Story Transcript

DISTRIBUTION SYSTEMS

Water Piping and Pumps

Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They are targeted at engineers and designers who wish to develop their knowledge in this field to effectively design, specify, sell or apply HVAC equipment in commercial applications. Although TDP topics have been developed as stand-alone modules, there are logical groupings of topics. The modules within each group begin at an introductory level and progress to advanced levels. The breadth of this offering allows for customization into a complete HVAC curriculum – from a complete HVAC design course at an introductory-level or to an advancedlevel design course. Advanced-level modules assume prerequisite knowledge and do not review basic concepts.

Water piping and pumping is a fundamentals topic of HVAC design. The correct layout, selection and sizing of the piping system and associated hydronic components is required to properly deliver chilled and hot water as required to maintain comfort conditions. Piping connections at various equipment are covered, along with piping arrangements for chilled water systems. Pump basics, pipe sizing, and a pump selection example complete the TDP.

© 2005 Carrier Corporation. All rights reserved. The information in this manual is offered as a general guide for the use of industry and consulting engineers in designing systems. Judgment is required for application of this information to specific installations and design applications. Carrier is not responsible for any uses made of this information and assumes no responsibility for the performance or desirability of any resulting system design. The information in this publication is subject to change without notice. No part of this publication may be reproduced or transmitted in any form or by any means, electronic or mechanical, for any purpose, without the express written permission of Carrier Corporation.

Printed in Syracuse, NY CARRIER CORPORATION Carrier Parkway Syracuse, NY 13221, U.S.A.

Table of Contents Introduction ..................................................................................................................................... 1 Types of Piping Systems ................................................................................................................. 1 Closed-Loop (Evaporator) ........................................................................................................... 1 Open-Loop (Condenser) .............................................................................................................. 2 Once-Thru.................................................................................................................................... 2 Water Distribution Systems............................................................................................................. 3 1-Pipe Systems............................................................................................................................. 3 2-Pipe Systems............................................................................................................................. 4 3-Pipe Systems............................................................................................................................. 5 4-Pipe Systems............................................................................................................................. 6 Direct and Reverse Return Systems................................................................................................. 7 Direct Return................................................................................................................................ 7 Reverse Return............................................................................................................................. 8 Water Piping Components and Accessories .................................................................................... 8 Pipe Materials .............................................................................................................................. 9 Joints ............................................................................................................................................ 9 Fittings ....................................................................................................................................... 10 Valves ........................................................................................................................................ 11 Hydronic System Components .................................................................................................. 16 Strainers ................................................................................................................................. 16 Expansion Tanks.................................................................................................................... 16 Air Separators ........................................................................................................................ 18 Air Vents................................................................................................................................ 18 Thermometers, Gauges, Pete’s Plugs..................................................................................... 19 Pipe Hangars and Anchors..................................................................................................... 19 Volume Tanks........................................................................................................................ 20 Typical Piping Details at Equipment ............................................................................................. 21 Chillers....................................................................................................................................... 21 AHU Coil or Fan Coil................................................................................................................ 22 Pumps......................................................................................................................................... 22 System Piping Arrangements ........................................................................................................ 23 Parallel and Series Chiller Evaporators ..................................................................................... 23 Single Water-Cooled Chiller Loop ............................................................................................ 24 Multiple Water-Cooled Chiller Loop with Dedicated Pumps.................................................... 24 Multiple Water-Cooled Chillers with Manifolded Pumps ......................................................... 25 Primary-Secondary Chilled Water System ................................................................................ 25 Primary-Only, Variable-Flow Chilled Water System................................................................ 26 Chiller Head Pressure Control ................................................................................................... 27 Head Pressure Control Piping Methods with Diverting Valve .............................................. 28 Head Pressure Control Piping Method with VFD or Modulating Valve ............................... 29 Pump Basics and Types of Pumps................................................................................................. 29 Pump Curve ............................................................................................................................... 32 Selection..................................................................................................................................... 35 Centrifugal Pump Types ............................................................................................................ 36

Pipe Sizing and Pump Selection Example ..................................................................................... 37 Step 1: Determine Water Velocity in Piping.............................................................................37 Step 2: Determining Piping Friction Losses .............................................................................37 Step 3: Gather Job Specific Component Pressure Drops and Design Data ..............................38 Step 4: Review the Highest Pressure Drop Circuit and Calculate Water Flows........................39 Step 5: Size the Pipe; Find the Friction Rate/100 ft..................................................................40 Step 6: Find the Longest Circuit Pressure Drop........................................................................41 Step 7: Sum All the Pressure Drops for Pump Selection ..........................................................42 Step 8: Size the Chilled Water Loop.........................................................................................43 Step 9: Check Evaporator Loop Volume ..................................................................................45 Piping System Calculator Tool ..................................................................................................46 Summary........................................................................................................................................ 46 Work Session ................................................................................................................................. 47 Appendix........................................................................................................................................ 49 References..................................................................................................................................49 Charts and Tables.......................................................................................................................49 Chart 1 – Friction Loss for Closed Loop ...............................................................................50 Chart 2 – Friction Loss for Open Loop..................................................................................51 Chart 3 – Friction Loss for Closed and Open Copper Tubing System ..................................52 Table 4 – Physical Properties of Steel Pipe ...........................................................................53 Table 5 – Friction Loss of Valves in Equivalent Length of Straight Pipe .............................54 Table 6 – Friction Loss of Pipe Fittings in Equivalent Feet of Straight Pipe ........................55 Table 7 – Special Fitting Losses in Equivalent Feet of Straight Pipe ....................................56 Table 8 – Control Valves and Strainer Losses in Equivalent Feet of Straight Pipe...............57 Work Session Answers ..............................................................................................................58

WATER PIPING AND PUMPS

Introduction In this TDP module we will cover major topics associated with chilled water piping, and to a limited extent, hot water piping. We will discuss the three types of piping systems and the four basic piping distribution designs used to supply and return water to HVAC hydronic equipment. There are important components and accessories that are required to complete a water piping system. These include valves, tanks, and air eliminators. We will examine these system components and define their role in the total hydronic system. After examining some typical piping hook-ups to commercial HVAC equipment, we will diagram and discuss popular piping arrangements, such as primary secondary and primary variable flow. We will then discuss a popular pipe-sizing tool from a noted pump manufacturer that streamlines the sizing process. We will also examine types of water pumps used in HVAC systems and their characteristics and applications. Upon completion of this TDP, the reader should feel comfortable identifying, selecting, and applying the major components of water piping systems.

Types of Piping Systems Before piping design can be discussed in detail, you must first have an understanding of the three basic types of piping systems: closed-loop, open-loop, and once-thru.

Closed-Loop (Evaporator) In a closed-loop piping system, the water is contained within a closed piping system, or loop, through which it circulates. While there may be some nominal contact with the air depending on the type of tank used, the system is considered closed to the environment. Typically, closed-loop systems are chemically treated to control corrosion, scale, slime, and algae within the piping but their chemical treatment requirements typically are not as extensive as an open-loop. Figure 1 Example of a Closed-Loop Piping System

Distribution Systems

1

WATER PIPING AND PUMPS

Open-Loop (Condenser) In an open-loop piping system, the water is in constant contact with the air and the system is therefore open to the atmosphere. A typical example of an open-loop system is a recirculating condenser water system with a cooling tower where the water is circulated through the cooling tower, sprayed over the tower media surface, collected into the tower basin, circulated through the condenser, and then sent back through the cooling tower. Figure 2 Example of an Open-Loop Recirculating System

Once-Thru In this type of system, water passes through the system once and is then discharged. An example of a once-thru system would be a chiller with river water piped into its water-cooled condenser. The rejected heat from the condenser is introduced back into the river, which is not always acceptable from an environmental perspective. In general, once-thru systems that use “city” water are not allowed because they use excessive amounts of water. Pipe-sizing methods are virtually the same for all three types of systems, however there are differences in friction loss due to expected corrosion rates in the pipes. Hence pipesizing charts differ between open and closed-loop systems. A once-thru system is considered an open-loop system, but typically does not get any chemical treatment like an open system does. But because river water may have more contaminants, the open-loop tables should be used, and may be conservative.

