14O

S2

80

4

260

55

690

5

8US1261-6MT10

1

1 unit

14O

S21)

80

4

260

118

690

5

8US1211-6MT10

1

1 unit

14O

• For load feeders with spring-loaded terminals

Spring-loaded terminals

S00

25

12

200

45

690

2

8US1251-5DS11

1

1 unit

14O

S00/S0

25

12

260

45

690

2

8US1251-5DT11

1

1 unit

14O

S0

32

10

200

45

690

5

8US1251-5NS11

1

1 unit

14O

S0

32

10

260

45

690

2

8US1251-5NT11

1

1 unit

14O

Accessories2) Device holders For lateral attachment to busbar adapters Side modules For widening busbar adapters

--

--

200

45

--

2

8US1250-5AS10

1

1 unit

14O

--

--

260

45

--

2

8US1250-5AT10

1

1 unit

14O

--

--

200

9

--

2

8US1998-2BJ10

1 10 units

14O

--

--

--

--

--

5

8US1998-1DA10

1

14O

Vibration and shock kits For high vibration and shock loads S2

1 unit

1)

For the assembly of feeders for reversing starters consisting of a motor starter protector and two contactors. 2) For additional mounting rails for busbar adapters, see page 8/50.

8/52

Siemens IC 10 · 2022

* You can order this quantity or a multiple thereof. Illustrations are approximate

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders Accessories For motor For starter contacprotectors tors Size

Version

Size

SD

Article No.

Price per PU

PU (UNIT, SET, M)

PS*

PG

d

RS assembly kits for reversing duty and 60 mm busbar systems RS assembly kits for screw terminals S00, S0 S0 S00

S00 S0 S0

Consisting of: • Wiring kit for main and auxiliary circuit • Busbar adapters • Device holders • Two connecting wedges • Mechanical interlocks • Two connecting clips for two contactors • Fixing accessories

Screw terminals 2 2 2

3RA2913-1DB1 3RA2923-1DB1 3RA2923-1EB1

1 1 1

1 unit 1 unit 1 unit

41B 41B 41B

2

3RA2933-1DB1

1

1 unit

41B

1 1

1 unit 1 unit

41B 41B

PU (UNIT, SET, M)

PS*

PG

100 100 units

14O

Link modules must be ordered separately.

3RA2913-1DB1 S2

S2

Consisting of: • Wiring kit for main and auxiliary circuit • Busbar adapters • Mechanical interlocks • Two connectors for two contactors • Fixing accessories Link modules must be ordered separately.

3RA2933-1DB1

S00 S0

S00 S0

3RA2913-1DB2

Consisting of: • Wiring kit for main and auxiliary circuit • Busbar adapters • Device holders • Two connecting wedges • Mechanical interlocks • Two connectors for two contactors • Two spacers (for size S0 only) • Fixing accessories

2 2

3RA2913-1DB2 3RA2923-1DB2

SD

Article No.

Link modules must be ordered separately.

For graphic overviews for RS assembly kits, see page 8/15 onwards. For motor For starter contacprotectors tors Size

Version

Size

Price per PU

d

Connecting wedges For mechanical linking of busbar adapters and device holders or of standard mounting rail adapters (2 units per combination required)

2

8US1998-1AA00

8US1998-1AA00

Spacers For height compensation on AC contactors size S0 with spring-loaded terminals

Spring-loaded terminals

S0

S0

Single-unit packaging

}

3RA2911-1CA00

1

1 unit

41B

S0

S0

Multi-unit packaging

}

3RA2911-1C

1

5 units

41B

3RA2911-1CA00

* You can order this quantity or a multiple thereof. Illustrations are approximate

Siemens IC 10 · 2022

8/53

8

Spring-loaded terminals

RS assembly kits for spring-loaded terminals

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders Accessories Version

SD

Article No.

Price per PU

PU (UNIT, SET, M)

PS*

PG

1

1 unit

41B

100 340 units

41B

d

Tools for opening spring-loaded terminals Spring-loaded terminals

Screwdrivers For all SIRIUS devices with spring-loaded terminals

3RA2908-1A

Length approx. 200 mm, 3.0 mm x 0.5 mm, titanium gray/black, partially insulated

2

3RA2908-1A

Unit labeling plates1) For SIRIUS devices 20 mm x 7 mm, titanium gray

20

3RT2900-1SB20

IC01_00181

Blank labels

3RT2900-1SB20

Manuals Configuration Manual for load feeders, see https://support.industry.siemens.com/cs/ww/en/view/39714188. PC labeling system for individual inscription of unit labeling plates available from: murrplastik Systemtechnik GmbH (see page 16/16).

8

1)

8/54

Siemens IC 10 · 2022

* You can order this quantity or a multiple thereof. Illustrations are approximate

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA2 load feeders 3RV29 infeed system for load feeders

■ Overview Types of infeed for 3RA2 fuseless load feeders

8US busbar adapters for 60 mm systems

On the whole four different power infeed possibilities are available: • Parallel wiring • Use of 3-phase busbars (combination with SIRIUS motor starter protectors and contactors possible) • 8US busbar adapters • SIRIUS 3RV29 infeed systems

The load feeders are mounted directly with the aid of busbar adapters on busbar systems with 60 mm center-to-center clearance in order to save space and to reduce infeed times and costs.

Insulated 3-phase busbar system 3-phase busbar systems provide an easy, time-saving and clearly arranged means of feeding 3RA2 load feeders with screw terminals. Different versions are available for sizes S00 and S0 and can also be used for the various different types of motor starter protectors.

The busbar adapters for busbar systems with 60 mm center-tocenter clearance are suitable for copper busbars with a width of 12 to 30 mm. The busbars can be 4 to 5 mm or 10 mm thick. The feeders are snapped onto the adapter and connected on the line side. This prepared unit is then plugged directly onto the busbar system, and is thus connected both mechanically and electrically at the same time. For "Selection and ordering data", see page 8/52.

The busbars are suitable for between two and five feeders. However, any kind of extension is possible by clamping the connection tags of an additional busbar (rotated 180°) underneath the terminals of the respective last motor starter protector. A combination of feeders of different sizes is possible with sizes S00 and S0. Connecting pieces are available for this purpose. The motor starter protectors are supplied by appropriate infeed terminals. 3RV2925-5AB

NSB0_02080a

8

3RV1915-1CB

NSB0_02079c

3RV2915-5B

3RV1915-6AB

SIRIUS load feeders with busbar adapters snapped onto busbars

SIRIUS 3RV29 infeed system The 3RV29 infeed system is a convenient means of energy supply and distribution for a group of several motor starter protectors or complete load feeders with screw or spring-loaded terminals up to size S0. The system is based on a basic module complete with a lateral incoming unit (3-phase busbar with infeed) which has two slots.

SIRIUS 3-phase busbar system size S00/S0

The 3-phase busbar systems are finger-safe. They are designed for any short-circuit stress which can occur at the output side of connected motor starter protectors.

Expansion modules are available for extending the system (3-phase busbars for system expansion). For the 3RV29 infeed system, see page 7/69.

The 3-phase busbar systems can also be used to construct "Starters (Type E)" of size S0 or S2 according to UL/CSA. However, special infeed terminals must be used for this purpose; see page 7/53.

Siemens IC 10 · 2022

8/55

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters General data

■ Overview 3RA6 fuseless compact starters and infeed system for 3RA6 More information Homepage, see www.siemens.com/sirius-compact-starters Industry Mall, see www.siemens.com/product?3RA6 Online configurator, see www.siemens.com/sirius/configurators

Very high operational reliability The high short-circuit breaking capacity and defined shut-down when the end of service life is reached mean that the SIRIUS compact starter achieves a very high level of operational reliability that would otherwise have only been possible with considerable additional outlay. This sets it apart from devices with similar functionality. Safe disconnection

8

The auxiliary switches (NC contacts) of the 3RA6 compact starters are designed as mirror contacts. This enables their use for safe disconnection, e.g. EMERGENCY STOP up to SIL 1 (IEC 62061) or PL c (ISO 13849-1) or, if used in conjunction with an additional infeed contactor, up to SIL 3 (IEC 62061) / PL e (ISO 13849-1). 3RA62 reversing starter

Communications integration through AS-Interface

Integrated functionality

To enable communications integration through AS-Interface there is an AS-i add-on module available in several versions for mounting instead of the control circuit terminals on the SIRIUS compact starter.

The SIRIUS 3RA6 compact starters are a generation of special load feeders with the integrated functionality of a motor starter protector, contactor and electronic overload relay. In addition, various functions of optional mountable accessories (e.g. auxiliary switches, surge suppressors) are already integrated in the SIRIUS compact starter.

The design of the AS-i add-on module permits a group of up to 62 feeders with a total of four cables to be connected to the control system. This reduces wiring work considerably compared to the parallel wiring method. Communications integration using IO-Link Up to four compact starters in IO-Link version (reversing and direct-on-line starters) can be connected together and conveniently linked to the IO-Link master through a standardized IO-Link connection. The IO-Link connection enables a high density of information in the local range. For details of the communication connection using IO-Link, see page 2/87 onwards. The diagnostics data of the process collected by the 3RA6 compact starter, e.g. short circuit, end of service life, limit position, etc., are not only indicated on the compact starter itself but also transmitted to the higher-level control system through IO-Link. Thanks to the optionally available operator panel, which can be installed in the control cabinet door, it is easy to control the 3RA6 compact starters with IO-Link from the control cabinet door. Permanent wiring/easy replacement

3RA6 compact starters with the integrated functionality of a motor starter protector, contactor and electronic overload relay.

Applications SIRIUS compact starters can be used wherever standard three-phase motors or resistive loads up to 32 A (approx. 15 kW/400 V) are directly started or switched. The compact starters are not suitable for the protection of DC loads. Approvals according to IEC, UL, CSA and CCC standards have been issued for the compact starters.

8/56

Siemens IC 10 · 2022

Using the SIRIUS infeed system for 3RA6 (see page 8/77), it is possible to carry out the wiring in advance without a compact starter having to be connected. A compact starter is very easily replaced simply by pulling it out of the device without disconnecting the wiring. Even with screw fixing or mounting on a standard mounting rail there is no need to disconnect any wiring (on account of the removable main and control circuit terminals) in order to replace a compact starter.

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters General data Consistent solution from the infeed to the motor feeder

SIRIUS 3RA6 compact starters

The SIRIUS infeed system for 3RA6 with integrated PE bar is offered as a user-friendly possibility of feeding in summation currents up to 100 A with a maximum conductor cross-section of 70 mm² and connecting the motor cable directly without additional intermediate terminals.

SIRIUS 3RA6 compact starters are universal motor feeders according to IEC 60947-6-2. As control and protective switching devices (CPS) they can connect, convey and disconnect the thermal, dynamic and electrical loads from short-circuit currents up to Iq = 53 kA, i.e. they are practically weld-free. They combine the functions of a motor starter protector, a contactor and an electronic overload relay in one enclosure. 45-mm-wide direct-on-line starters and 90-mm-wide reversing starters are available as variants.

Screw and spring-loaded terminals The SIRIUS compact starters and the infeed system for 3RA6 are available with screw and spring-loaded terminals.

The reversing starter version comes with not only an internal electrical interlock but also with a mechanical interlock to prevent simultaneous actuation of both directions of rotation.

Screw terminals Spring-loaded terminals The terminals are indicated in the corresponding tables by the symbols shown on orange backgrounds. System configurator for engineering A free system configurator is available to reduce further the amount of engineering work for selecting the required compact starters and matching infeed.

The compact starters have isolating features in accordance with IEC 60947-2 and can be used as disconnector units (main control switch according to EN 60204 or VDE 0113). Isolation is effected by moving the handle into the "OFF" position; disconnection by means of the control contacts is not enough. 3RA6 fuseless compact starters are available in five current setting ranges. The 3RA61 and 3RA62 have two control voltage ranges (AC/DC), and the 3RA64 and 3RA65 have one control voltage range (DC): Current setting range

For the use of SIRIUS 3RA6 compact starters in conjunction with highly energy-efficient IE3/IE4 motors, please observe the information on dimensioning and configuring, see Application Manual.

At 400 V AC for Rated control supply voltage for three-phase 3RA61, 3RA62 3RA64, 3RA65 motors compact starters compact starters Standard for IO-Link output P

A

kW

V AC/DC

V DC

0.1 ... 0.4

0.09

24

24

For more information, see page 1/8.

0.32 ... 1.25 0.37

Types of infeed for the 3RA6 fuseless compact starters

1 ... 4

1.5

On the whole four different infeed possibilities are available: • Parallel wiring • Use of 3-phase busbars (combination with SIRIUS motor starter protectors and SIRIUS contactors possible) • 8US busbar adapters • SIRIUS infeed system for 3RA6 (see page 8/77)

3 ... 12

5.5

8 ... 32

15

Note:

110 ... 240

8

Use of load feeders in conjunction with IE3/IE4 motors

Notes: The 3RA2 load feeders can be used for fuseless load feeders > 32 A up to 65 A. Load feeders in size S3 up to 100 A are available for customer assembly (see also page 8/4).