Figure 3 Example of a Once-Thru System

Distribution Systems

2

WATER PIPING AND PUMPS

Water Distribution Systems There are four main types of water distribution systems. They are defined by the number of pipes used in the system – 1-pipe, 2-pipe, 3-pipe, and 4-pipe. While this TDP will discuss primarily chilled water and condenser water system piping system design, it is important to understand the evolution from 1-pipe into the other three systems, all of which are used for heating as well as cooling.

1-Pipe Systems A 1-pipe water distribution system is a system that has a one main pipe looping around the building and then returning. 1-Pipe System Uses Since 1-pipe systems are typically only used for heating, the supply and return are shown connecting to a boiler instead of a chiller.

This pipe is both the supply and return main. Its size is constant throughout, and all of the water in the system flows through it feeding Figure 4 one or more zone heating terminals. A small amount of water is 1-Pipe Distribution System induced to leave the main at each riser by the use of a special flow fitting used on 1-pipe systems, sometimes referred to as a “monoflow” fitting. These fittings create a pressure drop in the main equal to or greater than the pressure drop through the riser, runout, zone terminal unit, and return piping. Control of flow rate to the zone terminal units in a 1-pipe system is often difficult to achieve. The pressure drop from the point where water leaves the main to where it returns is small and small changes in resistance in this line result in large changes in flow rate. As a result, many 1pipe systems avoid flow rate control at the zone terminals and achieve capacity control by regulating airflow over the zone terminals instead. History of 1-Pipe Systems The 1-pipe system has been used for many years in residential and smaller commercial buildings. It has been used as a hot water distribution system and seldom, if ever, for the distribution of chilled water.

Some advantages of the 1-pipe system include the simple design of the system that requires one pipe size. This simplicity of design leads to easy installation and low installed cost. However, 1-pipe systems have several disadvantages. The pumping head is generally higher than that in other systems because of the resistances occurring in series. That means the pump and pump energy is larger than other distribution systems of comparable size.

Distribution Systems

3

WATER PIPING AND PUMPS

The change in water temperature as the water moves through the system (the water gets colder after each successive terminal because of mixing) creates the possible need of larger units at the end of the main, which will complicate the selection of the zone terminal units and add cost due to oversized units near the end. Also, at part load, the end unit may be over or under capacity. In order to keep the pressure loss through the unit coils low, the water velocity through the coils must be kept low. This results in coils with large tube diameter, a greater number of tubes in parallel, or larger coils than used with other distribution systems. Therefore, a physical space and terminal cost penalty exist when a 1-pipe system is used. The 1-pipe system is poorly suited to chilled water distribution for several reasons. The water quantity used in chilled-water systems is usually considerably higher than that used for heating because the unit coils work on smaller temperature differentials in the cooling mode than in the heating mode. In order to economically accommodate higher flow rate, zone terminals used for chilled water would need to be redesigned so they are not prohibitively large, expensive, or space-consuming.

2-Pipe Systems The 2-pipe water distribution system is used with both heating and cooling equipment containing water coils. It is equally useful for room fan coil units and medium or large central air handlers using combination hot water and chilled water coils. The 2-pipe system can be used to distribute either hot or cold water, or alternate between the two. The same piping is used for both heating and cooling so there must be a definite outdoor temperature, which is called the “changeover temperature,” or some other indicator of building load, at which point the hot water in the piping is replaced by the chilled water and vice versa. Some 2-pipe fan coil units are equipped with electric heat in addition to the heating capability of the hot water coil. This “touch up” electric heat can be used if heating is required for a fan coil but the system is still not changed over to the heating mode. 2-pipe system changeover

Figure 5

takes time and normally is done seasonally.

2-Pipe Reverse Return Distribution System

There are two forms of 2-pipe water distribution systems in common use: 2-pipe direct return and 2-pipe reverse return. Direct and reverse return will be covered later. In a 1-pipe system, the supply and return main is the same pipe. The quantity of water flowing through the main is approximately constant and the main is built of one diameter pipe throughout its length. On the other hand, in the 2-pipe system, the supply and return mains are separate pipes and water leaving the supply main goes into the return main. As water leaves the

Distribution Systems

4

WATER PIPING AND PUMPS

supply main and goes through the terminal units, the quantity of water flowing in the main is reduced, so the pipe diameter can be reduced. The opposite is true for the return main, which starts out small at the furthest terminal and has to be increased in size as water enters it. Advantages of 2-pipe systems include the fact that a higher friction loss can be taken in both the piping and the zone terminal units and still have a total pumping head lower than that in the same size 1-pipe system because the zone terminals are in parallel water circuits, not series. Also, it is easier to balance the flow to each unit in this system than in the 1-pipe system, assuming branch balancing valves are installed in the piping as the system is installed. Another advantage of 2-pipe systems is that the water temperature entering each zone terminal will be the same in temperature because the return water from each terminal unit does not mix with the supply water in the supply main. However, the installed cost is greater than that for a 1-pipe system. In systems of the same size, even though the average Pumping head pipe diameter in the 2-pipe system is smaller than that in the 1- refers to the total pressure pipe system, the extra pipe and greater number of fittings means drop in ft wg that the water that this system will have a greater first cost. Like the 1-pipe pump(s) must overcome to system, the 2-pipe system distributes only a common tempera- circulate the water through ture fluid to the zone terminals. Because the system cannot the system. Lower head deliver hot water or chilled results in lower pump water simultaneously to the energy consumption. Cooling to Heating coils, it must be in either the When a 2-pipe system is heating or cooling mode. To change over from heating to changed over from cooling cooling, the water in the mains must be completely circulated to heating or vice versa, it through the chiller and back to the unit before any cooling is is important that the water available at the zones. Changeover takes time. It is not practiintroduced is not too hot or cal to plan to change over frequently. Seasonal changeover is too cold. This would cause the most common method used. Two-pipe supplemental heatthermal shock to the boiler ing systems are also quite common, both for separate or the chiller. perimeter heating and zone reheat at the terminals.

3-Pipe Systems The 3-pipe water distribution system has two supply mains feeding each zone terminal, one for chilled water and one for hot water, and a common return main. The chilled water supply and hot water supply lines are sized according to normal standards and the return is sized to handle the maximum flow rate (which is the cooling flow rate). As with 2-pipe systems, the return main can be either direct return or reverse return configuration. Figure 6 3-Pipe Distribution System

Distribution Systems

5

WATER PIPING AND PUMPS

Because of the two supply mains to each zone terminal, there is always hot and cold water present at the entrance to the zone coil ready to be used when needed. This gives any fan coil or air handler supplied by the 3-pipe water distribution system the ability to heat or cool at any time. No changeover from summer to winter cycle is needed in the 3-pipe system. ASHRAE 90.1 However, the operating cost of this system can ASHRAE 90.1 does not allow for the become prohibitively high because of the mixing of use of 3-pipe systems because of hot and cold return water. It is important to be famil- the mixing of hot and cold water in iar with 3-pipe systems because they have been the common return pipe uses excess energy. installed in existing buildings and are still in use.

4-Pipe Systems The 4-pipe water distribution system is actually two, 2-pipe systems in parallel; each system consisting of its own supply and return main. One system is always distributing chilled water to the units and returning it to the chiller. The other is distributing hot water to the units and returning the water to the boiler. Unlike the 3-pipe system, there is no mixing of hot and cold water. By using two separate coils in each zone terminal unit, or one coil with a separate cooling and heating circuit, the heating and cooling systems are completely separated. The chilled water flows through a cooling coil and the hot water flows through a separate heating coil. At no point are the two circuits connected. In a 4-pipe water distribution system, each terminal unit can become a separate zone of control, with its own thermostat. Both hot and Figure 7 cold water are available to all units at 4-Pipe Distribution System one time. Four-pipe distribution systems are actually two 2-pipe systems in parallel. This system offers both hot and chilled water to all zones simultaneously, enabling the system to meet cooling and heating loads whenever and wherever they occur. There is no need for seasonal or more frequent changeover. The hot and chilled water circuits are completely separate and the two water streams are never mixed. The design methods, valves, and controls are similar to 2-pipe and 3-pipe systems. A 4-pipe system with a fossil fuel-fired boiler can deliver a competitive or lower operating cost than some 2-pipe systems with “touch-up” electric heat built into the unit. That is because the electric heaters in the 2-pipe unit must sometimes operate more often than is expected and electric resistance heat is expensive, and the heaters may require a larger building electric service. This operation occurs prior to the entire system changeover to heating. Fossil fuel rates typically offer an advantage to electric rates.

Distribution Systems

6

WATER PIPING AND PUMPS

However, 4-pipe systems have a higher installed price than 2-pipe and most 3-pipe systems. The extra pipe and valves at the zone terminals tend to make the 4-pipe system the most costly in terms of installed cost. Four-pipe systems also require terminal units with dual coils or a 2-circuit coil, which costs more. Also, there are four pipes to run throughout the building, which takes more time and consumes more space for piping than the other systems. For commercial buildings, the choice comes down to 2-pipe versus 4-pipe designs. The comfort and control advantage of 4-pipe over 2-pipe must be weighed against the higher installed cost of the 4-pipe system. Where the building configuration and layout of spaces may require long periods of both heating and cooling simultaneously, and occupant comfort is a requirement, 4pipe makes the most sense. When the building lends itself to a seasonal changeover without large compromises in comfort, 2-pipe is suitable.

Direct and Reverse Return Systems Closed-loop systems can be further classified as direct return or reverse return.

Direct Return The direct return system allows piping to be run in the most direct path to optimize piping costs. The disadvantage is that the flow at each fan coil unit or air handler usually needs to be balanced using a balancing valve. The length of the water circuit through the supply and return piping to each fan coil or air handler is different in direct return piping. Fan coils close to the pump receive greater flow rate than those further away unless balancing is accomplished. Open-loop systems such as the condenser water system discussed earlier with a cooling tower are always direct return since individual terminals don’t exist and balancing is relatively simple. Figure 8 Direct Return Horizontal System Layout

Distribution Systems

7

WATER PIPING AND PUMPS

Reverse Return The reverse return system is piped so that the length of the water circuit through the supply and return piping to each fan coil or air handler is essentially the same. Therefore, pressure drops are basically equal. Buildings such as hotels with multiple identical fan coil units with identical flows are excellent candidates for reverse return systems. Reverse return has greater pipe lengths and cost. However, the cost of adding a balancing valve for each fan coil using a direct return system could offset the additional costs of the added reverse return piping. If the individual fan coil or airhandling unit water pressure drops are not reasonably close to each Figure 9 other, engineers will often specify Reverse Return Horizontal System Layout balancing valves anyway, regardless of the piping arrangement.

Water Piping Components and Accessories There are many, varied, components that make up all water, and air-water systems. Pipe, fittings, valves, strainers, pumps, chillers, air-handling units, cooling towers, expansion tanks, air separators, Pete’s plugs, thermometers, gauges, air vents, pipe supports, and possibly a volume tank are all included. Following are descriptions of hydronic components that are used in chilled water piping systems.

Distribution Systems

8

WATER PIPING AND PUMPS

Pipe Materials Typically the piping used in an HVAC system is either schedule 40 black steel welded or cutgrooved pipe, or lighter gauge rolled-groove steel pipe for sizes 2-1/2-in. diameter and above. Type L copper or threaded schedule 40 black steel pipe is normally used for 2-in. diameter and smaller. In some closed-loop water source heat pump applications, schedule 40 PVC piping has been used where local codes and inspectors permit. If PVC is used on the exterior of a building it should be protected from the elements with insulation so that the piping does not deteriorate from extended exposure. Use of PVC Piping Schedule 40 PVC is sometimes used on the interior of the building where codes allow or, in some climates, on the exterior as a means to reduce cost.

Figure 10 Materials Used for Water Piping

Joints Steel pipe is offered with weld, mechanical groove or threaded connections. Copper pipe is offered with solder or mechanical rolled-groove connections. PVC pipe is offered with solvent or mechanical grooved connections. Weld-joint pipe has beveled ends so that when two pieces are butted toFigure 11 gether they form a groove for welding. Weld and Threaded Joint

The threaded joint design has male tapered threads at the end of the pipe that screw into the female thread of a fitting. Solder (sweat) joints and solvent joints are formed by one end that slips inside the other; solder or glue is used to seal the joint.

Figure 12 Sweat or Solvent Joint

Distribution Systems

9

WATER PIPING AND PUMPS

Mechanical groove joints have a groove that is cut or rolled into the end of the pipe and fitting. The joint is then completed with a mechanical coupling that locks into the grooves. Each coupling has a rubber gasket that seals the joint.

Grooved Joints Large equipment like centrifugal chillers are often available with a choice of either weld stub-outs or groove stub-outs factoryinstalled for the chilled water and the condenser water connections.

Figure 13 Mechanical (Groove) Joint Actual photo courtesy of Victaulic Company

Fittings Numerous fittings are available such as 90 and 45-degree elbows, tees, concentric reducers, eccentric reducers, flanges, etc. Fittings that allow for the least pressure drop, best routing and proper drainage should be used. The friction loss that best represents the type of fittings for a specific project (standard radius elbow versus long radius elbow for instance) can be most easily found in the Fitting Equivalent Length Pressure Drop Charts in the Appendix when calculating total system pressure drop. Equivalent lengths for unusual fittings not covered in the Tables will have to be determined by consulting with the manufacturer. Figure 14 Example of Various Pipe Weld Fittings

Distribution Systems

10

WATER PIPING AND PUMPS

Valves Many types of valves are available in the HVAC industry. Each type of valve has certain characteristics that make it better for certain applications such as shutoff, balancing, control (also referred to as “throttling”), or oneway flow. Some valves are suitable for multiple applications. A brief description of the different types of valves and their applications are listed below. Butterfly valves are generally found on larger sized systems and are used for shutoff duty, throttling duty and where there is frequent operation. They have good flow control (linear relationship between percent open and percent of full flow through the valve), low cost, high capacity and Figure 15 low pressure drop. They typically Butterfly Valves, Lug Pattern have bigger valves and are used on pipe sizes 2 ½-in. and larger. Lug-pattern will either through-bolt between two flanges, or be secured at the end of a pipe section, while a wafer-pattern is a more economical style that just sits between the bolted flanges without its own lugs. Gate valves, also known as “stop valves,” are designed for shutoff duty. When the valve is in the wide-open position, the gate is completely out of the fluid stream, thus providing straight through flow and a very low pressure drop. Gate valves should not be used for throttling. They are not designed for this type of service and consequently it is difficult to control fluid flow with any degree of accuracy. Vibration and chattering of the disc occurs when the valve is used for throttling, resulting in damage to the seating surface. The flow rate arrows in the figure indicate that a gate valve can be installed without regard to direction of flow within the pipe; they can seat in either direction. The globe valves shown next need to seat against the flow, which is why there is only one flow direction arrow on Figure 16 the figure. Gate Valve

Distribution Systems

11

WATER PIPING AND PUMPS

Globe, angle, and “Y” valves are of the same basic design and are designed primarily for throttling (balancing) duty. The angle or Y-pattern valve is recommended for full flow service since it has a substantially lower pressure drop at this condition than the globe valve. Another advantage of the angle valve is that it can be located to replace an elbow, thus eliminating one fitting.