To comply with the clearances and creepage distances demanded according to UL 508 there are the following infeed possibilities:

The SENTRON 3VL circuit breakers and the SIRIUS 3RT contactors can be used for fuseless load feeders > 100 A.

Type of infeed

Infeed terminal (according to UL 508, Type E)

Type

Parallel wiring

Terminal block for "Self-Protected Combination Motor Controller (Type E)"

3RV2928-1H

The SIRIUS 3RA6 compact starters are suitable for use in any climate. They are intended for use in enclosed rooms in which no severe operating conditions (such as dust, caustic vapors, hazardous gases) prevail. Suitable covers must be provided for installation in dusty and damp locations.

3-phase busbars

3-phase infeed terminal 3RV2925-5EB for constructing "Starters (Type E)" UL 508

Infeed system for 3RA6

Infeed on left, 50/70 mm2 screw terminal with 3 sockets, outgoing terminal with screw/springloaded terminals, including PE bar

3RA6813-8AB (screw terminals), 3RA6813-8AC (spring-loaded terminals)

Operating conditions

The permissible ambient temperature during operation is -20 to +60 °C. The rated short-circuit current ICS according to IEC 60947-6-2 is 53 kA at 400 V. Note: The maximum permissible short-circuit currents of the device versions for the various system types and voltages are available upon request from Technical Support: www.siemens.com/support-request

Siemens IC 10 · 2022

8/57

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters General data Overload tripping times

More components of the 3RA6

The tripping time in the event of overload can be set on the device to normal starting conditions (CLASS 10) and to heavy starting conditions (CLASS 20). As the breaker mechanism still remains closed after an overload, resetting is possible by either local Manual RESET or Auto RESET1) after three minutes cooling time.

Apart from the control supply voltage, "Overload" (1 CO) and "Short circuit/Function fault" (1 NO) signaling contacts are already integrated into the 3RA61/3RA62 – and lockable via two 6-pole removable control circuit terminals. The 3RA61 has two auxiliary contacts (1 NO + 1 NC) for displaying the position of the main contacts. Unlike the 3RA61 direct-on-line starter, the 3RA62 reversing starter has one auxiliary contact (1 NO) per direction of rotation per main contact.

With Auto RESET, there is no need to open the control cabinet. Diagnostics options The compact starter provides the following diagnostics options: • With LEDs - Connection to the control voltage - Position of the main contacts • With mechanical display - Tripping due to overload - Tripping due to short circuit - Tripping due to malfunction (end of service life reached because of worn switching contacts or a worn switching mechanism or faults in the control electronics)

8

These states can also be evaluated in the higher-level control system: • With parallel wiring using the integrated auxiliary and signaling switches of the compact starter • With AS-Interface or IO-Link in even greater detail using the respective communication interface Four complement versions for 3RA61 and 3RA62 compact starters • For standard mounting rail or screw fixing: basic version including one pair of main circuit terminals and one pair of control circuit terminals • For standard mounting rail or screw fixing when using the AS-i add-on module: without control circuit terminals because the AS-i add-on module is plugged on instead • For use with the infeed system for 3RA6: without main circuit terminals because they are supplied with the infeed system and the expansion modules • For use with the infeed system for 3RA6 and the AS-i add-on module: without terminal complement (also for reordering when replacing the compact starter) The control circuit terminals are always required by the compact starters for IO-Link; the main circuit terminals depend on the use of the infeed system. 1)

The Auto RESET function is not available for versions 3RA6120-.B/.C with a rated current of 1.25 A and 3RA6250-.B/-.C with a rated current of 4 A. The reset can be alternatively carried out by disconnecting the supply voltage A1/A2 via the NC contacts 95/96 (overload signaling contact). The Auto RESET function is provided with this circuitry.

8/58

Siemens IC 10 · 2022

Available for the 3RA61 and 3RA64 direct-on-line starters is a slot for an optional auxiliary switch (optionally 2 NO, 2 NC or 1 NO + 1 NC) and for the 3RA62 and 3RA65 reversing starters there are two slots (for auxiliary switches, see "Accessories" on page 8/70). Force-guided operation of the auxiliary contacts Force-guided operation between individual auxiliary circuits exists for the compact starter in the version as a direct-on-line starter for parallel wiring (3RA61) between the auxiliary circuits of the NC contacts (NC 21-22) and the NO contacts (NO 13-14) in the basic unit. In addition, the optional auxiliary switch offers force-guided contacts in the 3RA6913-1A version, each with one normally closed contact and one normally open contact. Configurator

Configurator

Advantages: • Simple usage – from individual compact starters or also with corresponding infeed system and AS-i connection • In the final configuration, you will be presented with additional technical information such as CAD data and product data sheets as well as characteristic curves, operating instructions, manuals, etc. See www.siemens.com/sirius/configurators

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters General data Article No. scheme Product versions

Article number 3RA6 @ @ @ – @ @ @ @ @

Product function

Direct-on-line starter Reversing starter Direct-on-line starter for IO-Link Reversing starter for IO-Link Infeed system Accessories • Auxiliary switches • Terminals • IO-Link accessories • Fixing elements • Control kit

Connection methods

No terminals Screw terminals Spring-loaded terminals

Setting range

0.1 ... 0.4 A 0.32 ... 1.25 A 1 ... 4 A 3 ... 12 A 8 ... 32 A

Rated control supply voltage

24 V DC 24 V AC/DC 110 ... 240 V AC/DC

Terminal complement variant

None 1/1 0/1 1/0

1 2 0 2 5 0 4 0 0

For motor standard output 0.09 ... 15 kW1) For motor standard output 0.09 ... 15 kW1) For motor standard output 0.09 ... 15 kW1)

5 0 8 9 1 2 3 4 5

For motor standard output 0.09 ... 15 kW1)

0

@ @ @ @ @ 0 1 2 A B C D E For direct-on-line/reversing starters for IO-Link For direct-on-line/reversing starters For direct-on-line/reversing starters

B 4 B 3 P 3 0 2 3 4

Without main and control circuit terminals With 1 pair of main circuit and 1 pair of control circuit terminals Without main circuit terminals, with 1 pair of control circuit terminals With 1 pair of main circuit terminals, without control circuit terminals

Special versions Example 1)

3RA6 1 2 0 – 0 A B 3 0

Standard three-phase motor, basis 4-pole at 400 V AC; the actual starting and rated data of the motor to be protected must be considered when selecting the units.

Note: The Article No. scheme shows an overview of product versions for better understanding of the logic behind the article numbers.

For your orders, please use the article numbers quoted in the selection and ordering data.

■ Benefits Product advantages The SIRIUS 3RA6 compact starters offer a number of benefits: • Compact design saves space in the control cabinet • Little planning and assembly work and far less wiring thanks to a single complete unit with one article number • Low variance and therefore low stock levels, with two wide voltage ranges and five wide setting ranges for the rated current • High plant availability through integrated functionalities such as prevention of main contact welding and disconnection at end of service life • Enhanced productivity through automatic device RESET1) in case of overload and differentiated detection of overload and short circuit • Easy checking of the wiring and testing of the motor direction prior to startup thanks to optional control kits 1)

• Quick replacement of devices thanks to removable terminals with spring-loaded and screw terminals in the main and control circuit • Efficient power distribution through the related SIRIUS infeed system for 3RA6 • Direct connection of the motor feeder cable to the SIRIUS infeed system for 3RA6 thanks to integrated PE bar • Connecting and looping through of incoming feeders up to a cross-section of 70 mm² • When using the infeed system for 3RA6, possibility of directly connecting the motor cable without intermediate terminals • Integration in Totally Integrated Automation thanks to the optional connection to AS-Interface or IO-Link The SIRIUS 3RA6 compact starters create the basis for highavailability and future-proof machine concepts.

The Auto RESET function is not available for versions 3RA6120-.B/.C with a rated current of 1.25 A and 3RA6250-.B/-.C with a rated current of 4 A. The reset can be alternatively carried out by disconnecting the supply voltage A1/A2 via the NC contacts 95/96 (overload signaling contact). The Auto RESET function is provided with this circuitry.

Siemens IC 10 · 2022

8/59

8

Compact starters

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters General data

■ Technical specifications More information Industry Mall, see www.siemens.com/product?3RA6 System Manual, see http://support.industry.siemens.com/cs/ww/en/view/27865747 FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16301/faq

Note on security: In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept. Siemens products and solutions represent only one component of such a concept. For more information about the subject of Industrial Security, see www.siemens.com/industrialsecurity.

Type

3RA61

3RA62

3RA64

3RA65

mm mm

45 x 170 x 165 45 x 191 x 165

90 x 170 x 165 90 x 191 x 165

45 x 170 x 165 45 x 191 x 165

90 x 170 x 165 90 x 191 x 165

mm

160

°C

-20 ... +70, restriction as from 60 depending on design

°C °C

-55 ... +80 -55 ... +80

Depth from standard mounting rail Permissible ambient temperature • For operation (permissible operational current, see the following section "Electrical specifications") • During storage • During transport Permissible mounting position

22,5° 22,5° 90°

Shock resistance (sine-wave pulse)

a = 60 m/s² = 6 g with 10 ms; for every 3 shocks in all axes f = 4 ... 5.8 Hz; d =15 mm; f = 5.8 ... 500 Hz; a = 20 m/s2;10 cycles

Vibratory load

8

90°

NSB0_00649a

W

D

Mounting dimensions (W x H x D) • Screw terminals • Spring-loaded terminals

H

Mechanics and environment

Degree of protection IP on the front

Acc. to IEC 60529

Touch protection on the front

Acc. to IEC 60529

IP20 Finger-safe for vertical touching from the front

Installation altitude

m

Up to 2 000 above sea level without restriction

Relative air humidity

%

10 ... 90 3

Pollution degree

Electrical specifications IEC 60947-6-2

Device standard Maximum rated operational voltage Ue

V V

690 400 at 3RA6250-.E... and 3RA6500-.E... (Reversing starter 32 A designs)

Rated frequency

Hz

50/60

Rated insulation voltage Ui (pollution degree 3)

V

690

Rated impulse withstand voltage Uimp Rated operational current Ie1) and setting range for overload release

0.1 ... 0.4 A 0.32 ... 1.25 A 1 ... 4 A 3 ... 12 A 8 ... 32 A

Permissible operational current of the compact starter2) When several compact starters are mounted side-by-side in the 3RA6 infeed system (for more details on the various design variants, see System Manual) • For a control cabinet inside temperature of +40 °C • For a control cabinet inside temperature of +60 °C • For a control cabinet inside temperature of +70 °C Trip class (CLASS)

kV

6

A A A A A

0.4 1.25 4 12 32

% % %

100 80 60

Acc. to IEC 60947-4-1, EN 60947-4-1 (VDE 0660 Part 102)

10/20

Overload function Ratio of lower to upper current mark

1:4

Rated service short-circuit breaking capacity ICS at 50/60 Hz, 400 V AC

kA

53

Rated service short-circuit breaking capacity ICSIT at 50/60 Hz 400/690 V AC in IT systems

kA

1.5

1)

2)

For the use of 3RA6 compact starters in conjunction with highly energyefficient IE3/IE4 motors, please observe the information on dimensioning and configuring, see Application Manual.

8/60

Siemens IC 10 · 2022

Details about installation conditions and the use of the compact starters, and particularly about the derating of the rated current, can be found in the System Manual.

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters General data Type

3RA61

3RA62

3RA64

3RA65

Electrical specifications (continued)

Max. switching frequency

AC-41 AC-43 AC-44

No-load switching frequency

mW mW W W W

10 100 1 1.8 5.4

1/h 1/h 1/h

750 250 15

1/h

3 600

3 600, depending on the IO-Link communication time

Isolating features of the compact starter

Acc. to IEC 60947-3

✓ Isolation is assured only by moving the actuator into the "OFF" position.