Figure 17 Globe Valve

Globe, angle and Y valves can be opened or closed substantially faster than a gate valve because of the shorter lift of the disc. When valves are to be operated frequently, the globe design provides the more convenient operation. The seating surfaces of the globe, angle or Y valves are subject to less wear and the plug and seat are easy to replace compared to the gate valve discussed previously. Figure 18 Angle Globe Valve

Figure 19 Y-Globe Valve

Distribution Systems

12

WATER PIPING AND PUMPS

Plug valves, also called plug cocks, are primarily used for balancing flow rates in systems not subject to frequent flow changes. They come with cylindrical or tapered plugs that are usually lubricated to reduce galling, turning torque, and face leakage. Plug valves have approximately the same loss as a gate valve when in the fully open position. When partially closed for balancing, this line loss increases substantially. For large flow rate applications, a globe or butterfly will be used instead of a plug valve. Their sizes are limited to smaller applications because of cost.

Figure 20 Plug Valve

Ball valves are used for full open/closed service, with limited requirement for precise control. They are best suited for quick-open linear control. Their advantage is low cost, high capacity, low leakage, and tight sealing. Figure 21 Ball Valve

Check valves prevent the flow of water in the reverse direction. There are two basic designs of check valves, the swing check and the lift check. The swing check valve may be used in a horizontal line or in a vertical line if flow is upward. The flow through the swing check is in a straight line and without restriction at the seat. Swing checks are generally used in combination with gate valves. Figure 22 Swing Check Valve

Distribution Systems

13

WATER PIPING AND PUMPS

The lift check operates in a manner similar to that of a globe valve and, like the globe valve, its flow is restricted. The disc is seated by backflow or by gravity when there is no flow, and is free to rise and fall, depending on the pressure under it. The lift check should only be installed in horizontal piping and usually is used in combination with globe, angle and Y valves. Figure 23 Lift Check Valve

Control Valves: 3-Way and 2-Way Control valves can be 2-position (open or closed), 2-way modulating (modulates to vary flow through the coil and system), or 3-way modulating (modulates flow through the coil by bypassing water back to the return thereby maintaining a nearly constant flow through the system). Threeway valves are used for hot and cold water flow control on chillers, boilers, air coils, and most all HVAC hydronic units where temperature control is necessary. Three-way mixing valves have two inlets and one outlet. Three-way diverting valves have one inlet and two outlets. Mixing valves are typically used to vary the flow through a load (such as a chilled or hot water coil). Diverting valves are used to direct the flow one way or another and are useful in applications like 2-pipe changeover or in bypass applications. Three-way valves are used in many applications such as flow rate variation, temperature variation, and primary-secondary pumping systems in both 2-pipe and 4-pipe systems. Two-way modulating valves are used for variable flow through heating and cooling coils. They throttle the flow for part-load control instead of Figure 24 bypassing the flow around the coil. Control Valve Types

Distribution Systems

14

WATER PIPING AND PUMPS

Circuit Setters™ are valves that allow for preset balancing as in direct return system. The manufacturer’s application information should be used when using circuit setters in a design. The Circuit Setter™ balance valve is designed specifically for preset proportional system balance. This valve assures optimum system flow balance at minimum operating horsepower. A Circuit Setter™ is a popular three-function valve providing flow Figure 25 balance, flow metering, and shutoff. Circuit Setter Photo courtesy of Bell & Gossett

A Triple Duty Valve™ is often used on the discharge of the pump to replace an individual shut off valve, balancing valve and check valve. Triple duty valves are used to save cost of material and labor. Determining which valve to use is a matter of choice, based on the application and cost.

Figure 26 Triple Duty Valve Photo courtesy of Bell & Gossett

Relative Valve Comparison Chart $ Size

Ball1

Gate2

Globe2

Swing Check1

Wafer Butterfly3

Lug Butterfly3

¼

6

40

50

40





½

6

30

50

40





1

15

50

75

60





2

40

100

215

150

100

120

3

210

310

1100

500

120

140

4

250

600

1300



140

160

6

375

1000

2500



220

260

Notes: 1. All sizes threaded bronze body 2. Sizes ¼ to 2-in. threaded bronze body; sizes 3 to 6-in. threaded iron body 3. All sizes cast iron body

Figure 27 Comparison of Valve Costs

Distribution Systems

15

WATER PIPING AND PUMPS

Hydronic System Components Strainers The typical strainer used in the HVAC industry is a “Y” strainer. The strainer (minimum 20 mesh) is used to prevent construction debris from entering the equipment during initial startup and to catch any small debris that may be circulating through the system during normal operation or servicing. Strainers are normally installed on the inlet side of a chiller as well as the suction side of a pump. In some rare cases, strainers are also installed at the inlet of chilled water coils. Strainers are very important in open-loop systems and once-through systems since debris can enter the system at any time. They are also important to use on packaged units that use a brazed plate, or tube-in-tube heat exchanger because the small water passages should be kept clean.

Figure 28 “Y” Strainer Photo courtesy of Flexicraft Industries

Systems with large quantities of debris may use a “basket” strainer in lieu of a “Y” strainer. The basket strainer has two baskets and a transfer valve that allows flow to be changed from one basket to the other. This allows for one basket to be cleaned while the other is in use. A basket strainer is expensive and is used sometimes for extra straining of condenser water systems on water-cooled chillers.

Expansion Tanks Temperature changes cause the water to expand or contract within a closed-loop system. As the temperature increases, the water occupies a larger volume of space. An expansion tank is sized to handle the excess water that is a result of temperature change and water expansion and should be part of every closed-loop system, chilled water, condenser water, or hot water. Expansion tanks are not required in open systems like a cooling tower water loop. An expansion tank also provides a make-up location for automatic replacement of water to the system that has been lost due to various reasons such as, leakage through pump glands or servicing. Expansion tanks are available as an open tank, or a closed type tank. A diaphragm tank is a closed tank with an internal diaphragm that separates the water and air and is in the closed tank category. The open tank is just that, a tank that is open to the atmosphere.

Bladder Tanks The most commonly used tank is the bladder tank since it can be installed at any convenient point in the system and is usually most cost effective.

Distribution Systems

16

WATER PIPING AND PUMPS

The variation of water volume caused by temperature changes can be calculated by determining the total water volume in the system and then multiplying the volume by the change in specific volume of water between the highest and lowest temperatures expected. Bladder tanks are another type of closed tank and cost more per gallon than diaphragm tanks, but bladder tanks have a larger “acceptance volume” (the actual amount of water the tank can hold) than diaphragm; so for the particular application, the cost difference can be negligible. The liner (bladder) is replaceable, whereas the membrane for the diaphragm tank is not. The diaphragm membrane can be a wear point due to expansion/contraction. Bladder tanks have an acceptance volume of approximately 95 percent, which means if the system expansion were calculated to be 200 gallons, the actual tank size required would be approximately 210 gallons.

Volume of Expansion Tanks Practically speaking, the change in water system volume is usually about 1 percent for chilled-water systems and about 3-4 percent for normal hot water systems. This volume, however, is not the volume of the expansion tank. It represents the expansion volume of the system.

To size an expansion tank you will need to know the total gallons of water in the system, temperature of the water when the system is filled, average maximum operating temperature of the water, minimum operating pressure, and the maximum operating pressure which is typically chosen at 10 percent below the relief valve setting. Elevation differences between the tank, pumps, relief valves, and top of the system may also be considered. For maximum pump protection, Figure 29 the tank should be located on the suction side of the pumps, usually the Diaphragm Type Expansion Tank Photo courtesy of Bell & Gossett point of no pressure change (where a gauge would read 0 psig). Consulting with your local tank vendor for advice on the best location is advised in critical situations. A wrong location may result in pump cavitation or the need for excess residual system pressure.