Main and EMERGENCY STOP switch characteristics of the compact starter and accessories

Acc. to IEC 60204



Protective separation

Acc. to IEC 60947-2

Control circuit to auxiliary circuit • Horizontal standard mounting rail • Other mounting position

V V

Up to 400 Up to 250

Auxiliary circuit to auxiliary circuit • Horizontal standard mounting rail • Other mounting position

V V

Up to 400 Up to 250

V

Up to 400

Main circuit to auxiliary circuit • Any mounting position EMC interference immunity

Acc. to IEC 60947-1

Conducted interference • In the main circuit • In the auxiliary circuit

BURST acc. to IEC 61000-4-4

Conducted interference • In the main circuit - Conductor - Ground - Conductor - Conductor • In the auxiliary circuit - Conductor - Ground - Conductor - Conductor

SURGE acc. to IEC 61000-4-5

Corresponds to degree of severity 3 kV kV

4 3

4 2

kV kV

4 2

2 1

kV kV

2 1

0.51) 0.51)

Auxiliary switches • Integrated - Position of the main contacts - Overload/short circuit and malfunction signal • Expandable - Position of the main contacts

1 NO + 1 NC 1 CO/1 NO

Surge suppressors

Integrated (varistor)

2 NO

1 NO + 1 NC

8

Power loss Pv max of all main conducting paths 0.4 A Dependent on rated current Ie 1.25 A (upper setting range) 4A 12 A 32 A

2 NO

2 NO, 2 NC, 1 NO + 1 NC

Electromagnetic operating mechanisms Control voltage Frequency

At AC

V V

24 AC/DC 110 ... 240 AC/DC

Hz

50/60 ( 5%) 0.7 ... 1.25 Us

Operating range No-load switching frequency Line protection

At 10 kA At 50 kA

Shock resistance • Breaker mechanism OFF • Breaker mechanism ON

1/h

3 600

mm² mm²

2.5 4

g g

25 15

24 DC -0.85 ... 1.2 Us

Normal switching duty 12 x In

Making capacity

10 x In

Breaking capacity Switching capacity dependent on rated current

Up to 12 A Up to 32 A

Endurance in operating cycles • Electrical endurance

At Ie = 0.9 x In and 400 V

kW kW

5.5 15 3 ... 10 000 000

2x 3 000 000 3 ... 10 000 000

2 x 1 500 000

✓ Function available 1) To maintain maximum interference immunity in a harsh electromagnetic environment, additional overvoltage protection should be provided in the control circuit. The 5SD7432-4 plug-in surge arrester with remote signaling, for instance, is suitable, see Catalog LV 10.

Siemens IC 10 · 2022

8/61

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters General data Type

3RA6120-.@B3., 3RA6250-.@B3.

3RA6120-.EB3., 3RA6250-.EB3.

@ = A, B, C or D Rated operational current  12 A

Rated operational current 32 A

Rated control supply voltage

V

24 AC

24 DC

24 AC

24 DC

Inrush peak current

A

0.59

0.47

0.59

0.47

Hold current

A

0.13

0.12

0.17

0.14

Closed

W

2.8

2.9

3.5

3.1

Operating times, typical • On • Off

ms ms

< 160 < 35

< 140 < 35

< 160 < 30

< 140 < 30

Type

3RA6120-.@P3., 3RA6250-.@P3.

3RA6120-.EP3., 3RA6250-.EP3.

@ = A, B, C or D Rated operational current  12 A

Rated operational current 32 A

Rated control supply voltage

V

110 AC

240 AC

110 DC

240 DC

110 AC

240 AC

110 DC

240 DC

Inrush peak current

A

0.24

0.40

0.17

0.29

0.24

0.40

0.17

0.29

Hold current

A

0.06

0.08

0.03

0.02

0.06

0.07

0.04

0.03

Closed

W

3.8

6

3.1

5.1

3.7

5.2

3.4

5.8

Operating times, typical • On • Off

ms ms

< 160 < 50

< 140 < 80

< 150 < 50

< 140 < 70

< 160 < 40

< 140 < 60

< 150 < 40

< 140 < 60

Type

3RA6400-.@B4., 3RA6500-.@B4.

3RA6400-.EB4., 3RA6500-.EB4.

8

@ = A, B, C or D Rated operational current  12 A

Rated operational current 32 A

Rated control supply voltage

V

24 DC

24 DC

Inrush peak current

A

0.39

0.53

Hold current

A

0.13

0.15

Closed

W

2.9

3.4

Operating times, typical1) • On • Off

ms ms

< 140 < 35

< 140 < 30

1)

Plus IO-Link communication.

8/62

Siemens IC 10 · 2022

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters General data Type

3RA61

3RA62

3RA64

3RA65

Control circuit Rated operational voltage • External auxiliary switch • Internal auxiliary switch • Short-circuit signaling switch • Overload signaling switch Switching capacity • External auxiliary switch

• Internal auxiliary switch

• Signaling switch

AC-15 • Up to Ue = 230 V • Up to Ue = 400 V • Up to Ue = 289/500 V • Up to Ue = 400/690 V DC-13 • Up to Ue = 24 V • Up to Ue = 60 V • Up to Ue = 125 V • Up to Ue = 250 V AC-15 • Up to Ue = 230 V • Up to Ue = 400 V • Up to Ue = 289/500 V • Up to Ue = 400/690 V DC-13 • Up to Ue = 24 V • Up to Ue = 60 V • Up to Ue = 125 V • Up to Ue = 250 V • Up to Ue = 480 V AC-15 • Up to Ue = 230 V • Up to Ue = 400 V DC-13 • Up to Ue = 24 V • Up to Ue = 250 V

V V V V

400/690 400/690 400 400

A A A A

6 3 2 1

A A A A

6 0.9 0.55 0.27

A A A A

6 3 2 1

A A A A A

10 2 1 0.27 0.1

A A

3 1

A A

2 0.11

Contact reliability

Short-circuit protection • Short-circuit current IK  1.1 kA

• Short-circuit current IK < 400 A

10 000 000 AC-15, 230 V • Up to 6 A • Up to 3 A • Up to 1 A • Up to 0.3 A DC-13, 24 V • Up to 6 A • Up to 3 A • Up to 0.5 A • Up to 0.2 A DC-13, 110 V • Up to 1 A • Up to 0.55 A • Up to 0.3 A • Up to 0.1 A • Up to 0.04 A DC-13, 220 V • Up to 0.3 A • Up to 0.1 A • Up to 0.05 A • Up to 0.018 A

8

External auxiliary switches, internal auxiliary switches Endurance in operating cycles • Mechanical service life • Electrical endurance

3 000 000

200 000 500 000 2 000 000 10 000 000 30 000 100 000 2 000 000 10 000 000 40 000 100 000 300 000 2 000 000 10 000 000 110 000 650 000 2 000 000 10 000 000

At 17 V and 5 mA

Oper- 1 faulty switching operation per 100 000 000 ating cycles

Fuse links, operational class gG - NEOZED type 5SE - DIAZED type 5SB - LV HRC type 3NA Miniature circuit breaker up to 230 V with C characteristic

A

10

A

10

Siemens IC 10 · 2022

8/63

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters General data Type

3RA61

3RA62

3RA64

Signaling switches Endurance in operating cycles • Mechanical service life • Electrical endurance AC-15

At 230 V and 3 A

Contact reliability

At 17 V and 5 mA

Oper- 1 faulty switching operation per 100 000 000 ating cycles

Fuse links, operational class gG - NEOZED type 5SE - DIAZED type 5SB - LV HRC type 3NA Miniature circuit breaker up to 230 V with C characteristic

A

6

A

6

A

4

Short-circuit protection • Short-circuit current IK  1.1 kA

• Short-circuit current IK < 400 A

8

Overload (short-circuit current IK  1.1 kA)

8/64

Siemens IC 10 · 2022

Fuse links, operational class gG - NEOZED type 5SE - DIAZED type 5SB - LV HRC type 3NA

20 000 6 050

3RA65

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters 3RA61, 3RA62 compact starters > 3RA61 direct-on-line starters

■ Selection and ordering data Width 45 mm

Direct-on-line start

Rated short-circuit current ICS = 53 kA at 400 V A set of 3RA6940-0A adapters is required for screw fixing. PU (UNIT, SET, M) = 1 PS* = 1 unit PG = 42F

NSB0_01946

3RA6120-1CB32 Standard three-phase motor 4-pole at 400 V AC1)

3RA6120-2EB32 Setting range for electronic overload release

Instantaneous electronic release

SD2) Article No.

A

A

d

Price SD2) Article No. per PU

Price per PU

Standard output P

kW

d

0.09

0.1 ... 0.4

56

10

3RA6120-0A@30

--

0.37

0.32 ... 1.25

56

10

3RA6120-0B@30

--

1.5

1 ... 4

56

2

3RA6120-0C@30

--

5.5

3 ... 12

168

2

3RA6120-0D@30

--

15

8 ... 32

448

2

3RA6120-0E@30

--

Screw terminals

Spring-loaded terminals

8

For use with the infeed system for 3RA6 and with the AS-i add-on module or as a replacement device, without main and control circuit terminals

For standard mounting rail or screw fixing, including 1 pair of main circuit terminals and 1 pair of control circuit terminals 0.09

0.1 ... 0.4

56

2

3RA6120-1A@32

2

3RA6120-2A@32

0.37

0.32 ... 1.25

56

2

3RA6120-1B@32

2

3RA6120-2B@32

1.5

1 ... 4

56

2

3RA6120-1C@32

2

3RA6120-2C@32

5.5

3 ... 12

168

2

3RA6120-1D@32

2

3RA6120-2D@32

15

8 ... 32

448

2

3RA6120-1E@32

2

3RA6120-2E@32

For use in the infeed system for 3RA6, without main circuit terminals, with 1 pair of control circuit terminals 0.09

0.1 ... 0.4

56

10

3RA6120-1A@33

10

3RA6120-2A@33

0.37

0.32 ... 1.25

56

2

3RA6120-1B@33

10

3RA6120-2B@33

1.5

1 ... 4

56

2

3RA6120-1C@33

2

3RA6120-2C@33

5.5

3 ... 12

168

2

3RA6120-1D@33

2

3RA6120-2D@33

15

8 ... 32

448

2

3RA6120-1E@33

2

3RA6120-2E@33

Article No. supplements for rated control supply voltage B P

• 24 V AC/DC • 110 ... 240 V AC/DC

B P

For standard mounting rail or screw fixing for use with AS-i add-on module, with 1 pair of main circuit terminals, without control circuit terminals Rated control supply voltage 24 V AC/DC 0.09

0.1 ... 0.4

56

10

3RA6120-1AB34

10

3RA6120-2AB34

0.37

0.32 ... 1.25

56

10

3RA6120-1BB34

10

3RA6120-2BB34

1.5

1 ... 4

56

10

3RA6120-1CB34

10

3RA6120-2CB34

5.5

3 ... 12

168

2

3RA6120-1DB34

10

3RA6120-2DB34

15

8 ... 32

448

10

3RA6120-1EB34

10

3RA6120-2EB34

1)

The actual starting and rated data of the motor to be protected must be considered when selecting the units. 2) Standard delivery times apply for a rated control supply voltage of 24 V AC/DC. For the other rated control supply voltages, longer delivery times are possible.

* You can order this quantity or a multiple thereof. Illustrations are approximate

Siemens IC 10 · 2022

8/65

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters 3RA61, 3RA62 compact starters > 3RA62 reversing starters

■ Selection and ordering data Width 90 mm

Reversing duty

Rated short-circuit current ICS = 53 kA at 400 V Two sets of 3RA6940-0A adapters are required for screw fixing. PU (UNIT, SET, M) = 1 PS* = 1 unit PG = 42F

NSB0_01947

3RA6250-1CP32 Standard three-phase motor 4-pole at 400 V AC1)

3RA6250-2DP32 Setting range for electronic overload release

Instantaneous electronic release

SD2) Article No.

A

A

d

Price SD2) Article No. per PU

Price per PU

Standard output P

kW

d

For use with the infeed system for 3RA6 and with the AS-i add-on module or as a replacement device, without main and control circuit terminals 0.1 ... 0.4

56

10

3RA6250-0A@30

--

0.37

0.32 ... 1.25

56

10

3RA6250-0B@30

--

1.5

1 ... 4

56

10

3RA6250-0C@30

--

5.5

3 ... 12

168

10

3RA6250-0D@30

--

15

8 ... 32

448

10

3RA6250-0E@30

--

Screw terminals

Spring-loaded terminals

8

0.09

For standard mounting rail or screw fixing, including 1 pair of main circuit terminals and 1 pair of control circuit terminals 0.09

0.1 ... 0.4

56

10

3RA6250-1A@32

10

3RA6250-2A@32

0.37

0.32 ... 1.25

56

2

3RA6250-1B@32

2

3RA6250-2B@32

1.5

1 ... 4

56

2

3RA6250-1C@32

2

3RA6250-2C@32

5.5

3 ... 12

168

2

3RA6250-1D@32

2

3RA6250-2D@32

15

8 ... 32

448

2

3RA6250-1E@32

10

3RA6250-2E@32

For use in the infeed system for 3RA6, without main circuit terminals, with 1 pair of control circuit terminals 0.09

0.1 ... 0.4

56

10

3RA6250-1A@33

10

3RA6250-2A@33

0.37

0.32 ... 1.25

56

10

3RA6250-1B@33

10

3RA6250-2B@33

1.5

1 ... 4

56

10

3RA6250-1C@33

10

3RA6250-2C@33

5.5

3 ... 12

168

10

3RA6250-1D@33

10

3RA6250-2D@33

15

8 ... 32

448

10

3RA6250-1E@33

10

3RA6250-2E@33

Article No. supplements for rated control supply voltage B P

• 24 V AC/DC • 110 ... 240 V AC/DC

B P

For standard mounting rail or screw fixing for use with AS-i add-on module, with 1 pair of main circuit terminals, without control circuit terminals Rated control supply voltage 24 V AC/DC 0.09

0.1 ... 0.4

56

10

3RA6250-1AB34

10

3RA6250-2AB34

0.37

0.32 ... 1.25

56

10

3RA6250-1BB34

10

3RA6250-2BB34

1.5

1 ... 4

56

10

3RA6250-1CB34

10

3RA6250-2CB34

5.5

3 ... 12

168

10

3RA6250-1DB34

10

3RA6250-2DB34

15

8 ... 32

448

10

3RA6250-1EB34

10

3RA6250-2EB34

1) 2)

The actual starting and rated data of the motor to be protected must be considered when selecting the units. Standard delivery times apply for a rated control supply voltage of 24 V AC/DC. For the other rated control supply voltages, longer delivery times are possible.

8/66

Siemens IC 10 · 2022

* You can order this quantity or a multiple thereof. Illustrations are approximate

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters 3RA64, 3RA65 compact starters for IO-Link > 3RA64 direct-on-line starters

■ Selection and ordering data Direct-on-line start

Rated control supply voltage 24 V DC Width 45 mm Rated short-circuit current ICS = 53 kA at 400 V A set of 3RA6940-0A adapters is required for screw fixing.

NSB0_01946

PU (UNIT, SET, M) = 1 PS* = 1 unit PG = 42F

3RA64 with 3RA6911-1A auxiliary switch Standard three-phase motor 4-pole at 400 V AC1)

Setting range for electronic overload release

Instantaneous electronic release

SD

A

A

d

Article No.

Price SD per PU

Article No.

Price per PU

Standard output P

Screw terminals kW

d

Spring-loaded terminals

For standard mounting rail or screw fixing, including 1 pair of main circuit terminals and 1 pair of control circuit terminals 0.09

0.1 ... 0.4

56

10

3RA6400-1AB42

10

3RA6400-2AB42

0.37

0.32 ... 1.25

56

10

3RA6400-1BB42

10

3RA6400-2BB42

1.5

1 ... 4

56

2

3RA6400-1CB42

2

3RA6400-2CB42

5.5

3 ... 12

168

2

3RA6400-1DB42

2

3RA6400-2DB42

15

8 ... 32

448

10

3RA6400-1EB42

10

3RA6400-2EB42

0.09

0.1 ... 0.4

56

10

3RA6400-1AB43

10

3RA6400-2AB43

0.37

0.32 ... 1.25

56

2

3RA6400-1BB43

2

3RA6400-2BB43

1.5

1 ... 4

56

2

3RA6400-1CB43

2

3RA6400-2CB43

5.5

3 ... 12

168

2

3RA6400-1DB43

2

3RA6400-2DB43

15

8 ... 32

448

10

3RA6400-1EB43

10

3RA6400-2EB43

1)

8

For use in the infeed system for 3RA6, without main circuit terminals, with 1 pair of control circuit terminals

The actual starting and rated data of the motor to be protected must be considered when selecting the units.

* You can order this quantity or a multiple thereof. Illustrations are approximate

Siemens IC 10 · 2022

8/67

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters 3RA64, 3RA65 compact starters for IO-Link > 3RA65 reversing starters

■ Selection and ordering data Reversing duty

Rated control supply voltage 24 V DC Width 90 mm Rated short-circuit current ICS = 53 kA at 400 V Two sets of 3RA6940-0A adapters are required for screw fixing.

NSB0_01947

PU (UNIT, SET, M) = 1 PS* = 1 unit PG = 42F

3RA65 with 3RA6911-1A auxiliary switch Standard three-phase motor 4-pole at 400 V AC1)

Setting range for electronic overload release

Instantaneous electronic release

SD

A

A

d

Article No.

Price SD per PU

Article No.

Price per PU

Standard output P

Screw terminals kW

d

Spring-loaded terminals

8

For standard mounting rail or screw fixing, including 1 pair of main circuit terminals and 1 pair of control circuit terminals 0.09

0.1 ... 0.4

56

10

3RA6500-1AB42

10

3RA6500-2AB42

0.37

0.32 ... 1.25

56

2

3RA6500-1BB42

10

3RA6500-2BB42

1.5

1 ... 4

56

2

3RA6500-1CB42

10

3RA6500-2CB42

5.5

3 ... 12

168

10

3RA6500-1DB42

10

3RA6500-2DB42

15

8 ... 32

448

10

3RA6500-1EB42

10

3RA6500-2EB42

For use in the infeed system for 3RA6, without main circuit terminals, with 1 pair of control circuit terminals 0.09

0.1 ... 0.4

56

10

3RA6500-1AB43

10

3RA6500-2AB43

0.37

0.32 ... 1.25

56

10

3RA6500-1BB43

10

3RA6500-2BB43

1.5

1 ... 4

56

10

3RA6500-1CB43

10

3RA6500-2CB43

5.5

3 ... 12

168

10

3RA6500-1DB43

10

3RA6500-2DB43

15

8 ... 32

448

10

3RA6500-1EB43

10

3RA6500-2EB43

1)

The actual starting and rated data of the motor to be protected must be considered when selecting the units.

8/68

Siemens IC 10 · 2022

* You can order this quantity or a multiple thereof. Illustrations are approximate

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters Accessories

■ Overview Accessories for SIRIUS 3RA6 compact starters

Busbar adapters for 60 mm systems

The following accessories are available specially for the 3RA6 compact starters: • Infeed system for 3RA6, see page 8/77 onwards • For AS-i add-on modules, see "Add-on modules for AS-Interface", page 8/75 onwards • External auxiliary switches: Snap-on auxiliary switch as versions 2 NO, 2 NC and 1 NO + 1 NC with screw or springloaded terminals; the contacts of the auxiliary switch open and close jointly with the main contacts of the compact starter. The NC contacts are designed as mirror contacts. • Control kit: Aid for manually closing the main contacts to check the wiring and motor direction under conditions of short-circuit protection • Adapter for screw fixing the compact starter, including push-in lugs • Main circuit terminal: Available with screw and spring-loaded terminals • Main circuit terminals mixed connection method: With the main circuit terminals mixed connection method it is also possible in the main circuit to switch from screw terminals on the line side to spring-loaded terminals on the outgoing side. This enables, for example, the side-by-side mounting of several compact starters and their cost-efficient connection using 3-phase busbars on the infeed side. The motors are then connected directly by the quick and reliably contacting spring-loaded terminals.

The compact starters are mounted directly with the aid of busbar adapters on busbar systems with 60 mm center-to-center clearance in order to save space and to reduce infeed times and costs. These feeders are suitable for copper busbars with a width from 12 to 30 mm. The busbars can be 4 to 5 mm or 10 mm thick.

The terminal block for "Self-Protected Combination Motor Controller", Type E is available for complying with the clearances and creepage distances demanded according to UL 508.

The "reversing starter" version requires a device holder alongside the busbar adapter for lateral mounting. The compact starters are snapped onto the adapter and connected on the line side. This prepared unit is then plugged directly onto the busbar system, and is thus connected both mechanically and electrically at the same time. For further accessories such as incoming and outgoing terminals, flat copper profiles etc., see Catalog LV 10. Accessories for operation with closed control cabinet doors Door-coupling rotary operating mechanisms for standard and EMERGENCY STOP applications are available for operating the compact starter with closed control cabinet doors. Accessories for SIRIUS 3RA6 compact starters in IO-Link version The following accessories are available specially for the 3RA64, 3RA65 compact starters: • Additional connecting cables for side-by-side mounting of up to four compact starters • Operator panel for on-site control and diagnostics of up to four compact starters coupled to each other

Accessories for infeed using 3-phase busbar systems The 3RV1915-1.B 3-phase busbars can be used as an easy, time-saving and clearly arranged means of feeding SIRIUS 3RA6 compact starters with screw terminals. Motor starter protector sizes S00 and S0 can also be integrated. The busbars are suitable for between two and five devices. However, any kind of extension up to a maximum summation current of 63 A is possible by clamping the connection tags of an additional busbar (rotated 180°) underneath the terminals of the respective last motor starter protector. Motor starter protectors S00 and S0 of the 3RV2 series can be combined in any way. The motor starter protectors are supplied by appropriate infeed terminals. Special infeed terminals are required for constructing "Starters (Type E)" according to UL/CSA. The 3-phase busbar systems have touch protection but empty connection tags must be fitted with covers. They are designed for any short-circuit stress which can occur at the output side of connected SIRIUS 3RA6 compact starters or motor starter protectors.

Siemens IC 10 · 2022

8/69

8

Accessories for UL applications

The 8US busbar system can be loaded with a maximum summation current of 630 A.

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters Accessories

■ Selection and ordering data Version

SD

Article No.

Price per PU

PU (UNIT, SET, M)

PS*

PG

d

Accessories specially for 3RA6 compact starters Control kit

15

3RA6950-0A

1

1 unit

42F

15

3RA6940-0A

1

1 unit

42F

For mechanical actuation of the compact starter

3RA6950-0A Adapters for screw fixing the compact starter (set including push-in lugs) Direct-on-line starters require one set, reversing starters two sets.

3RA6940-0A Screw terminals Auxiliary switches for compact starters • 2 NO

2

3RA6911-1A

1

1 unit

42F

• 2 NC

2

3RA6912-1A

1

1 unit

42F

• 1 NO +1 NC (these auxiliary contacts are force-guided)

2

3RA6913-1A

1

1 unit

42F

Main circuit terminals (incoming and outgoing side)

2

3RA6920-1A

1

1 unit

42F

Control circuit terminals (1 set consisting of 2 terminals) • For 3RA61

2

3RA6920-1B

1

1 unit

42F

• For 3RA62

2

3RA6920-1C

1

1 unit

42F

8

3RA6911-1A

3RA6920-1A

3RA6920-1B Spring-loaded terminals Auxiliary switches for compact starters • 2 NO

2

3RA6911-2A

1

1 unit

42F

• 2 NC

2

3RA6912-2A

1

1 unit

42F

• 1 NO +1 NC (these auxiliary contacts are force-guided)

2

3RA6913-2A

1

1 unit

42F

Main circuit terminals (incoming and outgoing side)

2

3RA6920-2A

1

1 unit

42F

Control circuit terminals (1 set consisting of 2 terminals) • For 3RA61

2

3RA6920-2B

1

1 unit

42F

• For 3RA62

2

3RA6920-2C

1

1 unit

42F

3RA6911-2A

3RA6920-2A

3RA6920-2B

8/70

Siemens IC 10 · 2022

* You can order this quantity or a multiple thereof. Illustrations are approximate

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters Accessories Version

SD

Article No.

Price per PU

PU (UNIT, SET, M)

PS*

PG

1

1 unit

42F

PU (UNIT, SET, M)

PS*

PG

d

Accessories specially for 3RA6 compact starters (continued) Main circuit terminals, mixed connection method

20

3RA6920-3A

SD

Article No.

1 set comprises: • 1 joint block on the line side with screw terminals • 1 joint block on the outgoing side with spring-loaded terminals

3RA6920-3A

Version

Price per PU

d

Accessories specially for 3RA64, 3RA65 compact starters for IO-Link

15 15

3RA6932-0A 3RA6933-0B

1 1

5 units 5 units

42F 42F

• 14-pole - 8 mm2) - 200 mm

15 15

3RA6931-0A 3RA6933-0C

1 1

5 units 5 units

42F 42F

Operator panels (set) • 1 operator panel • 1 enabling module • 1 interface cover • 1 fixing terminal

10

3RA6935-0A

1

1 unit

42F

Enabling modules (replacement)

10

3RA6936-0A

1

1 unit

42F

Interface covers (replacement)

10

3RA6936-0B

1

5 units

42F

Connecting cables (round) For connecting the operator panel 10-pole, 2 000 mm

15

3RA6933-0A

1

1 unit

42F

SD

Article No.

PU (UNIT, SET, M)

PS*

PG

1

1 unit

41E

8

3RA6931-0A

Additional connecting cables (flat) for side-by-side mounting of up to 4 compact starters • 10-pole - 8 mm1) - 200 mm1)

3RA6935-0A

1)

10-pole connecting cables are required for EMERGENCY STOP group concepts. 2) Is included in the scope of supply of the SIRIUS 3RA6 compact starter in IO-Link version.