Distribution Systems

17

WATER PIPING AND PUMPS

Air Separators Air separators are used in addition to an expansion tank in a closed system. Air separators eliminate entrained air from the system. As an example, 50˚ F water at 30 psig can contain up to 9 percent dissolved air. Circulation of the water through an air separator can remove a large percentage of this air that will improve the overall heat transfer efficiency of the system (air is an insulator) and reduce corrosion affect caused by dissolved oxygen. The air separator should be located where it will see the warmest water, usually on the suction side of the pump. In addition, an air separator is a pressure vessel and should be ASTM certified. See the Piping Details section of this TDP for connection of air Figure 30 separator to the expansion tank. Air Separator

Air Vents Air vents are also used to remove unwanted air from a closed-loop system. They should be located at high points in the system where air may be present. Current air vent designs allow air to be vented without loss of fluid from the system. However, in case of a vent failure it is recommended that the vent discharge be piped to a drain or waste line. Both manual and automatic air vents are used in the HVAC industry. Manual vents require that a service person bleed air from the system on a periodic basis where automatic air vents bleed the air based on a pressure setting (or by the drying out of a leather seal).

Figure 31 Air Vent Piping

Distribution Systems

18

WATER PIPING AND PUMPS

Thermometers, Gauges, Pete’s Plugs It is recommended that thermometers, sensors, and gauges be mounted at the inlet and outlet of each major piece of equipment. Major pieces of equipment are chillers, boilers, air handler coils, cooling towers, thermal storage tanks, and pumps. Pete’s plugs are small fittings with a rubber seal that can be used to read temperature or pressure with an insertion type thermometer or pressure gauge. They can be used in lieu of fixed location thermometers and gauges and are typically installed at small airhandling units, fan coil units, water source heat pumps, etc. Pressures are used to verify flow through heat exchangers and temperatures are used to measure equipment performance. It is very important that gauges or Pete’s plugs are located immediately upstream and downstream of each piece of equipment’s connection stub-out but prior to any valves. If mounted after the valve the pressure reading would include the pressure loss Figure 32 through the valve, this would give an Typical Thermometers, Pete’s Plugs, and Gauges inaccurate reading. Gauges and thermometer photos courtesy of Weiss Instruments, Inc.

Pipe Hangars and Anchors All piping should be supported with hangers that can withstand the combined weight of pipe, pipe fittings, valves, fluid in the pipe, and the insulation. They must also be capable of keeping the pipe in proper alignment when necessary. Where extreme expansion Recommended Support Spacing for Schedule 40 Pipe or contraction exists, roller-type Nominal Pipe Size Distance Between Supports hangers and saddles should be used. (ft) (in.) The pipe supports must have a ¾ - 1¼ 8 smooth, flat bearing surface, free from 1½ - 2½ 10 burrs or other sharp projections that 3 – 3½ 12 would wear or cut the pipe. 4–6

14

The controlling factor in the spac8 - 12 16 ing of supports for horizontal piping is 14 - 24 20 the deflection of piping due to its own weight, weight of the fluid, piping Figure 33 accessories, and the insulation. The Recommended Support Spacing for Schedule 40 Pipe table lists the recommended support spacing for Schedule 40 steel pipe, using the listed conditions with water as a fluid. The support spacing for copper tubing is given in the next table, which also includes the weight of the tubing filled with water, fittings, accessories and insulation.

Distribution Systems

19

WATER PIPING AND PUMPS

In the vertical direction, on a tall building, i.e. 20-stories, the risers might be anchored on the 5th floor and on the 15th floor with an expansion device located at the 10th floor. This arrangement allows the riser to expand in both diRecommended Support Spacing for Copper Tubing rections from the 5th and 15th floor, resulting in less pipe travel at headers, Tube OD Distance Between Supports whether they are located at the top or bottom (in.) (ft) of the building or in both locations. Smaller 5/8 6 buildings, i.e. 5-stories, risers are anchored 7/8 - 1 1/8 8 but once. Usually this is done near the 1 3/8 - 2 1/8 10 header, allowing the riser to grow in one direction only, either up or down depending 2 5/8 - 5 1/8 12 on the header location. 6 1/8 - 8 1/8 14 .

Pipe Anchors Unless piping is adequately and properly anchored, expansion may put excessive strain on fittings and equipment. Anchors, guides and expansion loops or compensators are located according to job conditions.

Figure 34 Recommended Support Spacing for Copper Tubes

Horizontal expansion is usually taken up in the many direction changes that occur in a normal layout. When long straight runs occur, proper anchoring is required, as are guides and either expansion devices or pipe loops to allow proper movement of the pipe as it goes through its temperature range. Detailed presentations on this topic are available in the Carrier System Design Manual, Part 3, and the ASHRAE Handbook-HVAC Systems and Equipment.

Volume Tanks An important factor in piping design involves having enough volume of chilled water in the piping system to assure stable operation of the chiller. Loop volume is the amount of fluid in the cooler, piping, cooling coils and optional storage tank that remains in circulation at all times. If the loop volume is too small, fluctuations in the loading will affect the chiller much more quickly and result in greater compressor cycling with resulting chilled water temperature swings. All chiller manufacturers require a minimum loop vol- Figure 35 ume for proper operation of their chillers to Volume Tank Requirements prevent rapid changes in water temperature and short cycling of the compressor. In effect, adequate loop volume acts as a “flywheel” so that the chiller does not cycle too quickly. To minimize cycling, the minimum loop volume should be at least three gallons per nominal ton capacity at the design point for normal comfort cooling duty applications. For process and loads that operate under variable flow conditions; the minimum should be from six to ten gallons per ton. Applications that operate under low ambient temperatures or use brine typically also require six to ten gallons per nominal ton. All recommendations are manufacturer dependent.

Distribution Systems

20

WATER PIPING AND PUMPS

A method to increase the loop volume is the addition of a volume tank connected to the chilled water system. For example, suppose a chiller installation with a 200-ton chiller was connected to a system calculated to have a loop volume of 400 gallons. The recommended minimum loop volume would be: (200 nominal tons) * (3 gallons/nominal ton) = 600 gallons If the loop volume were 400 gallons and the minimum required loop volume 600 gallons, a volume tank holding a minimum of 200 gallons would be required.

Typical Piping Details at Equipment Now that we have a basic understanding of piping systems and valves, let’s take a look at some typical piping details at various pieces of equipment.

Chillers The installer should mount the valves high, when the piping permits, to allow for removal of piping in order to service the equipment. Locating thermometers in vertical piping helps avoid damage that could result from mounting them on a horizontal section of pipe. Locate gauges close to the equipment so that the condenser and cooler pressure drops can be measured and flow verified. All of these devices must be accessible. The thermometers and gauges must be at an elevation and angle so they can be read.

Figure 36 Typical Water-Cooled Chiller Piping Details, Two-Pass Evaporator And Condenser Shown.

Distribution Systems

21

WATER PIPING AND PUMPS

AHU Coil or Fan Coil For coil piping, where unit discharge conditions are critical, a good recommendation is to use a separate balancing valve so flow can be set and then the valve locked in place. Having a valve on each side of the control valve also allows for control valve servicing. Mount the valves high and install flanges or unions on the entering and leaving coil connections to allow for removal of piping to service equipment. Locate Pete’s Plugs as close to the coil as possible so pressure can be measured and flow verified. Coil control valves can be 2position, 2-way modulating, or 3-way modulating. Multi-row coils should always be piped for counterflow and per the manufacturer’s recommendations. This means the water moves through the coil opposite the direction of airflow. This maximizes heat transfer. For a complete discussion on Figure 37 counterflow, refer to TDP-614, Coils: Direct Expansion, Chilled Water, and Typical Hot or Chilled Water Coil Piping Detail Heating.

Pumps A concentric reducer is recommended at the pump discharge to allow for smooth flow. A triple-duty valve can be substituted in lieu of a separate shutoff, balancing, and check valve.

An eccentric reducer is recommended at the pump suction to prevent air pockets in the suction line entering the pump. The check valve prevents reverse flow through the pump. Shutoff valves are provided to isolate the pump for servicing. Figure 38 Pump Piping Detail

Distribution Systems

22

WATER PIPING AND PUMPS

A separate balancing valve is used so that flow can be set and then the valve locked in place. A single combination valve with a memory stop can be used in lieu of having a shutoff valve and balancing valve on the pump discharge, though it should be mounted downstream of the check valve. Gauges or Pete’s plugs should be located as close to the pump as possible so pressure can be measured and flow verified. A suction diffuser (combination of a strainer and straightening vanes) can also be used at the inlet of the pump. A suction diffuser replaces the valve, strainer, and 90-degree elbow since these items are part of the diffuser. Suction diffusers are used when space limitations do not allow for a minimum of five pipe diameters on the suction side of end-suction pumps. They may also be used to save material and labor cost.