For matching IO-Link masters, see page 2/97 onwards. Version

Price per PU

d

Terminals for "Self-Protected Combination Motor Controllers (Type E)" acc. to UL 508 for infeed through parallel wiring with compact starters Terminal blocks Type E For extended clearances and creepage distances (1 and 2 inch)

}

3RV2928-1H

Note: 3RV2928-1H

UL 508 demands 1-inch clearance and 2-inch creepage distance at line side for "Combination motor controller (Type E)". Terminal blocks are not required for use according to CSA. These terminal blocks cannot be used in combination with 3RV19.5 3-phase busbars.

* You can order this quantity or a multiple thereof. Illustrations are approximate

Siemens IC 10 · 2022

8/71

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters Accessories Number of compact Modular starters and motor starter spacing protectors that can be connected

Rated For motor SD current In starter at 690 V protectors

Article No.

Price per PU

PU (UNIT, SET, M)

PS*

PG

1 1 1 1

1 unit 1 unit 1 unit 1 unit

41E 41E 41E 41E

PU (UNIT, SET, M)

PS*

PG

1 10 units

41E

Without lateral accessories mm

A

Size

d

3-phase busbars for infeed with 3RA6

3RV1915-1AB

3RV1915-1BB

For feeding several compact starters and/or motor starter protectors with screw terminals, mounted side-by-side on standard mounting rails, insulated, with touch protection. 2 3 4 5

45 45 45 45

S00, S01) S00, S01) S00, S01) S00, S01)

63 63 63 63

} } } }

3RV1915-1AB 3RV1915-1BB 3RV1915-1CB 3RV1915-1DB

Article No.

3RV1915-1CB

3RV1915-1DB 1)

Not suitable for 3RV21 motor starter protectors for motor protection with overload relay function and for 3RV27 and 3RV28 circuit breakers according to UL 489/CSA C22.2 No. 5.

Version

Modular spacing

For motor starter protectors

SD

mm

Size

d

S00, S0

}

3RV1915-6AB

Article No.

Price per PU

Covers for connection tags of the 3-phase busbars

8

Touch protection for empty positions

--

3RV1915-6AB

Conductor cross-section

Tightening torque Solid or Finely AWG stranded stranded cables, solid with end or stranded sleeve

For compact starters and motor starter protectors

SD

mm²

Size

d

mm²

AWG

Nm

Price per PU

PU (UNIT, SET, M)

PS*

PG

3-phase infeed terminals for 3-phase busbars according to IEC and for constructing "Starters (Type E)" according to UL 508 Connection from top 2.5 ... 25 2.5 … 16 10 ... 4

3 ... 4

S00, S0

2

3RV2925-5EB

1

1 unit

41E

Input: 4; Output: 2 ... 2.5

S00, S0

}

3RV2915-5B

1

1 unit

41E

3RV2925-5EB

3-phase infeed terminals for 3-phase busbars Connection from below1) 2.5 ... 25 2.5 … 16 10 ... 4

3RV2915-5B 1)

This terminal is connected in place of a compact starter, please take the space requirement (45 mm) into account.

8/72

Siemens IC 10 · 2022

* You can order this quantity or a multiple thereof. Illustrations are approximate

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters Accessories Version

SD

Article No.

Price per PU

PU (UNIT, SET, M)

PS*

PG

d

Busbar adapters for 60 mm systems For flat copper profiles according to DIN 46433 Width: 12 ... 30 mm Thickness: 4 ... 5 mm or 10 mm

2

8US1211-1NS10

1

1 unit

14O

2

8US1250-1AA10

1

1 unit

14O

PU (UNIT, SET, M)

PS*

PG

8US1211-1NS10

Device holders for lateral mounting alongside the busbar adapter for 60 mm systems Required in addition to the busbar adapter for mounting a reversing starter

Version

Color of actuator

Version of SD extension shaft mm

Article No.

Price per PU

8

8US1250-1AA10

d

Door-coupling rotary operating mechanisms for operating the compact starter with closed control cabinet doors The door-coupling rotary operating mechanisms consist of a selector, a coupling driver and a 130 mm long extension shaft (6 mm x 6 mm). The door-coupling rotary operating mechanisms are designed to degree of protection IP64. The door interlocking prevents accidental opening of the control cabinet door in the ON position of the motor starter protector. The OFF position can be locked with up to 3 padlocks. 3RV2926-0B

Door-coupling rotary operating mechanisms

Black

130

}

3RV2926-0B

1

1 unit

41E

EMERGENCY STOP door-coupling rotary operating mechanisms

Red/yellow

130

}

3RV2926-0C

1

1 unit

41E

* You can order this quantity or a multiple thereof. Illustrations are approximate

Siemens IC 10 · 2022

8/73

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters Accessories Version

SD

Article No.

Price per PU

PU (UNIT, SET, M)

PS*

PG

1

1 unit

41B

100 340 units

41B

d

Tools for opening spring-loaded terminals Screwdrivers For all SIRIUS devices with spring-loaded terminals

3RA2908-1A

Spring-loaded terminals

Length approx. 200 mm, 3.0 mm x 0.5 mm, titanium gray/black, partially insulated

2

3RA2908-1A

Unit labeling plates1) For SIRIUS devices 20 mm x 7 mm, titanium gray

20

3RT2900-1SB20

IC01_00181

Blank labels

3RT2900-1SB20

Manuals System Manual for 3RA6 compact starter and infeed system for the 3RA6, see https://support.industry.siemens.com/cs/ww/en/view/27865747 PC labeling system for individual inscription of unit labeling plates available from: murrplastik Systemtechnik GmbH (see page 16/16).

8

1)

8/74

Siemens IC 10 · 2022

* You can order this quantity or a multiple thereof. Illustrations are approximate

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters Add-on modules for AS-Interface

■ Overview

The AS-i add-on modules can be combined only in connection with compact starters with a rated control supply voltage of 24 V AC/DC. AS-i add-on module for local control

D0

AS-i

3RA6120-..B3.

D1

AS-i

Y4

Y2

AUX PWR -

With this new module it is also possible for the connected compact starter to be operated directly using simple switches, i.e. without recourse to AS-i communication, if required.

S1

+

S2

3RA6970-3F

Automatic- 0 - Manual Switch with 3 switch positions Shown in "0" position

"Automatic" mode NC contacts can be connected to the inputs Y2 and Y4 through the local terminals on the AS-i add-on module. If the "+" terminals are connected simultaneously to both local inputs, the AS-i add-on module will be in "Automatic" mode, i.e. it will communicate with the control system through AS-Interface.

S0

+

AUX PWR +

Switch with 3 switch positions Switch

Automatic

0

Manual

S0

Closed

Open

Open

S1

Closed

Open

Open

S2

Open

Open

Closed

NSB0_02096a

Various AS-i add-on modules are available for communication of the 3RA6 compact starter with the control system using AS-Interface: • Standard version • With two local inputs • With two free external inputs • With one free external input and one free external output • With two free external outputs • For local control

Local control Circuit diagram example for controlling a 3RA6120 direct-on-line starter using an AS-i add-on module for local control

8

Opening the two inputs Y2 and Y4 will result in the direct disconnection of the compact starter. Operation through AS-i communication is finished and the compact starter can now be switched on and off directly using NO contacts (one NO contact per direction of rotation on the reversing starter).

AS-i

D0

"LED AUX Power" must light up green, the 24 V DC supply must be ensured and the AS-i control supply voltage must no longer be applied. Resetting to "Automatic" mode

3RA6250-..B3.

D1

AS-i

If a "1" signal is simultaneously applied at the local inputs, the availability bit DI 0 is switched to a "1" signal.

S4

Y4 S0

+

AUX PWR +

Y2

AUX PWR -

S1

+

S3 S2

3RA6970-3F

Automatic- 0 - Manual Switch with 3 switch positions Shown in "0" and "Right" position

Switch with 3 switch positions Switch

Automatic

0

Manual

S0

Closed

Open

Open

S1

Closed

Open

Open

S2

Open

Open

Closed

Switch with 2 switch positions Switch

LEFT

RIGHT

S3

Open

Closed

S4

Closed

Open

NSB0_02097a

If AS-i communication is reset, the motor is first switched off and then on again when requested by the control system.

Switch with 2 switch positions

LEFT - RIGHT

Circuit diagram example for controlling a 3RA6250 reversing starter using an AS-i add-on module for local control

Siemens IC 10 · 2022

8/75

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters Add-on modules for AS-Interface

■ Selection and ordering data Version

SD

Article No.

Price per PU

PU (UNIT, SET, M)

PS*

PG

d

AS-i add-on modules 2

3RA6970-3A

1

1 unit

42F

2

3RA6970-3B

1

1 unit

42F

2

3RA6970-3C

1

1 unit

42F

2

3RA6970-3D

1

1 unit

42F

2

3RA6970-3E

1

1 unit

42F

2

3RA6970-3F

1

1 unit

42F

• Flat, yellow, extender

10

3RK1901-0NA00

1

5 units

42C

• Flat, black, extender

10

3RK1901-0PA00

1

5 units

42C

3RK1904-2AB02

1

1 unit

42C

Standard version For communication of the compact starter with the control system using AS-Interface With two local inputs For safe disconnection through local safety relays, e.g. cable-operated switches

3RA6970-3A

With two free external inputs Replaces the digital standard inputs "Motor On" and "Group warning" With one free external input and one free external output Replaces the digital standard input "Group warning" 3RA6970-3B to -3F

With two free external outputs Only for direct-on-line starters, replaces the digital standard output "Motor CCW" For local control Control of the compact starter optionally using AS-Interface or local switches

Spare parts for AS-i add-on modules

8

Connection plugs for data and auxiliary supply cable With 2 insulation displacement terminations for standard stranded wires 2 x 0.5 ... 0.75 mm2

3RK1901-0NA00, 3RK1901-0PA00

Accessories for AS-i add-on modules AS-Interface addressing unit V3.0 2 • For AS-Interface modules and sensors and actuators with integrated AS-Interface according to AS-i specification V3.0 • For setting the AS-i address of standard slaves, and slaves with extended addressing mode (A/B slaves) • With input/output test function and many other commissioning functions • Battery operation with four type AA batteries (IEC LR6, NEDA 15) • Scope of supply: - Addressing unit with four batteries - Addressing cable, with M12 plug to addressing plug (hollow plug), length 1.5 m 3RK1904-2AB02

For matching AS-Interface masters, routers and power supply units, see pages 2/29, 2/41 and 2/67 onwards.

8/76

Siemens IC 10 · 2022

* You can order this quantity or a multiple thereof. Illustrations are approximate

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters Infeed system for 3RA6

■ Overview More information Homepage, see www.siemens.com/sirius-infeed-system

Online configurator, see www.siemens.com/sirius/configurators

Industry Mall, see www.siemens.com/product?3RA68

The infeed system for 3RA6 compact starters enables far less wiring in the main circuit and, thanks to the easy exchangeability of the compact starters, reduces the usual downtimes for maintenance work during the plant's operating phase. The infeed system provides the possibility of completely prewiring

the main circuit without a compact starter needing to be connected at the same time. As the result of the removable terminals in the main circuit, compact starters can be integrated in an infeed system in easy manner (without the use of tools).

2 3 4

1 9

8

5

8

IC01_00648

6

7

11 12 10 1

Infeed terminal

7

PE pick-off

2

3-socket expansion module

8

Connecting wedges

3

2-socket expansion module

9

End cover

4

Expansion plug

10 45 mm adapter for SIRIUS motor starter protector size S0

5

PE infeed

11 3RA61 direct-on-line starter

6

PE expansion plug

12 3RA62 reversing starter

Infeed system for 3RA6 compact starters

Siemens IC 10 · 2022

8/77

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters Infeed system for 3RA6 In addition, the integrated PE bar means it is optionally possible to connect the motor cable directly to the infeed system without additional intermediate terminals. The infeed system for 3RA6 compact starters is designed for summation currents up to 100 A with a maximum conductor cross-section of up to 70 mm² on the infeed terminal block. The infeed system can be mounted on a standard mounting rail or flat surfaces.

$ Infeed

The PE pick-off is available with screw terminals and spring-loaded terminals (6/10 mm2). It is snapped into the infeed system from below.

, Connecting wedges Two connecting wedges are used to hold together two expansion modules.

- End covers

The 3-phase infeed is available as an infeed with screw terminal (25/35 mm2 up to 63 A or 50/70 mm2 up to 100 A) and as an infeed with spring-loaded terminal (25/35 mm2 up to 63 A).

On the last expansion module of a row, the socket provided for the expansion plug can be covered by inserting the end cover.

The infeed with spring-loaded terminal can be fitted on the left as well as on the right of an expansion module.

. 45 mm adapter for SIRIUS 3RV1/3RV2 motor starter

The infeed with screw terminal is supplied only with a 3-socket expansion module and permanently fitted on the left side.

SIRIUS 3RV1 and 3RV2 motor starter protectors size S0 with screw terminals can be fitted to the adapter, enabling them to be plugged into the infeed system.

The infeeds with screw terminal enable connection of the main conductors (L1, L2, L3) either from above or from below. The infeed with screw terminal is supplied complete with one end cover, the infeed with spring-loaded terminal complete with two end covers.

% 3-socket expansion module The expansion module with three sockets for compact starters is available with screw terminals and with spring-loaded terminals. Expansion modules enable the infeed system to be expanded and can be fitted to each other in any number.

8

+ PE pick-off

Two expansion modules are held together with the help of two connecting wedges and one expansion plug. These assembly parts are included in the scope of supply of the respective expansion module. When the infeed system for 3RA6 compact starters is used, the compact starters (plug-in modules) are easily assembled and disassembled even when live.

protector

Terminal covers for increasing finger-safety on the front Universally configured terminal covers are available for the 25/35 mm2 and 50/70 mm2 3-phase infeeds with screw terminal: • 3RA6880-2AB terminal covers for infeeds with screw terminal 25/35 mm2 (3RA6812-8AB/AC) • 3RA6880-3AB terminal covers for infeeds with screw terminal 50/70 mm2 (3RA6813-8AB/AC) The terminal covers can be used in two ways on the infeed terminals of the infeeds with screw terminal 25/35 mm² and 50/70 mm² (see illustration): • If the terminals are connected, the cables are also covered: - by approx. 14 mm with the 3RA6880-2AB - by approx. 18 mm with the 3RA6880-3AB • On clamping points without connected cables, the covers can be turned once and then pushed over the clamping points for finger-safe covering of the metal parts.

Optional possibilities: • PE connection on motor outgoing side • Outfeed for external auxiliary devices • Connection to 3RV29 infeed system • Integration of SIRIUS 3RV1 and 3RV2 motor starter protectors size S0 up to 25 A (using 3RA6890-0BA adapter)

& 2-socket expansion module If only two instead of three additional sockets are required, then the 2-socket expansion module is the right choice. It has the same functionality as the 3-socket expansion module.

( Expansion plug Two expansion modules can be connected together using the expansion plug. Flexible expansion of the infeed system is thus possible.

) PE infeed This module enables a PE cable to be connected. The PE infeed can be ordered with screw terminals and springloaded terminals (35 mm2) and can be fitted on the left or right of the expansion block.

* PE expansion plug The PE expansion plug is inserted from below and enables two PE bars to be connected.

8/78

Siemens IC 10 · 2022

Use of the 3RA6880-2AB terminal cover on the infeed with screw terminal 25/35 mm² (3RA6812-8AB/AC). The upper cover increases the fingersafety for the connected conductors. The identical lower cover is turned for use and prevents touching of the voltage-carrying metal parts of the infeed terminal. For better recognition, the covers are shown as transparent in this illustration and not in their original color.

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters Infeed system for 3RA6 Terminal blocks

Proposal for upstream short-circuit protection devices

Using the terminal block the three phases can be fed out of the system; this means that 1-phase, 2-phase and 3-phase components can also be integrated in the system.

The following short-circuit data apply for the components of the infeed system for 3RA6 compact starters:

After the end cover is pulled out, the terminal block can be plugged onto an expansion module.

Conductor crosssection

Maximum let-through current Id,max and current integral I2t

Proposal for upstream short-circuit protection device

Expansion plug for SIRIUS 3RV29 infeed systems After the end cover is pulled out, the expansion plug for the SIRIUS 3RV29 infeed system can be plugged onto an expansion module. It connects the infeed system for 3RA6 compact starters with the SIRIUS 3RV29 infeed system.

The following maximum rated operational currents apply for the components of the infeed system for 3RA6: Component

circuit

mm²

kA

Short-circuit protection for 3RA681.-8A. infeed with screw terminal (25/35 mm2 and 50/70 mm2) 2.5 ... 35, Id, max < 21 kA, I²t = 530 kA²s 2.5 ... 70

Maximum rated operational current

Maximum rated operational current

Maximum prospective Ishort-

3RV2041-4MA10 (LV HRC gG 3NA3; 315 A)

50

Short-circuit protection for infeed with spring-loaded terminal 25/35 mm2, 3RA6830-5AC 4

Id, max < 9.5 kA, I²t = 85 kA²s

3RV2021-4DA10

40

A

6

30

Infeed with screw terminal 50/70 mm²

100

Id, max < 12.5 kA, I²t = 140 kA²s 3RV2031-4EA10

10

3RV2031-4WA10

25

Infeed with screw terminal 25/35 mm²

63

Id, max < 15 kA, I²t = 180 kA²s

16/25

3RV2031-4JA10

65

Infeed with spring-loaded terminal 25/35 mm²

63

Id, max < 19 kA, I²t = 440 kA²s

3RV2041-4JA10

65

Expansion plug

63

3RV2041-4MA10 (LV HRC gG 3NA3; 315 A)

50

Id, max < 21 kA, I²t = 530 kA²s

Short-circuit protection for terminal block, 3RV2917-5D 1.5

Id, max < 7.5 kA

5SY...

2.5

Id, max < 9.5 kA

1)

4

Id, max < 9.5 kA

6 1)

8

With side-by-side mounting of several expansion modules, the maximum rated operational current from the second expansion module to the end of the row is 63 A.

35

Id, max < 12.5 kA To prevent the possibility of short circuits, the cables on the terminal block must be installed so that they are short-circuit-proof.

Siemens IC 10 · 2022

8/79

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters Infeed system for 3RA6

■ Selection and ordering data Version

SD

Article No.

Price per PU

PU (UNIT, SET, M)

PS*

PG

1

1 unit

42F

1

1 unit

42F

1

1 unit

42F

1

1 unit

42F

1

1 unit

42F

d

3-phase infeeds and expansion modules Infeeds with screw terminal 25/35 mm2 left Infeed with screw terminal at line side with a permanently fitted 3-socket expansion module with screw or spring-loaded terminals on the outgoing side and integrated PE bar Expansion module with 3 sockets for 3 direct-on-line starters or 1 direct-on-line starter and 1 reversing starter Screw terminals 3RA6812-8AB

• Screw terminals on the outgoing side

2

3RA6812-8AB Spring-loaded terminals

• Spring-loaded terminals on the outgoing side

2

3RA6812-8AC

3RA6812-8AC

Infeeds with screw terminal 50/70 mm2 left

8

Infeed with screw terminal at line side with a permanently fitted 3-socket expansion module with screw or spring-loaded terminals on the outgoing side and integrated PE bar

3RA6813-8AB

Expansion module with 3 sockets for 3 direct-on-line starters or 1 direct-on-line starter and 1 reversing starter, suitable for UL operation according to UL 508 Type E Screw terminals • Screw terminals on the outgoing side

2

3RA6813-8AB Spring-loaded terminals

• Spring-loaded terminals on the outgoing side

2

3RA6813-8AC

3RA6813-8AC

Infeed with spring-loaded terminal 25/35 mm2 left or right Spring-loaded terminals Up to 63 A

2

3RA6830-5AC

3RA6830-5AC

8/80

Siemens IC 10 · 2022

* You can order this quantity or a multiple thereof. Illustrations are approximate

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters Infeed system for 3RA6 Version

SD

Article No.

Price per PU

PU (UNIT, SET, M)

PS*

PG

1

1 unit

42F

1

1 unit

42F

1

1 unit

42F

1

1 unit

42F

d

Expansion modules 2-socket expansion modules With screw or spring-loaded terminals and integrated PE bar With 2 sockets for 2 direct-on-line starters or 1 reversing starter Expansion plug and 2 connecting wedges are included in the scope of supply. Screw terminals 3RA6822-0AB

• Version with screw terminals

2

3RA6822-0AB Spring-loaded terminals

• Version with spring-loaded terminals

2

3RA6822-0AC

3RA6822-0AC

3-socket expansion modules With screw or spring-loaded terminals and integrated PE bar With 3 sockets for 3 direct-on-line starters or 1 direct-on-line starter and 1 reversing starter Expansion plug and 2 connecting wedges are included in the scope of supply.

3RA6823-0AB

• Version with screw terminals

2

3RA6823-0AB

8

Screw terminals

Spring-loaded terminals • Version with spring-loaded terminals

2

3RA6823-0AC

3RA6823-0AC

* You can order this quantity or a multiple thereof. Illustrations are approximate

Siemens IC 10 · 2022

8/81

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters Infeed system for 3RA6 Version

SD

Article No.

Price per PU

PU (UNIT, SET, M)

PS*

PG

1

1 unit

42F

1

1 unit

42F

1

1 unit

42F

d

Accessories for infeed systems for 3RA6 PE infeeds, 25/35 mm2 Screw terminals • Version with screw terminals

2

3RA6860-6AB

3RA6860-6AB Spring-loaded terminals • Version with spring-loaded terminals

2

3RA6860-5AC

3RA6860-5AC

PE pick-offs 6/10 mm2 Screw terminals 2

3RA6870-4AB

8

• Version with screw terminals

3RA6870-4AB Spring-loaded terminals • Version with spring-loaded terminals

2

3RA6870-3AC

1

1 unit

42F

PE expansion plugs

2

3RA6890-0EA

1

1 unit

42F

Expansion plugs Between 2 expansion modules

2

3RA6890-1AB

1

1 unit

42F

2

3RA6890-1AA

1

1 unit

42F

3RA6870-3AC

Expansion plugs

3RA6890-0EA

Included in the scope of supply of the expansion modules

3RA6890-1AB Expansion plugs for SIRIUS 3RV29 infeed system Connects infeed system for 3RA6 to 3RV29 infeed system

3RA6890-1AA

8/82

Siemens IC 10 · 2022

* You can order this quantity or a multiple thereof. Illustrations are approximate

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RA6 compact starters Infeed system for 3RA6 Version

SD

Article No.

Price per PU

PU (UNIT, SET, M)

PS*

PG

d

Accessories for infeed systems for 3RA6 (continued) 45 mm adapters For SIRIUS 3RV1.2 and 3RV2.2 motor starter protectors/circuit breakers size S0 up to 25 A • Screw terminals (conductor cross-section AWG 10)

Screw terminals 2

3RA6890-0BA

1

1 unit

42F

2

3RA6880-2AB

1

1 unit

42F

2

3RA6880-3AB

1

1 unit

42F

1

1 unit

41E

1

1 unit

41B

3RA6890-0BA

Terminal covers for infeeds with screw terminal IP20 terminal covers for infeeds with screw terminal 25/35 mm² (3RA6812-8AB/AC) (2 units per pack)

3RA6880-2AB IP20 terminal covers for infeeds with screw terminal 50/70 mm² (3RA6813-8AB/AC) (2 units per pack)

8

3RA6880-3AB

Terminal blocks For integration of 1-phase, 2-phase and 3-phase external components • Spring-loaded terminals

Spring-loaded terminals }

3RV2917-5D

3RV2917-5D

Tools for opening spring-loaded terminals Screwdrivers For all SIRIUS devices with spring-loaded terminals

3RA2908-1A

Length approx. 200 mm, 3.0 mm x 0.5 mm, titanium gray/black, partially insulated

Spring-loaded terminals 2

3RA2908-1A

Manuals System Manual for 3RA6 compact starter and infeed system for the 3RA6, see https://support.industry.siemens.com/cs/ww/en/view/27865747

* You can order this quantity or a multiple thereof. Illustrations are approximate

Siemens IC 10 · 2022

8/83

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RM1 motor starters

■ Overview Seamlessly integrated safety right through to the main circuit

3RM13 motor starter with reversing functionality, electronic overload protection and safety-related shutdown

3RM1 motor starters: • Homepage, see www.siemens.com/sirius-motor-starter-3RM1 • Industry Mall, see www.siemens.com/product?3RM1

3SK + 3RM1

3SK safety relays for protecting the 3RM1 motor starters: • Homepage, see www.siemens.com/safety-relays • Industry Mall, see www.siemens.com/product?3SK

IC01_00533

More information

8

TIA Selection Tool Cloud (TST Cloud), see www.siemens.com/tstcloud/?node=MotorStarter3RM1

SIRIUS 3RM1 motor starters are compact devices, 22.5 mm wide, combining a large number of functions in a single enclosure. They consist of combinations of relay contacts, power semiconductors (hybrid technology), and an electronic overload relay for operational switching of three-phase motors up to 3 kW (at 400 V) and resistive loads up to 10 A at AC voltages up to 500 V. The 3RM1 motor starters with overload protection with wide setting range are available as direct-on-line starters and reversing starters and as versions with safety-related shutdown up to SIL 3 and PL e.