System Piping Arrangements The figures that accompany the description of each piping arrangement do not show all possible system variations. The diagrams that are shown are to help you understand some of the basic variations of chilled water and condenser water systems.

Parallel and Series Chiller Evaporators Where chiller capacities greater than can be supplied by a single chiller are required, or where stand-by capability is desired, chillers may be installed in parallel. Units may be of the same or different sizes. Usually, equally sized chillers are utilized to accomplish commonality of parts and maintain simplicity. If unequal sized chillers are used, cooler flow rates must be balanced to ensure proper flow to each chiller. Software is available from the chiller manufacturer that automatically stages multiple chillers of equal or unequal size. Where a large temperature drop (greater than 18º F) is desired, chillers may have to be installed in series. Use of reduced pass configuration may be required to keep waterside pressure Figure 39 Parallel and Series Chiller Piping drop at an acceptable level. One-pass evaporators shown.

Future Expansion Arrangements Parallel chiller arrangement lends itself to future expansion because another chiller can simply be added to the “ladder.” Two chillers in a series cannot accommodate future expansion since pressure drop in the evaporator circuit would become too great with three chillers.

Distribution Systems

23

WATER PIPING AND PUMPS

Single Water-Cooled Chiller Loop Shown is a single chiller system. It is important to maintain minimum chilled water loop volumes as discussed previously as a single chiller system is often where a loop volume deficiency can exist. Note that the chilled-water pump pushes water through the chiller then out to the coils. The heat energy from the pump will be cooled in the chiller evapora- Figure 40 tor before being recirculated to Single Water-Cooled Chiller System Piping, the coils. Two-pass evaporator and condenser shown.

Multiple Water-Cooled Chiller Loop with Dedicated Pumps In this parallel chiller scheme, there is a dedicated pump for each cooling tower cell and chiller. When chilled water pumps are piped as shown, each chiller is interlocked to its respective pump. The operation of an individual chiller is dependent on the operation of its pumps and tower fan.

Figure 41 Multiple Water-Cooled Chillers, Dedicated Pumps Two pass evaporator and condensers shown.

Distribution Systems

24

WATER PIPING AND PUMPS

Multiple Water-Cooled Chillers with Manifolded Pumps When chilled water pumps are manifolded as shown, a condition will exist when one chiller is off and the other is running where there would be flow through the off chiller. To eliminate this problem, a 2position isolation valve must be added to shutoff flow when the chiller is deenergized. The advantage of this arrangement is that either pump can operate with either chiller. A third pump could even be added as a standby if so desired. Manifolded Pumps Balancing It is easier to balance a manifolded pumping arrangement when the chillers are equally sized.

Figure 42 Multiple Water-Cooled Chillers, Manifolded Pumps, Two-pass evaporators and condensers shown.

Primary-Secondary Chilled Water System In a primary-secondary system, each parallel-piped chiller in the primary loop starts/stops with its dedicated pump. Flow for each chiller in the primary loop is maintained by water circulating through the chillers and back through the bypass which acts as a hydraulic decoupler line, or “bridge.” Water can flow in either direction within the bridge depending on which flow is greater at any one point in time, the primary flow or the secondary flow.

Figure 43 Primary-Secondary Piping System, One-Pass Evaporators Shown.

A primary-secondary chilled-water piping system is a traditional way of piping the chilled water loop for larger multi-chiller projects. It has been in use for decades and accomplishes isolation of the primary (production) loop from the secondary (building system) loop. This allows control of the chillers and air handlers in the same piping system. The primary loop is contained within the mechanical equipment room (MER) and is often very short. The secondary loop runs throughout the building and serves the coil loads.

Distribution Systems

25

WATER PIPING AND PUMPS

When the primary flow exceeds secondary flow, water flows from discharge to suction in the bridge. When the secondary flow exceeds primary flow, water flows from suction to discharge in the bridge. Usually, variable-speed drives are used on the secondary pumps to match secondary pump flow to coil load flow demand. These pumps are the large, high-head pumps serving the entire system. When VFDS are used, two-way control valves are used on the coils on the load side of the system. The pump station is often a lead-lag pump arrangement with only one pump operating at any one point in time. This provides standby and ability to equalize pump operating hours. Check valves are needed for each secondary pump to prevent water circulating backward through the idle secondary pump. Many designers like to place a 3-way control valve with a bypass on one of the coils to be used as a safety valve for low flow just in case the VFD control fails. As the two-way coil control valves close off, less water is pumped through the secondary circuit and the secondary loop pressure rises. This would normally mean that the primary pumps would be starved for water if there wasn’t a bypass line. However, the flow not needed by the secondary pumps moves from discharge to suction through the bridge and returns to the primary pumps thereby insuring a constant primary loop flow to the active chiller(s). During startup conditions, the coil control valves might all go wide open and the secondary pump will pump more than the design flow provided by the primary loop. If this happens, water flows the opposite way in the bridge line. The extra water not needed by the primary loop passes from bottom to top in the bridge and back to the secondary pump. The hydraulic decoupler (bridge) line is typically sized for the flow rate required by the largest chiller and should not exceed a pressure drop of 1.5 ft wg. It should be a minimum of 3-5 pipe diameters long. For simplicity, the bypass line is often sized the same size as the main supply and return lines, provided it does not exceed the stated criteria for pressure loss.

Primary-Only, Variable-Flow Chilled Water System Primary-only, variableflow systems take advantage of the ability to modulate the flow through the chiller evaporator and eliminate the need for two sets of pumps (primary and secondary) and instead use a single set of pumps equipped with VFDs. Variable flow systems have become more popular on primary- secondary systems since there are Figure 44 fewer pumps to buy so Primary-Only Variable-Flow System, floor space is saved, along One-Pass Evaporators Shown. with first cost.

Distribution Systems

26

WATER PIPING AND PUMPS

Maximum Capacity of Chillers With a variable primary water flow, the chillers can be “over-pumped” with the VFD as a means of achieving maximum capacity. Normal return water temperature and flow rate may not load them 100 percent. For a discussion on maximum capacity, refer to TDP 623, Water-Cooled Chillers.

Two-way control valves are used on the coils and a bridge line is still used and is sized for the minimum flow rate through the largest chiller. A control valve (traditionally controlled by a precision flow meter) is used in the bridge to ensure that the minimum flow rate always returns to the operating chiller(s).

It is important to understand, however, that there are still limitations on the amount of flow variability. Specifically, the manufacturer’s recommended chilled water flow range must still be respected as well as the rate of change of flow. As a rule of thumb, the minimum evaporator flow rate should not fall below approximately 40 percent to prevent laminar flow. This means that Staging Chillers flow may be modulated from 100 percent down to 40 percent, resulting in energy savings as the pump energy is More recently, it has been found related to speed by the cube of the ratio of speeds. The better to stage chillers on actual DDC controls must also limit the rate of flow change to load, not flow rate, since flow is adhere to manufacturer’s recommendations. The chiller not necessarily a true indicator manufacturer should be contacted for specific chiller ap- of load. To do this, temperature sensors in the supply and the plication guidelines when designing a primary-only return lines, coupled with flow variable flow system. For specific recommendations on meters, are used to calculate variable flow through evaporators, refer to TDP-622, Air- actual load with DDC software. Cooled Chillers, and TDP-623, Water-Cooled Chillers. Since a primary variable system is inherently more complicated than the traditional primarysecondary system, the operating staff must be trained specifically on how to maintain and operate the variable flow arrangement. If the installation is in a remote area, or a fail-safe design is required, it is probably better to use a traditional primary-secondary system. If a primary-only, variable flow system is used, an accurate measurement of the return flow rate is essential to stable, reliable operation. This means a precision flow meter is necessary.