Video: SIRIUS 3RM1 motor starters – Compact, economical, simple

Problem-free integration of functional safety into the main circuit through the simple combination of 3RM1 and 3SK devices

Functional safety in the main circuit needs to be both simple and flexible. The unique compatibility of hybrid 3RM1 fail-safe motor starters and 3SK safety relays means that integrated functional safety right through to the main circuit is no longer a problem. Their compact design allows the motor starters to be installed to the right of the safety relay in a simple manner, just like an output expansion. The wiring of the safety-related signals to the relay can be performed simply, quickly and in an error-free manner using the device connector. The ergonomically designed enclosure with removable terminals and terminal labeling in the hinged cover allows for the cables to be conveniently diagonally mounted from the front. Either screw or spring-loaded terminals with push-in technology are available. Highlights • Fail-safe disconnection of motors up to 3 kW • Problem-free combination of fail-safe motor starters and safety relays • End-to-end system, simple setup using device connectors • Ergonomic enclosure Note: For SIRIUS 3SK safety relays, see page 11/13.

8/84

Siemens IC 10 · 2022

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RM1 motor starters Article No. scheme Product versions

Article number

Product function

Direct-on-line starters Failsafe direct-on-line starters Reversing starters Failsafe reversing starters

Wide setting range for electronic overload release

0.1 ... 0.5 A 0.4 ... 2.0 A 1.6 ... 7.0 A (10 A)1)

Connection method

Screw terminals Spring-loaded terminals (push-in) Mixed connection method

Rated control supply voltage Us

0 0 0 0

@ @ @ @

– – – –

@ @ @ @

AA AA AA AA

@ @ @ @

4 4 with ATEX certification and safety-related shutdown 4 4 with ATEX certification and safety-related shutdown For motor standard output 0 ... 0.12 kW2) For motor standard output 0.09 ... 0.75 kW2) For motor standard output 0.55 ... 3 kW2)

1 2 7 1 2

Spring-loaded terminals (push-in)

3

24 V DC 110 ... 230 V AC, 110 V DC

Example 1)

3RM10 3RM11 3RM12 3RM13

0 1 3RM13 0 1 – 2 AA 0 4

Operation of resistive loads with up to 10 A.

2)

Standard three-phase motor, basis 4-pole at 400 V AC; the actual starting and rated data of the motor to be protected must be considered when selecting the units.

Note: The Article No. scheme shows an overview of product versions for better understanding of the logic behind the article numbers.

For your orders, please use the article numbers quoted in the selection and ordering data.

■ Benefits Standards and approvals • IEC/EN 60947-4-2 • UL 60947-4-2 • CSA • ATEX • IEC 61508: SIL 3 • IEC 62061: SIL 3 • ISO 13849-1: PL e • CCC approval for China

8

• Less space required in the control cabinet (20 to 80%) thanks to high functional density, which also means reduced wiring and testing • Greater endurance and reduced heat losses thanks to hybrid technology • Lower costs for stock keeping and configuration as a result of the wide setting range of the electronic overload release (up to 1:5) • Fast wiring without tools for rigid conductors or conductors equipped with end sleeves thanks to spring-loaded terminals (push-in) • Safety-related shutdown in accordance with SIL 3 / PL e by shutting down the control supply voltage without additional devices in the main circuit • The motor starters can be ideally combined with 3SK safety relays for safety-related shutdown (see page 11/13) • Motor status feedback to the higher-level control system in the case of 3RM10 and 3RM12 motor starters in the 24 V DC version • Virtually error-free wiring on the mains connection side and reduction in short-circuit protective devices by means of 3RM19 infeed system • ATEX certification of the overload protection of the 3RM1 Failsafe motor starters: "Increased safety" type of protection EEx e according to ATEX directive 2014/34/EU • The 3RM1 motor starters can be used with highly energyefficient IE3/IE4 motors. In this regard, please observe the information on dimensioning and configuring, see Application Manual. For more information about IE3/IE4, see page 1/8.

Siemens IC 10 · 2022

8/85

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RM1 motor starters

■ Technical specifications More information Industry Mall, see www.siemens.com/product?3RM1

FAQs, see https://support.industry.siemens.com/cs/ww/en/ps/16311/faq

Equipment Manual, see https://support.industry.siemens.com/cs/ww/en/view/66295730 Type

3RM10, 3RM12

3RM11, 3RM13

General technical specifications Dimensions (W x H x D)

mm

22.5 x 100 x 141.6

Ambient temperature • During operation • During storage • During transport

°C °C °C

-25 … +60 -40 … +70 -40 … +70

m

4 000

Installation altitude at height above sea level, maximum

2 000

6 g / 11 ms

Shock resistance

1 ... 6 Hz, 15 mm; 20 m/s², 500 Hz

Vibration resistance Degree of protection IP on the front

According to IEC 60529

IP20

Touch protection on the front

According to IEC 60529

Finger-safe for vertical touching from the front Vertical, horizontal, standing (consider derating)

IC01_00469

Mounting position

Type

3RM1.01

3RM1.02

3RM1.07

2

7

0.4 ... 2

1.6 ... 7

8

Main circuit Operational voltage, rated value, maximum

V

500

Operating frequency

Hz

50/60

Operational current at AC-53a at 400 V at an ambient temperature of 40 °C

A

0.5

Minimum load [%]

%

20

Adjustable current response value of the inverse-time delayed overload release

A

0.1 ... 0.5

Type

3RM1.0.-.AA04

3RM1.0.-.AA14

DC

AC/DC

Control circuit Type of voltage of the control supply voltage Control supply voltage • At DC • At AC at 50 Hz

V V

24 --

110 110 … 230

Frequency of the control supply voltage

Hz

--

50/60

8/86

Siemens IC 10 · 2022

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RM1 motor starters Type

3RM1.0.-1AA.4

3RM1.0.-3AA.4

3RM1.0.-2AA.4

Connections/terminals Type of electrical connection for main circuit (1 or 2 conductors can be connected) Connectable conductor cross-section for main contacts • Solid • Finely stranded - With end sleeve - Without end sleeve

Screw terminals

Spring-loaded terminals (push-in)

mm²

1 x (0.5 ... 4), 2 x (0.5 ... 2.5)

1 x (0.5 ... 4)

mm² mm²

1 x (0.5 ... 4), 2 x (0.5 ... 1.5) --

1 x (0.5 ... 2.5) 1 x (0.5 ... 4)

Type of electrical connection for auxiliary and control circuit (1 or 2 conductors can be connected)

Screw terminals

Spring-loaded terminals (push-in)

Type of connectable conductor cross-sections for auxiliary contacts • Solid

mm²

1 x (0.5 ... 2.5), 2 x (1.0 ... 1.5)

1 x (0.5 ... 1.5), 2 x (0.5 ... 1.5)

• Finely stranded - With end sleeve

mm²

1 x (0.5 ... 2.5), 2 x (0.5 ... 1) --

1 x (0.5 ... 1.0), 2 x (0.5 ... 1.0)

- Without end sleeve

mm²

Type of connectable conductor cross-sections for AWG cables • For main contacts

1 x (0.5 ... 1.5), 2 x (0.5 ... 1.5)

1 x (20 ... 12), 2 x (20 ... 14) 1 x (20 ... 14), 2 x (18 ... 16)

• For auxiliary contacts

1 x (20 ... 12)

1 x (20 ... 16), 2 x (20 ... 16)

■ Accessories 1

More information Equipment Manual, see https://support.industry.siemens.com/cs/ww/en/view/66295730

3-phase infeed system (3RM19 3-phase busbar system)

8

The system permits an easy, time-saving and safe means of feeding two or more 3RM1 motor starters. It can be used only with motor starters with screw terminals and in combination with 8US1716-0RK00 adapters for mounting rails in the main circuit. IC01_00169c

The maximum summation current must not exceed 25 A. The primary infeed is connected via a 3-phase infeed terminal. The busbars are available in three lengths, for two, three or five motor starters. More than five devices can be connected by clamping the connection tags of a second busbar underneath, rotated 180°.

4

The 3-phase busbars have touch protection but empty connection tags must be fitted with covers. 3

2

1 Four 3RM1 motor starters on standard mounting rail with one free slot 2 3RM1920-1AA 3-phase infeed terminal 3 Two 3RM1910-1DA 3-phase busbars rotated through 180° for the connection of up to nine motor starters 4 Covers for three 3RM1910-6AA connection tags respectively for unused slots

3RM19 infeed system with 3-phase infeed terminal: In the above example, two 3-phase busbars (5-pole busbars) rotated 180° allow up to nine 3RM1 motor starters to be connected. Contact with the unused connection tags in unoccupied positions is prevented safely by the covers.

Siemens IC 10 · 2022

8/87

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RM1 motor starters Fuse module for the use of 3RM1 motor starters on 8US busbar systems and mounting rails The fuse module permits the very compact construction of a load feeder with a maximum width of 22.5 mm. The 3RM1 motor starter in combination with the integrated fuses for short-circuit protection can therefore be used on 8US busbar systems. Thanks to the range of different adapters, the fuse module can be used in all 60 mm busbar systems and also in compact busbar systems and on mounting rails. The interface to the adapter also permits a simple and secure replacement of the load feeder.

1

2

3

The fuse module can be combined with all 3RM1 motor starters. The easily replaceable fuses protect the connected motor and the cables.

1 Busbar system

5 4

5

2 Cover profiles for busbars 3 Busbar adapter 4 Compact busbar adapter 5 3RM1 motor starter 6 3RM19 fuse module

8

IC01_00611a

7 3RM19 fuse module with open flap (Flap cannot be opened when fuse module is inserted. The fuse module must be removed to change the fuses.)

6 7

By means of the fuse module, 3RM1 motor starters can be used in busbar systems and 8US compact busbar systems, as well as on mounting rails

8/88

Siemens IC 10 · 2022

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RM1 motor starters Device connectors for the control circuit

Safe group shutdown can be implemented particularly easily in conjunction with 3SK safety relays. In this case, up to five motor starters can be directly connected to 3SK safety relays via the device connector and then safely shut down (see page 11/13). 3SK safety relay

3RM1 motor starter

IC01_00218b

IC01_00178a

The device connectors for 3RM1 motor starters (24 V DC control supply voltage only) reduce the outlay for cabling by looping through the control supply voltage. The device connectors can be snapped onto a standard mounting rail or fixed to a level mounting panel using screws.

Motor

Ideal connection: Combination of four SIRIUS 3RM1 Failsafe motor starters with SIRIUS 3SK safety relays

Electromechanical switching devices in series with hybrid motor starters

Using the device connectors exclusively for feeding in the control supply voltage By using device connectors, a maximum of five motor starters can be supplied with 24 V DC control supply voltage. This requires the control supply voltage to be applied to the A1 and A2 terminals of only one motor starter. Device daisy chain connectors can be used for gaps between two motor starters. Device termination connectors terminate a group. Using the device connectors for safe group shutdown In combination with the 3RM11 and 3RM13 fail-safe motor starters, the device connector can also be used for safetyrelated shutdown. For this application, groups of no more than five fail-safe motor starters can be connected using a device connector, and the group must be terminated with a termination connector. Removing the control voltage supply from the first motor starter will safely shut down the whole group.

Switching an inductive load - in particular of motors < 1 kW with high inductance - with an electromechanical switching device (e.g. contactor) can cause high and steep voltage edges. The resulting faults/damage can be prevented by first disconnecting with the hybrid motor starter or by using EMC suppression modules: • For 3RT2916-1P.. EMC suppression modules for direct mounting on the contactor, see page 3/122 • For motor suppression modules that are fitted in the main circuit, see page 8/93 Note: For more information, see https://support.industry.siemens.com/cs/ww/en/view/109758696.

Siemens IC 10 · 2022

8/89

8

Device connector with 3RM1 motor starter

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RM1 motor starters

■ Selection and ordering data More information Industry Mall, see www.siemens.com/product?3RM1 Operational power for three-phase motor at 400 V1)

Adjustable current Control supply response value of the voltage inverse-time delayed overload release At DC At AC at 50 Hz

SD

kW

A

V

V

d

0 … 0.12

0.1 … 0.5

24

--

}

0.09 … 0.75

0.4 … 2

24

--

}

0.55 … 3

1.6 … 7

24

--

0 … 0.12

0.1 … 0.5

0.09 … 0.75

Article No.