Chiller Head Pressure Control Overnight cooling of the tower and condenser water loop can produce temperatures below 55º F upon start-up. Chillers are designed to operate at condenser water temperatures 55º F and above. Consequently, a bypass is required to maintain an acceptable water temperature so that the chiller will not shut down upon startup.

Distribution Systems

27

WATER PIPING AND PUMPS

Head Pressure Control Piping Methods with Diverting Valve There are three piping configurations that can be used to control the condensing pressure and temperature in the water-cooled chiller condenser when used on a recirculating cooling tower loop. The first two methods utilize a diverting valve. The third method utilizes either a modulating valve or a VFD to vary the flow rate in the condenser. Method one locates the condenser water pump “outside” the bypass line such that flow rate will be constant through the cooling tower regardless of diverting valve position. In this scheme, during periods where head pressure control may be required, such as morning start up, the chiller condenser will experience lower flow. These lower flow rates can used to Figure 45 maintain acceptable condensing pres- Chiller Head Pressure Control with 100% Tower Flow sures. Two-pass condenser shown. Tower manufacturers typically prefer control schemes that maintain constant tower flow so that the fill in the tower can be fully wetted during operation. That way predictable heat transfer in the tower is assured. Reduced flows in the condenser can result in increased fouling in the tubes over time. Method two locates the condenser water pump “inside” the bypass line such that flow rate will be constant through the chiller condenser regardless of diverting valve position. In this scheme, during periods where head pressure control may be required, the cooling tower will experience a reduction in flow. The chiller manufacturer recommends this scheme, because full flow is maintained in the condenser.

Figure 46 Chiller Head Pressure Control with 100% Condenser Flow, Two-pass condenser shown.

Distribution Systems

28

WATER PIPING AND PUMPS

Head Pressure Control Piping Method with VFD or Modulating Valve Method three uses a modulating valve to vary the flow in the condenser. The reduced flow rate through the condenser results in less heat transfer and the saturated condensing temperature stabilizes. The flow through the condenser water pump and cooling tower also varies as the system head varies due to the change in valve position. The valve will modulate with the variation in water temperature to maintain the desired saturated condensing temperature. In this design, the condenser pump will “ride the curve” because the condenser flow will vary. A VFD can also be used to control the flow directly from a head pressure control signal from the chiller. This method varies the flow through both the condenser and cooling tower and is not as common as the Figure 47 other two methods using diverting Chiller Head Pressure Control Using VFD or Modulating Valve valves. Two-pass condenser shown.

Variable Condenser Flow If flow rate is varied through the condenser, it is paramount to respect the on-board chiller safeties such as high condensing temperature. As a general rule, variable condenser flow is not the norm for chiller operation. This is especially true on centrifugal chillers that are dependent on head pressure reductions at part load. In centrifugals, reduced condenser flows may elevate head pressures, resulting in loss of efficiency and possible chiller instability.

Pump Basics and Types of Pumps After the piping system has been laid out, and the total pressure loss, or head, for the pumps is calculated, the selection of pumps can be made. However, a basic understanding of pump terminology is required. In this TDP module we will concentrate on centrifugal pump designs which are the most common types used in comfort air conditioning. Capacity Capacity is the amount of liquid that can be pumped, given in terms of gallons per minute (gpm).

Distribution Systems

29

WATER PIPING AND PUMPS

Head Head (hd) is an energy unit that is usually expressed in feet of the liquid being pumped. In a closed system, friction is the only loss or head that the pump has to overcome. The height of water on the suction side of the pump is always exactly equal to the height of the discharge side piping. In open systems this is not true, there is always a difference in head between the suction side and discharge side of the pump. In a cooling tower for in- Figure 48 stance, the height between the water Pumping Head Examples level in the basin and the exit from the distribution nozzles at the top of the tower represents the unbalanced head that must be overcome by the pump. If the distribution system consists of spray nozzles that require a specific pressure to force water through the nozzles, this pressure must be added to the static head also. The total head of the pump will consist of the following: pipe friction loss, valves including control valves, accessories, equipment such as coolers, condensers coils, air separators, etc., and any unbalanced head. If you have a high-rise building, the static head can impose significant pressure on the system components. Example – A 50-story building with 12-ft between floors would be 600 ft. high. Since 2.31 ft. equals 1 psi, the pressure on the components at the lowest level would be 600 ft./2.31 ft/psi = 260 psi. The system components at the lowest elevation must be designed for this pressure. In this example, the chiller “waterboxes” would have to be constructed to accommodate 260 psi. If the cooling tower was on the roof, the condenser waterboxes would have to be 300 psi rated as well. If the cooling tower was ground-mounted, the condenser waterbox could be standard construction. Discharge Head Discharge head is the head at the pump discharge, made up of the static head at the pump outlet, any positive static pressure in the discharge side of the system, discharge pipe friction loss, and any equipment pressure drop. A pump discharge pressure gauge would indicate total discharge head. Suction Head Suction head is the head indicated on a pressure gauge at the pump suction. In a closed-loop system it would be the remaining discharge pressure after subtracting all the piping friction, and the valve and equipment losses. In an open-loop system, suction head includes static head (or lift), entrance loss and friction head in the suction piping, and any positive pressure existing on the suction side. With a closed-loop system in operation, a pressure gauge at the pump suction would indicate a positive suction head. On an open-loop system the gauge would read negative if the pump was above the fluid source being pumped. Liquid Horsepower Liquid horsepower is obtained by the formula, gpm ∗ hd ∗ sp gr ÷ 3960 (for standard water sp gr =1.0), where 3960 converts the equation units into horsepower (33,000 ft ∗ lb per minute, divided by 8.33 lb per gallon).

Distribution Systems

30

WATER PIPING AND PUMPS

Brake Horsepower Brake horsepower (bhp) is the power required to drive the pump and equals the liquid horsepower divided by the overall efficiency of the pump. Net Positive Suction Head Net positive suction head (NPSH) is equal to the pressure drop in ft wg of the liquid from the suction flange to the point inside the impeller where pressure starts to rise. NPSH available at the pump suction for the actual application must always be greater than the NPSH required for the pump used. Failure to do so would allow fluid vaporization within the pump (cavitation). Cavitation can cause impeller Figure 49 failure, shaft failure and/or seal fail- Net Positive Suction Head at Pump Inlet ures. To check the available NPSH at the pump suction flange in a given system, use the following formula:

NPSH = 2.31(Pa − Pvp ) + (H s − H f

)

NPSH

If using a fluid other than water use the following formula:

NPSH =

2.31(Pa − Pvp ) sp gr

+ (H s − H f

)

Net positive suction head does not tend to be an issue in closed-loop piping systems. In open-loops, if the pump is elevated above the cooling tower basin, it is prudent to check the NPSH requirements of the pump.

Where: NPSH =

net positive suction head

2.31

=

conversion factor to change 1 psi to pressure head in ft of water

Pa

=

atmospheric pressure (absolute pressure, psia)

Pvp

=

vapor pressure corresponding to water temperature at the pump suction. For water returning from a cooling tower at 85º F it is 0.59648, for 86º F water it is 0.61585.

Hs

=

elevation head, static head (ft) above or below the pump suction. (If above, positive static head; if below, negative static head, sometimes termed suction lift.)

Hf

=

friction head (ft), loss in suction line. Must include entrance loss and pressure drop through valves and fittings.

sp gr

=

specific gravity of the fluid being pumped

Distribution Systems

31

WATER PIPING AND PUMPS Figure 50 shows a cross-section of a typical pump. This figure is of a centrifugal inline pump, which gets its name from the straight inlet and discharge water flow. Other centrifugal pump designs will be discussed later in the TDP Module. The figure shows six components of a typical pump: the motor, coupler, bearings, pump shaft, mechanical seal, and the impeller. The motor is typically an opendrip proof type provided by the pump Figure 50 manufacturer and selected specifically Typical Pump Cross-Section for the head and flows required. A coupler mechanism is provided to attach the pump shaft to the motor assembly. Specifically designed bearings are utilized to provide constant circulation of oil over all bearing surfaces. The pump shaft serves the purpose of transmitting the motor torque to the impeller. A mechanical seal is required to prevent water from entering the motor and bearing compartment. The impeller moves the water through the pump assembly. It is selected specifically for the flow and head required for the application.

Pump Curve The optimal pump curve for an air-conditioning application is shown here. The very steep curve is not desirable for HVAC duty because it can lead to surging at low flow rates. The very flat curve can be an issue because large flow rate changes occur with small changes in the head. Important items to understand about pumps are: 1. Varying the speed – proportion- Figure 51 ally raises or lowers the head Pump Curve Examples and capacity. The whole head curve shifts up or down. 2. Varying the impeller diameter – proportionally raises or lowers the head and capacity. The whole head curve shifts up or down. Increasing the impeller size raises the head and capacity. 3. Varying the impeller diameter – proportionally varies the capacity.

Distribution Systems

32

WATER PIPING AND PUMPS

4. Varying the pitch and number of vanes within the impeller changes the shape of the head capacity curve. 5. Varying the impeller and vane designs produce variations in head-capacity relationships. Narrow impellers with larger impeller-to-eye diameter ratios develop a larger head. Wide impellers with low diameter ratios are used for low heads and large flows. Changes in speed and impeller diameters are reflected in pump performance as follows: 2

⎛ bhp1 ⎞ rpm1 impeller dia.1 gpm1 ⎛ head1 ⎞ ⎟⎟ = ⎜⎜ ⎟⎟ or = = ⎜⎜ rpm2 impeller dia.2 gpm2 ⎝ head 2 ⎠ ⎝ bhp 2 ⎠

3

A given pump operates along its own head-capacity curve. It is a centrifugal device just like a fan. At full capacity flow, the operating point falls at the crossing of the pump head-capacity curve and the system head curve (Point 1). If the pressure drop increases the system curve and the operating point moves up the head-capacity curve (Point 2, reduced water flow). If a greater flow is desired, the pressure drop must be reduced and the operating point would move down the curve (Point 3) or the pump could be speeded up, Figure 52 or the impeller size increased which would move the head capacity curve Pump and System Curve Intersection upward (Point 4). These performance characteristics are just like a fan in a duct system. If the system head is overestimated and the pump is selected with a high head-capacity curve, unfortunate results may occur. The pump will operate on its head-capacity curve to produce an increased flow at decreased head and increased horsepower demand (Point 1). The system head should always be calculated without undue safety factors or as close as practical to the true values to eliminate possible waste of horsepower or possible overloading of pump motor with an unvalved system. If not sized properly, the balancing valve on the pump discharge may have to be throttled or the impeller size decreased to achieve the desired flow. This is especially true when evaluating system head on a system designed with parallel or series Figure 53 pumps. Overestimating Pump Head

Distribution Systems

33

WATER PIPING AND PUMPS

Parallel Pumps Parallel pump operation is most common in HVAC and results in multiple gpm capacities against a common head. Example: Two pumps selected at 120 gpm at 50 ft of head will produce 240 gpm at 50 ft of head. Parallel pump application is for systems requiring high capacity with a relatively low head or for systems where a number of small pumps handle the load with one or more pumps shutting down as required. The pumps should have matched characteristics and the motor should have ample power to avoid overloading when operated singly. Parallel Pumps Parallel pumps can provide a high degree of redundancy because there are multiple pumps on the same system. When only one pump of a twopump system is operational, the decreased head results in a flow of about 60 percent of total. That is because the system resistance has changed and the active pump can produce more flow. Parallel pumps should be selected of equal size.

Figure 54 Parallel Pump Characteristics

Series Pumps Identical series pumps are used if very high head is required as the flow rate is the same as for each individual pump, but the head is additive. A single higher rpm pump (i.e. 3500 rpm) could be selected, but the redundancy value of dual pumps would be lost. Series Pumps Series pump applications are less common in HVAC applications because a single pump can usually develop enough head.

Figure 55 Series Pump Characteristics

Distribution Systems

34

WATER PIPING AND PUMPS

Variable Speed Pumping Variable speed pumping is very common. A pump with a VFD operates much like a fan with a VFD. A differential pressure sensor located near the end-of-run in the piping system sends a signal to the VFD to slow down the pump rpm if pressure in the piping is rising, or increase the rpm if the pressure is falling from set point. The pump moves its rpm along the system curve resulting in variations in flow rate. Energy savings are excellent at reduced flow rates as the bhp follows the cube ratio of the rpm.

bhp 2

⎛ rpm 2 = bhp1 ∗ ⎜⎜ ⎝ rpm1

⎞ ⎟⎟ ⎠

3

Figure 56 Variable Speed Pumping Characteristics

Selection Pumps should be selected based on design, size, service, and performance. In terms of performance, a pump should be selected to provide the required flow rate at the design head while trying to achieve the lowest possible horsepower. Pump catalogs, with pump performance curves, allow the proper pump to be selected. Most pump manufacturers also have software programs that can select the optimal pump for your application. The following is an example of a pump selection from a manufacturer’s program.

Figure 57 Typical Centrifugal Pump Selection Screen Capture Courtesy of Bell & Gossett

Distribution Systems

35

WATER PIPING AND PUMPS

Centrifugal Pump Types There are several types of centrifugal pumps used in the HVAC industry, such as inline, close-coupled, end suction, vertical split case, and horizontal split case. Which type of pump to use is determined by the flow rate and head requirements, available space, serviceability and cost. The Pump Type Comparison chart below shows the ranking of each type of pump for each category.

Figure 58 Types of Centrifugal Pumps Photos courtesy of Bell & Gossett

Pump Type

Cost

Flow & Head Capability

Space Required

Ease of Service

In Line

Least 1

200 gpm @ 55 ft

Least 1

Poor 5

CloseCoupled

2

2,300 gpm @ 400 ft

2

4

End Suction

3

4,000 gpm @ 500 ft

3

1

Vertical Split Case

4

9,000 gpm @ 400 ft

4

2

Horizontal Split Case

Highest 5

40,000 gpm @ 600 ft

Most 5

Good 3

Figure 59 Pump Type Comparison

Distribution Systems

36

WATER PIPING AND PUMPS

Pipe Sizing and Pump Selection Example Steps 1-7 use a condenser water piping loop as the example system. Step 8 is for sizing the chilled-water piping loop. Once the piping system with all pipe routing, piping accessories, and equipment has been drawn and the flow rate for each piece of equipment has been determined, it becomes necessary to size the piping. Sizing of the piping will allow the total resistance (head) in the system to be determined so the pumps can be selected.

Step 1: Determine Water Velocity in Piping Pipe size is limited by velocity based on noise and pipe erosion considerations. Both sound and erosion increase as the velocity increases. The table below gives recommended velocity limits, which are based on experience and Recommended Water Velocities are designed to give good balance between pipe size and system life. Service Velocity Range (fps)

Water Velocity For our first example, sizing the condenser water piping on a single chiller system we will stay between 5 and 10 fps.

Pump discharge Pump suction Drain line Header Mains and Riser Branches and Runouts City water

8 to 12 4 to 7 4 to 7 4 to 15 3 to 10 5 to 10 3 to 07

Figure 60 Recommended Water Velocities

The header pipe is close to the pump and carries fluid to the mains and risers. Mains (horizontal) and risers (vertical) distribute the fluid to the various areas of the building where branches and runouts feed the water flow to the air terminals, fan coils, baseboard, etc.

Step 2: Determining Piping Friction Losses Friction Loss rate for pipe can be found by using Charts 1, 2 and 3, which are found in the Appendix. Charts 1 and 2 are normally used for larger size steel pipes, >2 ½-in., and Chart 3 is usually for smaller pipes,