Price per PU

PU (UNIT, SET, M)

PS*

PG

3RM1001-@AA04

1

1 unit

41D

3RM1002-@AA04

1

1 unit

41D

}

3RM1007-@AA04

1

1 unit

41D

110

110 ... 230 X

3RM1001-@AA14

1

1 unit

41D

0.4 … 2

110

110 ... 230 X

3RM1002-@AA14

1

1 unit

41D

0.55 … 3

1.6 … 7

110

110 ... 230 X

3RM1007-@AA14

1

1 unit

41D

0 … 0.12

0.1 … 0.5

24

--

}

3RM1201-@AA04

1

1 unit

41D

0.09 … 0.75

0.4 … 2

24

--

}

3RM1202-@AA04

1

1 unit

41D

0.55 … 3

1.6 … 7

24

--

}

3RM1207-@AA04

1

1 unit

41D

0 … 0.12

0.1 … 0.5

110

110 ... 230 X

3RM1201-@AA14

1

1 unit

41D

0.09 … 0.75

0.4 … 2

110

110 ... 230 2

3RM1202-@AA14

1

1 unit

41D

0.55 … 3

1.6 … 7

110

110 ... 230 X

3RM1207-@AA14

1

1 unit

41D

0 … 0.12

0.1 … 0.5

24

--

2

3RM1101-@AA04

1

1 unit

41D

0.09 … 0.75

0.4 … 2

24

--

}

3RM1102-@AA04

1

1 unit

41D

0.55 … 3

1.6 … 7

24

--

}

3RM1107-@AA04

1

1 unit

41D

0 … 0.12

0.1 … 0.5

110

110 ... 230 X

3RM1101-@AA14

1

1 unit

41D

0.09 … 0.75

0.4 … 2

110

110 ... 230 X

3RM1102-@AA14

1

1 unit

41D

0.55 … 3

1.6 … 7

110

110 ... 230 X

3RM1107-@AA14

1

1 unit

41D

0 … 0.12

0.1 … 0.5

24

--

}

3RM1301-@AA04

1

1 unit

41D

0.09 … 0.75

0.4 … 2

24

--

}

3RM1302-@AA04

1

1 unit

41D

0.55 … 3

1.6 … 7

24

--

}

3RM1307-@AA04

1

1 unit

41D

0 … 0.12

0.1 … 0.5

110

110 ... 230 X

3RM1301-@AA14

1

1 unit

41D

0.09 … 0.75

0.4 … 2

110

110 ... 230 X

3RM1302-@AA14

1

1 unit

41D

0.55 … 3

1.6 … 7

110

110 ... 230 X

3RM1307-@AA14

1

1 unit

41D

Direct-on-line starters

3RM1001-1AA04

8

Reversing starters

3RM1201-1AA04

Failsafe direct-on-line starters

3RM1101-1AA04

Failsafe reversing starters

3RM1301-1AA04 Type of electrical connection • Screw terminals for main circuit, screw terminals for control circuit • Spring-loaded terminals (push-in) for main circuit, spring-loaded terminals (push-in) for control circuit • Screw terminals for main circuit, spring-loaded terminals (push-in) for control circuit 1)

1 2 3

The actual starting and rated data of the motor to be protected must be considered when selecting the units.

8/90

Siemens IC 10 · 2022

* You can order this quantity or a multiple thereof. Illustrations are approximate

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RM1 motor starters Product designation

SD

Article No.

Price per PU

PU (UNIT, SET, M)

PS*

PG

d

3-phase infeed system for 3RM1 with screw terminals }

3RM1920-1AA

1

1 unit

41D

• For 2 motor starters

}

3RM1910-1AA

1

1 unit

41D

• For 3 motor starters

}

3RM1910-1BA

1

1 unit

41D

• For 5 motor starters

}

3RM1910-1DA

1

1 unit

41D

Covers For 3 connection tags of the 3-phase busbars

}

3RM1910-6AA

1 10 units

41D

Fuse module with 3NW6007-1 fuse

2

3RM1932-1AB

1

1 unit

41D

Fuse module without fuse1)

2

3RM1930-1AA

1

1 unit

41D

Adapters for 60 mm busbar systems 22.5 mm x 200 mm x 41.5 mm

5

8US1216-0AS00

1

1 unit

14O

5

8US1616-0AK02

1

1 unit

14O

3-phase infeed terminals • For 3-phase busbars

3RM1920-1AA 3-phase busbars

3RM1910-1AA

3RM1910-1BA

8

3RM1910-1DA

3RM1910-6AA

Fuse modules for 3RM1 for use on busbars or mounting rails

3RM1932-1AB

Adapters

Note: The adapter can be used on busbars with a width of 12 mm and a thickness of 5 mm or 10 mm.

8US1216-0AS00 Adapters for 60 mm compact busbar systems 22.5 mm x 160 mm x 41.5 mm Note: The adapter can be used on busbars with a width of 12 mm, 15 mm, 20 mm, 25 mm or 30 mm and a thickness of 5 mm or 10 mm.

8US1616-0AK02 1)

For details of alternative fuses, see Equipment Manual.

* You can order this quantity or a multiple thereof. Illustrations are approximate

Siemens IC 10 · 2022

8/91

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RM1 motor starters Product designation

SD

Article No.

Price per PU

PU (UNIT, SET, M)

PS*

PG

d

Adapters 5

8US1716-0RK00

1

1 unit

14O

2

8US1922-2CA00

1 10 units

14O

2

8US1922-2AA00

1 10 units

14O

2

8US1922-2BA00

1 10 units

14O

Device connectors For 3RM1 motor starters, 24 V DC, 22.5 mm

2

3ZY1212-2EA00

1

1 unit

41L

Device daisy chain connectors For 3RM1 motor starters 24 V DC, 22.5 mm For gaps without motor starters in assemblies

2

3ZY1212-2AB00

1

1 unit

41L

Device termination connectors For 3RM1 motor starters, 24 V DC, 22.5 mm

2

3ZY1212-2FA00

1

1 unit

41L

Adapter for 35 mm DIN mounting rails 22.5 mm x 185 mm x 23.5 mm

8US1716-0RK00

Cover profiles1)2) Cover profiles for busbars 12 mm x 5 mm x 1 000 mm 40 mm or 60 mm center-to-center busbar clearance depending on busbar system 8US1922-2CA00 15 mm x 5 mm x 1 000 mm 20 mm x 5 mm x 1 000 mm 25 mm x 5 mm x 1 000 mm 30 mm x 5 mm x 1 000 mm 40 mm or 60 mm center-to-center busbar clearance depending on busbar system 8US1922-2AA00

8

12 mm x 10 mm x 1 000 mm 15 mm x 10 mm x 1 000 mm 20 mm x 10 mm x 1 000 mm 25 mm x 10 mm x 1 000 mm 30 mm x 10 mm x 1 000 mm 60 mm center-to-center busbar clearance 8US1922-2BA00

Device connectors

3ZY1212-2EA00

3ZY1212-2AB00

3ZY1212-2FA00 1)

The cover profiles for busbars can be used for maintaining minimum spacing between the load feeders. 2) For further accessories for the configuration of a busbar system, see Catalog LV 10.

8/92

Siemens IC 10 · 2022

* You can order this quantity or a multiple thereof. Illustrations are approximate

© Siemens 2022

Load feeders and motor starters for use in the control cabinet SIRIUS 3RM1 motor starters Product designation

SD

Article No.

Price per PU

PU (UNIT, SET, M)

PS*

PG

1

6 units

41L

1

6 units

41L

1

6 units

41L

d

Removable terminals Terminals for main circuit, 2-pole Screw terminals • Version with screw terminals, up to 1 x 4 mm² or 2 x 2.5 mm²

2

3ZY1122-1BA00 Spring-loaded terminals (push-in)

3ZY1122-1BA00

• Version with spring-loaded terminals (push-in), up to 1 x 4 mm² or 2 x 1.5 mm² (both in one end sleeve)

2

3ZY1122-2BA00

Terminals for control circuit, 3-pole Screw terminals • Version with screw terminals, up to 2 x 1.5 mm² or 1 x 2.5 mm²

2

3ZY1131-1BA00 Spring-loaded terminals (push-in)

• Version with spring-loaded terminals (push-in), up to 2 x 1.5 mm²

2

3ZY1131-2BA00

1

6 units

41L

Push-in lugs for wall mounting 2 lugs per device are required

2

3ZY1311-0AA00

1 10 units

41L

Sealable covers, 22.5 mm For simple protection against unauthorized access

2

3ZY1321-2AA00

1

5 units

41L

Coding pins for removable terminals For mechanical coding of the terminals

2

3ZY1440-1AA00

1 12 units

41L

• Titanium gray

2

3ZY1450-1AB00

1

5 units

41L

• Yellow

2

3ZY1450-1BB00

1

5 units

41L

• Square

15

3RK1911-6EA00

1

1 unit

42D

• Round

15

3RK1911-6EB00

1

1 unit

42D

1

1 unit

41B

3ZY1131-1BA00

Further accessories

3ZY1321-2AA00

3ZY1440-1AA00 Hinged cover Replacement cover, without terminal labeling, 22.5 mm wide

3ZY1450-1AB00 Motor suppression module

3RK1911-6EA00 Spring-loaded terminals

Screwdrivers For all SIRIUS devices with spring-loaded terminals

3RA2908-1A

Length approx. 200 mm, 3.0 mm x 0.5 mm, titanium gray/black, partially insulated

* You can order this quantity or a multiple thereof. Illustrations are approximate

2

3RA2908-1A

Siemens IC 10 · 2022

8/93

8

3ZY1311-0AA00

© Siemens 2022

Load feeders and motor starters for use in the control cabinet ET 200SP motor starters

■ Overview 1

2

2

3

4

6

5

6

7

IC01_00662a

1

8 9

1 ET 200SP interface module

IC01_00613a

5

2 ET 200SP digital input 3

1 ET 200SP fail-safe motor starter 2 BaseUnit for ET 200SP motor starter

4 ET 200SP analog input

3 Fan

5 Dummy module consisting of BaseUnit + BU cover, 15 mm

4 3DI/LC module

4

5 Infeed bus cover

8

3 ET 200SP digital output

Motor starter, BaseUnit, fan and 3DI/LC control module

7 Dummy module consisting of BaseUnit + BU cover, 30 mm 8 3DI/LC module

6 ET 200SP motor starter F-DI and 9 Infeed bus cover ET 200SP motor starter

3RK1308 motor starter in the ET 200SP I/O system

More information Homepage, see www.siemens.com/sirius-motor-starter-et200sp

Further components in the ET 200SP I/O system:

Industry Mall, see www.siemens.com/product?3RK1308

• Catalog ST 70

TIA Selection Tool, see www.siemens.com/TST

• Homepage, see www.siemens.com/et200sp

ET 200SP motor starters ET 200SP is a scalable and extremely flexible modular I/O system with degree of protection IP20. As I/O modules, the ET 200SP motor starters are an integral part of this I/O system. They are switching and protection devices for 1- and 3-phase loads and are available as direct-on-line or reversing starters.

• Digital inputs can optionally be used via a 3DI/LC module • Control of the motor starter from the control system and of the diagnostics status via the cyclic process image • Diagnostics capability for active monitoring of the switching and protection functions • The signal states in the process image of the motor starter provide information about protective devices (short circuit or overload), the switching states of the motor starter, and system faults. Starter kit

Video: ET 200SP motor starters – Flexible, powerful, space-saving

Basic functionality All versions of the ET 200SP motor starter feature the following functionality: • Fully pre-wired motor starters for switching and protecting any AC loads up to 5.5 kW from 48 V AC to 500 V AC • Disconnection possible via fail-safe motor starters up to SIL 3 and PL e Cat. 4 • With self-assembling 32 A power bus, i.e. the load voltage is only fed in once for a group of motor starters • All control supply voltages connected only once, i.e. when modules are added they are automatically connected to the next module • Hot swapping is permissible

8/94

Siemens IC 10 · 2022

The 3RK1908-1SK00 starter kit is a favorably priced complete package for switching and monitoring motors in the ET 200SP system, see page 8/102. It contains: • A 3RK1308-0BC00-0CP0 reversing starter (0.9 to 3 A) • A 3RK1908-0AP00-0AP0 BaseUnit with 500 V and 24 V AC/DC infeed • An EMC distance module (consisting of 6ES7193-6BP00-0BA0 BaseUnit plus 6ES7133-6CV15-1AM0 BU cover 15 mm)

© Siemens 2022

Load feeders and motor starters for use in the control cabinet ET 200SP motor starters BaseUnits for motor starters

For motor starters with a 12 A rated current, the 3RW49288VB00 fan is included in the scope of supply.

1 24 V and 500 V DC

This fan can also be ordered as an option for motor starters with lower rated currents, if the boundary conditions demand this. For information on the ambient conditions for the use of motor starters, see chapter "Product features" in the Equipment Manual.

2 500 V AC 3 24 V DC 4 without infeed 5 3RK1908-0AP00-0EP0 (not shown here)

Designing interference-free motor starters

The 15 mm BU cover protects the plug contacts of the BaseUnit against dirt. Electromechanical switching devices in series with hybrid motor starters Switching an inductive load - in particular of motors